The Kuangya KYSPD-T3-2P is a dedicated surge protective device type 3
designed for fine protection of sensitive equipment at the terminal level of electrical
systems. It is applied in 230 V single-phase networks, safeguarding electronics,
computers, communication devices, and control circuits against transient surges.Using MOV-based suppression elements, this SPD offers reliable performance
with fast response time, compact size, and DIN-rail installation.
Integrated thermal disconnectors and visible fault indicators ensure safety,
while optional RC contacts provide remote fault monitoring.主な特徴
- Type 3 SPD according to IEC/EN 61643-11 (Class III protection).
- Nominal discharge current (In): 3 kA (8/20 μs).
- Maximum discharge current (Imax): 6 kA (8/20 μs).
- Voltage protection level (Up): ≤ 1.0–1.5 kV depending on Uc.
- Response time < 25 ns for rapid surge suppression.
- Back-up fuse: max 32 A gL/gG; ISCCR 6 kA AC.
- Compact 2P design for terminal or downstream protection.
- Optional RC contacts for remote signaling (AC 250 V / 0.5 A; DC 250 V / 0.1 A).
- Housing IP20, UL94 V-0 thermoplastic; operating temperature -40 °C to +70 °C.
- 35 mm DIN rail mounting; IEC/EN 61643-11 compliant.
仕様
Product Code | KYSPD-T3-2P |
---|
Category | Surge protective device type 3 |
---|
Nominal System Voltage | 230 V AC |
---|
ポール | 2P (L+N) |
---|
Continuous Operating Voltage (Uc) | 275 V AC |
---|
Nominal Discharge Current (In, 8/20 μs) | 3 kA |
---|
Maximum Discharge Current (Imax, 8/20 μs) | 6 kA |
---|
Voltage Protection Level (Up) | ≤ 1.0–1.5 kV |
---|
応答時間 | < 25 ns |
---|
Back-Up Fuse (max) | 32 A gL/gG |
---|
Short-Circuit Current Rating (ISCCR) | 6 kA AC |
---|
動作温度 | -40 °C to +70 °C |
---|
取り付け | 35 mm DIN rail, EN 60715 |
---|
Enclosure / Protection | Thermoplastic UL94 V-0 / IP20 |
---|
Remote Signaling (RC) | Optional; AC 250 V / 0.5 A; DC 250 V / 0.1 A |
---|
規格 | IEC/EN 61643-11 |
---|
配線と寸法
Connection diagram surge protective device type 3 KYSPD-T3-2P

Dimensions surge protective device type 3 KYSPD-T3-2P
アプリケーション
- Protection of terminal equipment such as computers, routers, and servers.
- Applied in residential, commercial, and industrial single-phase panels.
- Supplementary fine protection coordinated with upstream Type 2 SPDs.
よくあるご質問
- What class is KYSPD-T3-2P? It is Class III, Type 3 SPD according to IEC/EN 61643-11.
- What is its discharge capacity? In 3 kA, Imax 6 kA.
- What applications is it designed for? Terminal-level protection of electronics in 230 V AC systems.
- Does it have remote signaling? Yes, optional RC contacts can be provided.
- What is the max backup fuse rating? 32 A gL/gG.
レビュー