AFDD-1 アーク故障検出装置|RCBO機能付き防火装置

  • Arc-fault detection device (AFDD) with integrated overcurrent and residual current protection.

  • Rated current range: 6A–40A残留電流タイプ A, tripping curve B/C.

  • 準拠 EN62606 & EN61009-1, short-circuit capacity 6kA.

お見積もり

カテゴリー:

概要

について AFDD-1 Arc Fault Detection Device integrates アーク故障検出(AFDD),
overcurrent protection (MCB) そして residual current protection (RCCB, Type A) in one compact 1P+N module.
It complies with EN62606 そして EN61009-1, providing early detection of series/parallel arc faults
and fast disconnection to reduce fire risks in residential, commercial and industrial installations.

Features

  • Triple protection: AFDD + MCB + RCCB(Type A)
  • Rated short-circuit capacity: 6 kA; tripping curves: B/C
  • LED indication for device status & tripping reason; continuous self-monitoring
  • コンパクト 1P+N (1 module) design, screw terminals top/bottom
  • Strain-relief clamps, snap-in slider; easy mounting on 35 mm DINレール
  • Mechanical endurance ≥ 20,000 cycles; Electrical endurance ≥ 4,000 cycles

技術データ

シリーズエーエフディー
モデルAFDD-1
ポール1P+N (1 Module)
Rated current (AC)6A, 10A, 13A, 16A, 20A, 25A, 32A, 40A
残留電流タイプタイプA
Rated residual current IΔn10 mA, 30 mA
Min./Max. test circuit voltage196 V / 253 V
Tripping characteristicB, C
Operating frequency50 Hz
Impulse withstand voltage (Uimp)4 kV
Rated voltage (AC)240 V
Rated short-circuit current (Icn)6 kA
Surge current strength0.25 kA
Max. total switching capacity6 kA
Rated insulation voltage250 V
Heat loss per pole3 W
Short-circuit backup fuse (SCPD)100 A (gG)
Overvoltage classIII
TerminalsScrew-type, top & bottom (load circuit)
Neutral conductor positionLeft / Right
Max. connection cable length70 m (DB to outer socket)
Clamping area1–25 mm²
締め付けトルク2.0–2.4 Nm
Mechanical endurance≥ 20,000 cycles
Electrical endurance≥ 4,000 cycles
Storage / Operating temperature-35℃…+60℃ / -25℃…+40℃
Housing type / materialDistribution board housing / Thermoplastic
取り付けDIN rail (35 mm)
Protection classIP20 (installed: IP40)
規格EN62606, EN61009-1
Power limitation category3
Pollution degree (EN60664)2
認証UKCA, CE

アプリケーション

Fire protection for final circuits up to 40 A in residential, commercial and public buildings
(bedrooms, offices, hospitals, schools). Suitable for TN-S そして TN-C-S networks.
Not suitable for TN-C systems or circuits with smooth DC residual currents not equal to 50 Hz.

認証

  • UKCA
  • CE
  • Standards: EN62606 (AFDD), EN61009-1 (RCBO)

よくあるご質問

What is the difference between AFDD and RCCB?

AFDD detects series/parallel arc faults to prevent fires; RCCB trips on residual (leakage) current. AFDD-1 integrates AFDD + MCB + RCCB in one device.

Can AFDD-1 be used in TN-C systems?

No. AFDD-1 is intended for TN-S and TN-C-S networks.

Which leakage types are detected?

Type A: sinusoidal AC and pulsating DC residual currents.

レビュー

レビューはまだありません。

“AFDD-1 Arc Fault Detection Device | Fire Protection with RCBO Function” の口コミを投稿します

メールアドレスが公開されることはありません。 が付いている欄は必須項目です