(1) O 1500v dc spd t1+t2 KY-15T/G1500 provides combined Type 1+2 surge protection for photovoltaic DC systems.
(2) Designed for utility-scale PV plants, inverters, and combiner boxes, compliant with IEC 61643-31 and CE/UKCA/RoHS.
(3) Features replaceable modules, remote alarm option, and shared wiring/dimension diagrams for T1+T2 series.
O 1500v dc spd t1+t2 KY-15T/G1500 is a combined Type 1+2 surge protective device
para Caixas combinadoras fotovoltaicas, inverter DC inputs, and DC feeders up to 1500VDC.
It safely handles lightning current discharge while limiting residual voltage, ensuring reliable protection
for photovoltaic systems. Fully compliant with
IEC 61643-31, CE, UKCA, and RoHS standards.
| Tipo | T1+T2 |
|---|---|
| Tensão do sistema (Ucpv) | 1500 V CC |
| Corrente de descarga nominal (In) | 20 kA |
| Corrente máxima de descarga (Imáximo) | 40 kA |
| Corrente de impulso (Iimp) | 6,25 kA |
| Nível de proteção de tensão (Up) | ≤ 5.5 kV |
| Tempo de resposta (ta) | < 25 ns |
| Corrente de curto-circuito admissível (Iscpv) | 10 kA |
| Contato de alarme remoto | 220V, 0,5A, NO/NC |
| Padrões | IEC 61643-31, GB/T 18802.31, CE, UKCA, RoHS |

Dimensão:

It provides both lightning current (Type 1) and surge voltage (Type 2) protection, suitable for main DC entry points in 1500V PV plants.
Yes, KY-15T/G1500 is designed for inverter DC inputs up to 1500V, preventing overvoltage and ensuring inverter safety.
It supports higher system voltage (1500V) and is ideal for large-scale PV plants where higher voltage strings are used.
As certificações IEC 61643-31, GB/T 18802.31, CE, UKCA e RoHS são cobertas.