Shunt Trip vs Undervoltage Release: How to Choose MX or MN

A shunt trip opens a circuit breaker when it receives an electrical command. An undervoltage release opens the breaker when the voltage on its own control supply drops below the device’s operating threshold. Choose by deciding what the breaker should do if control power disappears.

MX and MN compared

DesignfrageShunt trip (MX)Undervoltage release (MN)
What initiates opening?An applied trip command within the rated operating rangeLoss or sufficient reduction of voltage at the release
What happens if control power fails?The coil cannot respond without a suitable energy sourceThe breaker opens when the release reaches its dropout conditions
What should the designer confirm?Available control power at the time of demand and permitted command durationDropout and closing permissive thresholds and any approved delay

Use the exact accessory data

Schneider Electric’s ComPacT NSXm voltage release guide gives a concrete example: its MN trips below 0.35 times rated control voltage, may trip between 0.35 and 0.7 times, and permits closing again once voltage reaches 0.85 times rated. Those figures apply to the cited accessory. Restoring control voltage provides a closing permissive under the documented conditions. Any automatic closing requires separate equipment and control logic.

Design example: remote shutdown on a panel

Suppose a building controller sends a shutdown command to a feeder. If the design calls for the feeder to open on loss of the monitored control supply, evaluate an MN arrangement and plan for unwanted shutdowns during brief supply dips. If the feeder should open on an explicit command, evaluate an MX arrangement and verify that trip energy remains available under the conditions that demand shutdown. An emergency stop function requires assessment and validation of the complete safety circuit. Coil selection is one part of that design.

What to check before ordering

  1. Confirm the breaker frame, exact part number, accessory slot and compatibility with other releases or signaling contacts.
  2. Match rated control voltage, AC or DC type, and the documented operating range. For MX, also verify whether the command must be pulsed or may be maintained.
  3. Trace where control power comes from in normal operation and following a supply outage. For MN, confirm which supply the coil actually monitors.
  4. Confirm the required reset and restart behavior. Verify opening feedback separately using the appropriate position and trip indication contacts.
  5. Have qualified personnel validate the control sequence using the manufacturer’s instructions and the project’s isolation and commissioning procedures.

Can a PLC tell which release opened the breaker?

A generic trip contact may signal both MX and MN operation with the same state. For event history, log the trip command, monitor control supply status and record breaker feedback separately. Confirm which events the specific breaker can distinguish.

What information should go on a quotation request?

Für eine KUANGYA AC breaker oder MCB configuration review, send the exact breaker model, control voltage, required response to loss of control power, restart behavior and requested feedback. Have the supplier confirm compatible accessory part numbers before ordering.

elaine
elaine

Marketingleiter bei Kuangya, der sich auf die globale Förderung von Lösungen für den elektrischen Schutz und die Energieverteilung konzentriert: Markenaufbau in den Märkten für Photovoltaik, Energiespeicherung und industrielle Stromversorgung.● Professionelle Produkte: Sicherungen, Überspannungsschutzgeräte (SPD), Miniaturleistungsschalter (MCB) und Umschalter.● Wertversprechen: Wir bedienen den globalen Markt für erneuerbare Energien mit den Eckpfeilern "Sicherheit, Zuverlässigkeit und Innovation" und laden Sie ein, mit uns zusammenzuarbeiten, um gemeinsam den Fortschritt der intelligenten Stromverteilungstechnologie voranzutreiben.