RCBO VAL003 / VAL003N - Disjuntor de corrente residual monopolar+N com proteção contra sobrecorrente

  • rcbo single pole (1P+N) for residential & commercial circuits, In 5–40A, curves B/C.

  • Type AC / Type A, sensitivities 6 / 10 / 30 / 100 / 300 mA; Icn up to 10 kA @240V (VAL003) / 15 kA @120V (VAL003N).

  • Certified SEMKO / UKCA / CE / SAA; electrical & mechanical endurance 2,000 cycles.

Obter uma cotação

Categoria:

rcbo polo único VAL003 / VAL003N delivers combined residual-current and overcurrent protection in a compact 1P+N form factor (5–40 A), with Type AC/A, multiple IΔn options and B/C curves for residential and commercial circuits.

Visão geral

VAL003 and VAL003N are compact modular RCBOs designed to provide combined protection against overload, short-circuit and residual current faults on single-phase distribution branches. Both variants share the same compact 1P+N footprint and current range (5–40 A), while their rated voltage and breaking capacity differ to fit regional grids: VAL003 targets 240 V systems (up to 10 kA Icn), and VAL003N targets 120 V systems (up to 15 kA Icn). With selectable residual current types (AC / A) and multiple sensitivities (6 / 10 / 30 / 100 / 300 mA), the series suits residential, commercial and light industrial applications where space efficiency and reliable nuisance-trip control are required.

Principais recursos

  • Form factor: 1P+N (single-pole + neutral), compact modular width
  • Rated current (In): 5–40 A (typical steps: 5/6/10/16/20/25/32/40 A)
  • Residual current type: Type AC / Type A
  • Sensitivity options (IΔn): 6 / 10 / 30 / 100 / 300 mA
  • Tripping curves: B (3–5×In) e C (5–10×In)
  • Breaking capacity (Icn): up to 10 kA @ 240 V (VAL003); 15 kA @ 120 V (VAL003N)
  • Service life: electrical 2,000 cycles / mechanical 2,000 cycles
  • Front test button (T) for routine residual function verification
  • Standards & compliance: IEC/EN 61009-1; certifications SEMKO / UKCA / CE / SAA

RCBO Single Pole Technical Data (VAL003 / VAL003N)

ParâmetroVAL003VAL003N
Postes1P+N (single-pole + neutral)
Rated current (In)5–40 A5–40 A
Rated voltage (Ue)AC 240 VAC 120 V
Frequência50/60 Hz
Residual current typeType AC / Type A
Rated residual current (IΔn)6 / 10 / 30 / 100 / 300 mA
Tripping characteristic (MCB curve)B: 3–5 × In; C: 5–10 × In
Breaking capacity (Icn)4.5 / 6 / 10 kA @ 240 V15 kA @ 120 V
ResistênciaElectrical: 2,000 cycles; Mechanical: 2,000 cycles
PadrõesIEC/EN 61009-1
CertificaçõesSEMKO, UKCA, CE, SAA
InstalaçãoDIN-rail mounting; front wiring; test button (T)
Recommended applicationsResidential branch circuits, commercial lighting & sockets, small equipment feeds

Aplicativos

  • Residential distribution boards: lighting, socket circuits
  • Commercial offices & retail: small loads and outlets
  • Public facilities: classrooms, small rooms, admin areas
  • Light industrial auxiliaries where 1P+N and In ≤ 40 A are sufficient

Certifications & Compliance

Conforms to IEC/EN 61009-1, with certifications SEMKO, UKCA, CE, and SAA.
Refer to local codes for coordination and selectivity with upstream protective devices.

PERGUNTAS FREQUENTES

What is the difference between VAL003 and VAL003N?

They share the same 1P+N form factor and current range (5–40 A) and support both Type AC and Type A residual protections. VAL003 targets 240 V grids with up to 10 kA Icn; VAL003N targets 120 V grids with 15 kA Icn.

Which sensitivities (IΔn) are available?

6 / 10 / 30 / 100 / 300 mA. For typical socket and lighting circuits, 30 mA is most common; 6–10 mA may be used for higher touch-safety requirements; 100–300 mA are generally for special coordination scenarios per local codes.

How do I choose between curve B and curve C?

Use curve B (3–5×In) for resistive/lightly inductive loads; use curve C (5–10×In) for circuits with higher inrush (e.g., motors, transformers). Always verify with upstream protection and local standards.

Can it be used in light industrial panels?

Yes, within its ratings (1P+N, up to 40 A). For larger currents, three-phase systems, or special waveforms (e.g., EV / Type B), choose other series models accordingly.

Avaliações

Não há avaliações ainda.

Seja o primeiro a avaliar “RCBO VAL003 / VAL003N — Single-Pole+N Residual Current Breaker with Overcurrent Protection”

O seu endereço de e-mail não será publicado. Campos obrigatórios são marcados com *