OF reports breaker position. SD reports a trip. On supported models, SDE identifies an electrical fault trip. Use trip-unit diagnostics, where available, to investigate the specific cause.
In Schneider Electric’s ComPact NSX DC user guide, OF indicates main contact position. SD indicates a trip, including operation by a shunt trip or undervoltage release, the push-to-trip button, or the trip unit. SDE indicates a trip due to an electrical fault detected by the trip unit. These definitions describe the cited product and configuration. Other families can use different labels or support fewer functions.
| What the operator needs to know | Signal to look for | What to confirm |
|---|---|---|
| Is the breaker open or closed? | Position indication, such as OF | Contact state in ON, OFF and tripped conditions |
| Did the breaker trip? | Trip indication, such as SD | Which releases and test operations activate it |
| Did the trip unit detect an electrical fault? | Electrical fault indication, such as SDE | Which protection functions activate the output |
An open-position signal alone cannot establish why a feeder opened. In the documented ComPact NSX DC arrangement, an active SD signal distinguishes a trip from ordinary manual switching. The table shows logical indications, not PLC input levels. Verify the actual NO/NC terminals and input mapping for your installation.
| Event or state | OF position | SD trip | SDE electrical fault trip |
|---|---|---|---|
| Manual OFF with no active trip indication | Open | Inactive | Inactive |
| Shunt trip or undervoltage release operates | Open | Active | Inactive |
| Trip unit detects an electrical fault and trips | Open | Active | Active |
| Trip reset, breaker still open and indications cleared | Open | Inactive | Inactive |
The last row can look identical to manual OFF at the PLC. Log and timestamp signal transitions to preserve the trip event. Use available trip-unit records to distinguish causes such as overload and short circuit.
With a single dry contact input, a broken wire can look like an intentional contact opening. If the circuit signals an alarm by closing the contact, a broken wire can prevent the PLC from seeing a genuine trip. Where the operator must distinguish these states, specify a compatible supervised circuit. Include normal operation, a trip and a signal-loop break in the commissioning checks, and verify that each produces the intended indication.
Send the breaker part number, desired events, control voltage, PLC input details and number of signals. Start with the AC circuit breaker range o AC MCB range. For an application where source terminal orientation also matters, see our breaker reverse feed guide.