Kuangya AC MCBs protect branch circuits against overloads and short circuits in residential, commercial, and light-industrial panels. The range covers single-pole to four-pole configurations with B, C, or D tripping curves to match load characteristics from lighting and socket circuits to motor and transformer feeders. Tool-free DIN-rail mounting, front wiring access, and compact footprints simplify new installations and retrofits alike.
| パラメータ | Typical Value / Options |
|---|---|
| Standards (design) | IEC 60898-1 (domestic, final circuits); IEC 60947-2 (industrial, by model) |
| Rated Voltage Ue | 230/400 VAC, 50/60 Hz |
| Rated Current In | 6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 A (by model) |
| 破断能力 | 6 kA or 10 kA at 230/400 VAC (by model) |
| Tripping Curve | B / C / D |
| ポール | 1P / 2P / 3P / 4P |
| Dielectric Test | 2.5 kV, 1 min (typ.) |
| Impulse Withstand Uimp | 4 kV (typ.) |
| Insulation Category | Pollution degree 2; overvoltage category III |
| ターミナル容量 | Up to 25 mm² Cu (typ.), tightening torque 2.5 N·m (≈22 in-lb) |
| Protection Degree | IP20 (terminals) when installed |
| 取り付け | DIN rail EN 60715, top/bottom feed |
| Ambient | −25…+55 °C operation (typ.), ≤2000 m altitude |
| Materials | Thermoset/thermoplastic housing; copper alloy terminals |
| Options | Aux/Alarm contacts (OF/SD), handle lock, phase barriers (by model) |
B trips at 3–5× In (resistive loads), C at 5–10× In (mixed/inductive), D at 10–20× In (high inrush: motors, transformers).
Match the breaking capacity to the prospective short-circuit current at the installation point; many commercial panels require 10 kA.
No; use DC-rated breakers for direct current systems due to different arc behavior and polarity considerations.
Yes, auxiliary/alarm contacts are available on selected models; check the datasheet for part numbers.
They are designed according to IEC 60898-1 and/or IEC 60947-2 depending on model; compliance/marking is model-specific.