エムシービー

AC MCB — Miniature Circuit Breakers

  • Compact protection for 230/400 VAC distribution — B/C/D curves, 6–125 A (by model).
  • 6 kA / 10 kA breaking capacity options; DIN rail EN 60715; IP20 finger-safe terminals.
  • Designed according to IEC 60898-1 (final circuits) and IEC 60947-2 (industrial, by model).

概要

Kuangya AC MCBs protect branch circuits against overloads and short circuits in residential, commercial, and light-industrial panels. The range covers single-pole to four-pole configurations with B, C, or D tripping curves to match load characteristics from lighting and socket circuits to motor and transformer feeders. Tool-free DIN-rail mounting, front wiring access, and compact footprints simplify new installations and retrofits alike.

主な特徴

  • Ratings: 6–125 A (by model), 230/400 VAC, 50/60 Hz.
  • Breaking capacity: 6 kA or 10 kA at 230/400 VAC (by model).
  • Tripping curves: B (resistive), C (mixed/inductive), D (high inrush).
  • Poles: 1P / 2P / 3P / 4P with common trip.
  • Terminal capacity: up to 25 mm² Cu (typ.), captive screws; IP20 finger-safe.
  • Endurance: ≥ 10,000 mechanical operations (typ.); high electrical life for frequent switching (by curve).
  • Standards: designed according to IEC 60898-1 and IEC 60947-2 (model dependent).
  • Mounting: DIN rail EN 60715, top/bottom feed, padlockable handle options (by model).
  • Ambient: −25…+55 °C (typ.), storage −40…+70 °C; altitude ≤ 2000 m (typ.).
  • Accessories: auxiliary contacts / alarm (by model), phase barriers, label window.

Technical Specifications

パラメータTypical Value / Options
Standards (design)IEC 60898-1 (domestic, final circuits); IEC 60947-2 (industrial, by model)
Rated Voltage Ue230/400 VAC, 50/60 Hz
Rated Current In6, 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 A (by model)
破断能力6 kA or 10 kA at 230/400 VAC (by model)
Tripping CurveB / C / D
ポール1P / 2P / 3P / 4P
Dielectric Test2.5 kV, 1 min (typ.)
Impulse Withstand Uimp4 kV (typ.)
Insulation CategoryPollution degree 2; overvoltage category III
ターミナル容量Up to 25 mm² Cu (typ.), tightening torque 2.5 N·m (≈22 in-lb)
Protection DegreeIP20 (terminals) when installed
取り付けDIN rail EN 60715, top/bottom feed
Ambient−25…+55 °C operation (typ.), ≤2000 m altitude
MaterialsThermoset/thermoplastic housing; copper alloy terminals
OptionsAux/Alarm contacts (OF/SD), handle lock, phase barriers (by model)

寸法

AC MCB 1P — Outline & mounting
AC MCB 3P/4P — Outline & mounting

アプリケーション

  • Residential distribution boards, lighting and socket circuits.
  • Commercial sub-panels, HVAC, small motors and pumps (curve C/D).
  • Control panels and OEM equipment requiring compact short-circuit protection.
  • Retrofits and upgrades from legacy breakers to DIN-rail form factor.

クアンヤを選ぶ理由

  • Factory-direct supply with ISO-based quality control and traceability.
  • Wide selection across poles, ratings and curves to fit standard panels.
  • Stable lead times and export packaging validated for global shipping.
  • OEM options on labeling, accessories and packing (by project).

よくあるご質問

What is the difference between B, C and D curves?

B trips at 3–5× In (resistive loads), C at 5–10× In (mixed/inductive), D at 10–20× In (high inrush: motors, transformers).

6 kA vs 10 kA — which should I choose?

Match the breaking capacity to the prospective short-circuit current at the installation point; many commercial panels require 10 kA.

Can I use AC MCBs on DC?

No; use DC-rated breakers for direct current systems due to different arc behavior and polarity considerations.

Do you offer auxiliary contacts?

Yes, auxiliary/alarm contacts are available on selected models; check the datasheet for part numbers.

Are these compliant with IEC standards?

They are designed according to IEC 60898-1 and/or IEC 60947-2 depending on model; compliance/marking is model-specific.