AFDD-1 Arc Fault Detection Device | Fire Protection with RCBO Function

  • Arc-fault detection device (AFDD) with integrated overcurrent and residual current protection.

  • Rated current range: 6A–40A잔류 전류 유형 A, tripping curve B/C.

  • 다음 사항을 준수합니다. EN62606 & EN61009-1, short-circuit capacity 6kA.

견적 받기

카테고리:

개요

그리고 AFDD-1 Arc Fault Detection Device integrates 아크 결함 감지(AFDD),
overcurrent protection (MCB)residual current protection (RCCB, Type A) in one compact 1P+N module.
It complies with EN62606EN61009-1, providing early detection of series/parallel arc faults
and fast disconnection to reduce fire risks in residential, commercial and industrial installations.

Features

  • Triple protection: AFDD + MCB + RCCB(Type A)
  • Rated short-circuit capacity: 6 kA; tripping curves: B/C
  • LED indication for device status & tripping reason; continuous self-monitoring
  • 컴팩트 1P+N (1 module) design, screw terminals top/bottom
  • Strain-relief clamps, snap-in slider; easy mounting on 35mm DIN 레일
  • Mechanical endurance ≥ 20,000 cycles; Electrical endurance ≥ 4,000 cycles

Technical Data

시리즈AFDD
모델AFDD-1
1P+N (1 Module)
Rated current (AC)6A, 10A, 13A, 16A, 20A, 25A, 32A, 40A
Residual current type유형 A
Rated residual current IΔn10 mA, 30 mA
Min./Max. test circuit voltage196 V / 253 V
Tripping characteristicB, C
Operating frequency50Hz
Impulse withstand voltage (Uimp)4 kV
Rated voltage (AC)240 V
Rated short-circuit current (Icn)6 kA
Surge current strength0.25 kA
Max. total switching capacity6 kA
Rated insulation voltage250 V
Heat loss per pole3 W
Short-circuit backup fuse (SCPD)100 A (gG)
Overvoltage classIII
TerminalsScrew-type, top & bottom (load circuit)
Neutral conductor positionLeft / Right
Max. connection cable length70 m (DB to outer socket)
Clamping area1–25 mm²
Tightening torque2.0–2.4 Nm
Mechanical endurance≥ 20,000 cycles
Electrical endurance≥ 4,000 cycles
Storage / Operating temperature-35℃…+60℃ / -25℃…+40℃
Housing type / materialDistribution board housing / Thermoplastic
마운팅DIN rail (35 mm)
Protection classIP20 (installed: IP40)
표준EN62606, EN61009-1
Power limitation category3
Pollution degree (EN60664)2
인증UKCA, CE

애플리케이션

Fire protection for final circuits up to 40 A in residential, commercial and public buildings
(bedrooms, offices, hospitals, schools). Suitable for TN-STN-C-S networks.
Not suitable for TN-C systems or circuits with smooth DC residual currents not equal to 50 Hz.

인증

  • UKCA
  • CE
  • Standards: EN62606 (AFDD), EN61009-1 (RCBO)

자주 묻는 질문

What is the difference between AFDD and RCCB?

AFDD detects series/parallel arc faults to prevent fires; RCCB trips on residual (leakage) current. AFDD-1 integrates AFDD + MCB + RCCB in one device.

Can AFDD-1 be used in TN-C systems?

No. AFDD-1 is intended for TN-S and TN-C-S networks.

Which leakage types are detected?

Type A: sinusoidal AC and pulsating DC residual currents.