A shunt trip opens a circuit breaker when it receives an electrical command. An undervoltage release opens the breaker when the voltage on its own control supply drops below the device’s operating threshold. Choose by deciding what the breaker should do if control power disappears.
| Question de conception | Shunt trip (MX) | Undervoltage release (MN) |
|---|---|---|
| What initiates opening? | An applied trip command within the rated operating range | Loss or sufficient reduction of voltage at the release |
| What happens if control power fails? | The coil cannot respond without a suitable energy source | The breaker opens when the release reaches its dropout conditions |
| What should the designer confirm? | Available control power at the time of demand and permitted command duration | Dropout and closing permissive thresholds and any approved delay |
Schneider Electric’s ComPacT NSXm voltage release guide gives a concrete example: its MN trips below 0.35 times rated control voltage, may trip between 0.35 and 0.7 times, and permits closing again once voltage reaches 0.85 times rated. Those figures apply to the cited accessory. Restoring control voltage provides a closing permissive under the documented conditions. Any automatic closing requires separate equipment and control logic.
Suppose a building controller sends a shutdown command to a feeder. If the design calls for the feeder to open on loss of the monitored control supply, evaluate an MN arrangement and plan for unwanted shutdowns during brief supply dips. If the feeder should open on an explicit command, evaluate an MX arrangement and verify that trip energy remains available under the conditions that demand shutdown. An emergency stop function requires assessment and validation of the complete safety circuit. Coil selection is one part of that design.
A generic trip contact may signal both MX and MN operation with the same state. For event history, log the trip command, monitor control supply status and record breaker feedback separately. Confirm which events the specific breaker can distinguish.
For a KUANGYA AC breaker ou MCB configuration review, send the exact breaker model, control voltage, required response to loss of control power, restart behavior and requested feedback. Have the supplier confirm compatible accessory part numbers before ordering.