RCCB VKL001 - Disjuntor de corrente residual

  • The Kuangya VKL001 rccb monofásico device disconnects circuits upon residual current, preventing electric shock and fire hazards.

  • 2P / 4P options; In 16–100 A; IΔn 10/30/100/300 mA; Ue 240 V (2P) / 415 V (4P); Inc = IΔc up to 10 kA; Uimp 6 kV.

  • Compliant with IEC/EN 61008-1; approvals: SEMKO, UKCA, CE.

Obter uma cotação

Categoria:

Visão geral

The VKL001 rccb monofásico (also available for three-phase boards as 4P) detects earth-leakage
currents and trips before harm occurs, providing protection for people and installations. It is widely applied in
housing, the tertiary sector, and industry. Selection covers rated currents from 16 A to 100 A and residual
sensitivities from 10 mA to 300 mA.

Detection classes & selection

  • AC class — trips for slowly increasing sinusoidal AC residual currents, whether applied slowly or suddenly.
  • A class — all AC features plus tripping for pulsating DC residual currents, whether applied suddenly or increasing slowly.
  • High-immunity variants (Si/G/KV) — filters against spurious tripping caused by harmonics and transient surges; stable under 8/20 μs surge of 3000 A (per datasheet note).

Tripping sensitivity & time

  • 10 mA — precision instrument leakage protection and bathroom use (available on 2P/4P 16–40 A).
  • 30 mA — additional protection against direct contact.
  • 100 mA — coordinated with the earthing system for indirect contact protection.
  • 300 mA — protection against indirect contacts and fire hazards.
  • Instantaneous — tripping without intentional delay; break time under IΔn (Normal) ≤ 100 ms.
  • Short time delay (Si, G, KV) — ensures any tripping at least 10 ms (10–300 ms range).
  • Selective (S) — 150–500 ms, ensures discrimination with a downstream non-selective RCD.

Key features

  • Configurations: 2P / 4P; top or bottom supply; any mounting position.
  • Rated current In: 16, 25, 32, 40, 63, 80, 100 A.
  • Rated sensitivity IΔn: 10 mA (2P/4P 16–40 A), 30 mA, 100 mA, 300 mA.
  • Rated voltage Ue: 2P: 240 V~; 4P: 415 V~. Ui: 500 V. Frequency: 50/60 Hz.
  • Residual making & breaking (IΔm): 500 A (In 16–40 A); 630 A (63 A); 800 A (80 A); 1000 A (100 A).
  • Conditional short-circuit (Inc = IΔc): 6000 A or 10000 A (with upstream SCPD coordination).
  • Impulse withstand (Uimp): 6 kV; Dielectric test: 2.5 kV (1 min at power frequency).
  • Endurance: ≥ 20,000 mechanical operations / ≥ 2000 electrical operations.
  • Terminal protection degree: IP20; Fault current indicator: Yes.
  • Ambient: −25 °C … +55 °C (daily avg ≤ 35 °C); Storage: −40 °C … +70 °C.
  • Terminals: cable / pin-type busbar; sizes (cable): 25–35 mm²; 18–3 / 18–2 AWG; sizes (busbar): 10/16 mm²; 18–8 / 18–5 AWG.
  • Tightening torque: 2.5 N·m (≈ 22 in-lbs).
  • Mounting: DIN rail EN 60715 (35 mm), fast clip device; connection from top and bottom.
  • Standards & approvals: IEC/EN 61008-1; SEMKO, UKCA, CE.

Technical Data (full table)

PadrãoIEC/EN 61008-1
Model No.VKL001
Postes2P, 4P
Rated current (In)16A, 25A, 32A, 40A, 63A, 80A, 100A
Rated sensitivity (IΔn)10 mA (2P/4P 16–40 A), 30 mA, 100 mA, 300 mA
Rated voltage (Ue)2P: 240 V~; 4P: 415 V~
Insulation voltage (Ui)500 V
Rated frequency (fn)50/60 Hz
Rated residual making & breaking (IΔm)500 A (In = 16–40 A); 630 A (In = 63 A); 800 A (In = 80 A); 1000 A (In = 100 A)
Conditional short-circuit current (Inc = IΔc)6000 A; 10000 A
Type (waveform sensed)AC, A
Tripping time (Instantaneous)Break time under IΔn ≤ 100 ms
Tripping time (Short time delay)10–300 ms (Si, G, KV types)
Tripping time (Selective S)150–500 ms
Impulse withstand (Uimp)6 kV
Dielectric test voltage2.5 kV (1 min)
Pollution degree2
Electrical life≥ 2000 operations
Mechanical life≥ 20,000 operations
Fault current indicatorYes
Terminal protection degreeIP20
Ambient temperature−25 °C to +55 °C (daily avg ≤ 35 °C)
Storage temperature−40 °C to +70 °C
Terminal connection typeCable / Pin-type busbar
Terminal size (cable)25–35 mm²; 18–3 / 18–2 AWG
Terminal size (busbar)10/16 mm²; 18–8 / 18–5 AWG
Tightening torque2.5 N·m (≈ 22 in-lbs)
MontagemDIN rail EN 60715 (35 mm), fast clip
ConnectionTop and bottom
ApprovalsSEMKO, UKCA, CE

Aplicativos

  • Single-phase boards requiring an rccb monofásico device at 240 V~ (2P).
  • Three-phase distribution at 415 V~ (4P) with coordination for 6/10 kA conditional short-circuit.
  • Loads with electronics and frequent transients — use high-immunity variants (Si/G/KV) to reduce nuisance trips.