  • The Kuangya VKL001 RCCB مرحلة واحدة device disconnects circuits upon residual current, preventing electric shock and fire hazards.

  • 2P / 4P options; In 16–100 A; IΔn 10/30/100/300 mA; Ue 240 V (2P) / 415 V (4P); Inc = IΔc up to 10 kA; Uimp 6 kV.

  • Compliant with IEC/EN 61008-1; approvals: SEMKO, UKCA, CE.

احصل على عرض أسعار

التصنيف:

لمحة عامة

The VKL001 RCCB مرحلة واحدة (also available for three-phase boards as 4P) detects earth-leakage
currents and trips before harm occurs, providing protection for people and installations. It is widely applied in
housing, the tertiary sector, and industry. Selection covers rated currents from 16 A to 100 A and residual
sensitivities from 10 mA to 300 mA.

Detection classes & selection

  • AC class — trips for slowly increasing sinusoidal AC residual currents, whether applied slowly or suddenly.
  • A class — all AC features plus tripping for pulsating DC residual currents, whether applied suddenly or increasing slowly.
  • High-immunity variants (Si/G/KV) — filters against spurious tripping caused by harmonics and transient surges; stable under 8/20 μs surge of 3000 A (per datasheet note).

Tripping sensitivity & time

  • 10 mA — precision instrument leakage protection and bathroom use (available on 2P/4P 16–40 A).
  • 30 مللي أمبير — additional protection against direct contact.
  • 100 مللي أمبير — coordinated with the earthing system for indirect contact protection.
  • 300 mA — protection against indirect contacts and fire hazards.
  • Instantaneous — tripping without intentional delay; break time under IΔn (Normal) ≤ 100 ms.
  • تأخير زمني قصير (Si, G, KV) — ensures any tripping at least 10 ms (10–300 ms range).
  • Selective (S) — 150–500 ms, ensures discrimination with a downstream non-selective RCD.

Key features

  • Configurations: 2 ف-2/ف-4; top or bottom supply; any mounting position.
  • Rated current In: 16, 25, 32, 40, 63, 80, 100 A.
  • Rated sensitivity IΔn: 10 مللي أمبير (2P/4P 16-40 أمبير)، 30 مللي أمبير، 100 مللي أمبير، 300 مللي أمبير.
  • Rated voltage Ue: 2P: 240 V~; 4P: 415 V~. يو آي 500 V. التردد: 50/60 هرتز.
  • التصنيع والكسر المتبقي (IΔm): 500 A (In 16–40 A); 630 A (63 A); 800 A (80 A); 1000 A (100 A).
  • دائرة قصر مشروطة (Inc = IΔc): 6000 A or 10000 A (with upstream SCPD coordination).
  • الصمود الدافع (Uimp): 6 كيلو فولت; اختبار العزل الكهربائي: 2.5 kV (1 min at power frequency).
  • القدرة على التحمل: ≥ 20,000 mechanical operations / ≥ 2000 electrical operations.
  • Terminal protection degree: IP20; Fault current indicator: نعم.
  • Ambient: −25 °C … +55 °C (daily avg ≤ 35 °C); Storage: −40 °C … +70 °C.
  • المحطات الطرفية: cable / pin-type busbar; sizes (cable): 25–35 mm²; 18–3 / 18–2 AWG; sizes (busbar): 10/16 mm²; 18–8 / 18–5 AWG.
  • عزم دوران الشد: 2.5 N·m (≈ 22 in-lbs).
  • التركيب: DIN rail EN 60715 (35 mm), fast clip device; connection from top and bottom.
  • Standards & approvals: IEC/EN 61008-1; SEMKO, UKCA, CE.

Technical Data (full table)

قياسيIEC/EN 61008-1
رقم الموديل.VKL001
الأعمدة2 ف، 4 ف، 2 ف، 4 ف
التيار المقدر (في)16A، 25A، 32A، 40A، 63A، 80A، 100A، 100A
الحساسية المقدرة (IΔn)10 mA (2P/4P 16–40 A), 30 mA, 100 mA, 300 mA
الجهد المقنن (Ue)2 فولت: 240 فولت~؛ 4 فولت: 415 فولت~
جهد العزل (Ui)500 V
Rated frequency (fn)50/60 هرتز
Rated residual making & breaking (IΔm)500 A (In = 16–40 A); 630 A (In = 63 A); 800 A (In = 80 A); 1000 A (In = 100 A)
Conditional short-circuit current (Inc = IΔc)6000 A; 10000 A
النوع (الشكل الموجي المستشعر)تيار متردد، أ
Tripping time (Instantaneous)Break time under IΔn ≤ 100 ms
Tripping time (Short time delay)10–300 ms (Si, G, KV types)
Tripping time (Selective S)150–500 ms
الصمود الدافع (Uimp)6 كيلو فولت
Dielectric test voltage2.5 kV (1 min)
درجة التلوث2
الحياة الكهربائية≥ 2000 operations
الحياة الميكانيكية≥ 20,000 operations
مؤشر تيار العطلنعم
درجة الحماية الطرفيةIP20
درجة الحرارة المحيطة−25 °C to +55 °C (daily avg ≤ 35 °C)
درجة حرارة التخزين-40 درجة مئوية إلى +70 درجة مئوية
نوع التوصيل الطرفيكابل / قضيب ناقل من نوع دبوس
Terminal size (cable)25–35 mm²; 18–3 / 18–2 AWG
Terminal size (busbar)10/16 mm²; 18–8 / 18–5 AWG
عزم دوران الشد2.5 نيوتن-متر (≈ 22 بوصة-رطل)
التركيبDIN rail EN 60715 (35 mm), fast clip
الاتصالTop and bottom
الموافقاتSEMKO, UKCA, CE

التطبيقات

  • Single-phase boards requiring an RCCB مرحلة واحدة device at 240 V~ (2P).
  • Three-phase distribution at 415 V~ (4P) with coordination for 6/10 kA conditional short-circuit.
  • Loads with electronics and frequent transients — use high-immunity variants (Si/G/KV) to reduce nuisance trips.

rccb single phase VKL001 Kuangya 2P/4P 16–100A 10/30/100/300 mA

المراجعات

لا توجد مراجعات بعد.

كن أول من يقيم “RCCB VKL001 — Residual Current Circuit Breaker”

لن يتم نشر عنوان بريدك الإلكتروني. الحقول الإلزامية مشار إليها بـ *