AFDD-1 아크 결함 감지 장치 | RCBO 기능으로 화재 방지

  • Arc-fault detection device (AFDD) with integrated overcurrent and residual current protection.

  • Rated current range: 6A-40A잔류 전류 유형 A, tripping curve B/C.

  • 다음 사항을 준수합니다. EN62606 & EN61009-1, short-circuit capacity 6kA.

견적 받기

카테고리:

개요

그리고 AFDD-1 Arc Fault Detection Device integrates 아크 결함 감지(AFDD),
과전류 보호(MCB)잔류 전류 보호(RCCB, A형) in one compact 1P+N module.
It complies with EN62606EN61009-1, providing early detection of series/parallel arc faults
and fast disconnection to reduce fire risks in residential, commercial and industrial installations.

특징

  • 3중 보호: AFDD + MCB + RCCB(Type A)
  • Rated short-circuit capacity: 6 kA; tripping curves: B/C
  • LED indication for device status & tripping reason; continuous self-monitoring
  • 컴팩트 1P+N(모듈 1개) design, screw terminals top/bottom
  • Strain-relief clamps, snap-in slider; easy mounting on 35mm DIN 레일
  • Mechanical endurance ≥ 20,000 cycles; Electrical endurance ≥ 4,000 cycles

기술 데이터

시리즈AFDD
모델AFDD-1
1P+N(1 모듈)
정격 전류(AC)6A, 10A, 13A, 16A, 20A, 25A, 32A, 40A
잔류 전류 유형유형 A
정격 잔류 전류 IΔn10mA, 30mA
최소/최대 테스트 회로 전압196V / 253V
트립 특성B, C
작동 주파수50Hz
임펄스 내전압(Uimp)4kV
정격 전압(AC)240 V
정격 단락 전류(Icn)6 kA
서지 전류 강도0.25 kA
최대 총 스위칭 용량6 kA
정격 절연 전압250 V
극당 열 손실3 W
단락 백업 퓨즈(SCPD)100 A (gG)
과전압 등급III
터미널나사형, 상단 및 하단(부하 회로)
중립 도체 위치왼쪽/오른쪽
최대 연결 케이블 길이70 m (DB to outer socket)
클램핑 영역1-25 mm²
조임 토크2.0-2.4 Nm
기계적 내구성≥ 20,000회 이상
전기적 내구성≥ 4,000회 이상
보관/작동 온도-35℃...+60℃ / -25℃...+40℃
하우징 유형 / 재질배전반 하우징 / 열가소성 플라스틱
마운팅DIN 레일(35mm)
보호 등급IP20(설치: IP40)
표준EN62606, EN61009-1
전력 제한 카테고리3
오염도(EN60664)2
인증UKCA, CE

애플리케이션

Fire protection for final circuits up to 40 A in residential, commercial and public buildings
(bedrooms, offices, hospitals, schools). Suitable for TN-STN-C-S networks.
Not suitable for TN-C systems or circuits with smooth DC residual currents not equal to 50 Hz.

인증

  • UKCA
  • CE
  • 표준 EN62606(AFDD), EN61009-1(RCBO)

자주 묻는 질문

What is the difference between AFDD and RCCB?

AFDD detects series/parallel arc faults to prevent fires; RCCB trips on residual (leakage) current. AFDD-1 integrates AFDD + MCB + RCCB in one device.

Can AFDD-1 be used in TN-C systems?

No. AFDD-1 is intended for TN-S and TN-C-S networks.

Which leakage types are detected?

Type A: sinusoidal AC and pulsating DC residual currents.