Our AC RCCB range covers Type AC, Type A, Type F, and Type B/B+ plus selective Type S. Use this table to select the correct waveform sensitivity and trip characteristic.
Typ | Waveform Coverage | Typical Applications | Sensitivity (IΔn) | Pole | Anmerkungen |
---|---|---|---|---|---|
AC | Pure sinusoidal AC residual current | Standard residential/commercial loads | 30 / 100 / 300 mA | 2P / 4P | Do not use where pulsating DC may occur. |
A | AC + pulsating DC | Appliances with power electronics, SMPS | 10 / 30 / 100 / 300 mA | 2P / 4P | Recommended default for mixed modern loads. |
F | AC + pulsating DC + high-frequency components | Drives, UPS, frequency converters | 30 / 100 mA | 2P / 4P | Improved immunity to nuisance tripping. |
B / B+ | All currents including smooth DC | EV charging, PV inverters, industrial VFDs | 30 / 100 / 300 mA | 2P / 4P | Mandatory if smooth DC leakage is possible. |
S (Selective) | Time-delayed trip (~150–500 ms) | Upstream protection for discrimination | 100 / 300 mA | 2P / 4P | Use upstream of 30 mA devices to avoid blackouts. |
Use 30 mA Type A for personnel protection.
Selective Type S upstream; 30 mA downstream on final circuits.
Type B/B+ where smooth DC leakage may occur.
Typ F mit verbesserter HF-Störfestigkeit für Umrichter/USV.
High reliability and discrimination requirements.
Koordinieren Sie mit AC SPD; Type B when required by inverter.
RCCBs do not provide overload or short-circuit protection; always coordinate with an upstream MCB/MCCB.
Place upstream of branch circuits. Typical residential choice includes RCCB 63A 30mA.
Ensure phase sequence and shared neutral through the device for correct sensing.
30 mA for personnel protection; 100/300 mA for fire protection or upstream selectivity.
Layer protection for robust AC systems and proper selectivity.
Stack | Purpose | Anmerkungen | Related Category |
---|---|---|---|
MCB → RCCB | Overcurrent + leakage | Choose curve (B/C/D) and IΔn; respect Inc/IΔc values. | MCB |
RCBO (alternativ) | Kombiniert in einem Gerät | Vereinfacht den Schutz des Endstromkreises und die Verdrahtung. | RCBO |
RCCB + AFDD | Leakage + arc-fault | Use in bedrooms, aging wiring, combustible areas. | AFDD |
RCCB + AC SPD | Surge + leakage protection | Place SPD per coordination rules for upstream devices. | AC SPD |
Typical envelope values for Kuangya AC RCCB range. Confirm final numbers in the datasheet per model.
Parameter | Value / Range |
---|---|
Standard | IEC/EN 61008-1 |
Pole | 2P (single-phase) / 4P (three-phase) |
Nennstrom (In) | 16–125 A — popular: RCCB 63A 30mA |
Rated Sensitivity (IΔn) | 10 / 30 / 100 / 300 mA |
Nennspannung (Ue) | 240 V~ (2P) / 415 V~ (4P) |
Isolationsspannung (Ui) | ≥ 500 V |
Conditional Short-Circuit (Inc/IΔc) | 6–10 kA with upstream breaker |
Impulse Withstand (Uimp) | 4–6 kV |
Tripping Class | Instantaneous; Selective S (≈150–500 ms delay) |
Ausdauer | ≥ 10,000 mechanical/electrical operations |
Terminal-Kapazität | Up to 35 mm² Cu; pin/fork busbar compatible |
Montage | DIN rail 35 mm (EN 60715) |
Betriebstemperatur | −25 °C … +55 °C |
Waveform Types | Type AC / A / F / B / B+; Selective S |
Series-dependent approvals. Contact us for the exact certificate set per model family.
RCCB detects residual (earth) current only; RCBO integrates residual-current and overcurrent protection in one device for terminal circuits.
Use Type S upstream to achieve selectivity with downstream 30 mA RCDs. The intentional time delay (≈150–500 ms) prevents whole-board trips.
Use Type B/B+ where smooth DC residual currents are possible (certain EV chargers and PV inverters). Always confirm with the equipment manual.
It is the sensitivity threshold. 30 mA protects people; 100/300 mA are used upstream for fire protection/selectivity.
No. RCCB does not protect against overload or short circuit. Always coordinate with an upstream MCB or MCCB.
Type A is recommended for modern mixed loads because it also detects pulsating DC from power electronics. Type AC is for purely sinusoidal AC loads.
Press the TEST button monthly (or per local regulation) to verify correct trip function. Replace any device that fails the test.
In fire-risk areas (bedrooms, aging wiring, combustible storage), add an AFDD for arc-fault detection alongside RCCB.