The Kuangya VKL11 b type rccb provides residual-current protection with Type B/B+ detection suitable for AC and DC leakage conditions
2P / 4P; In 16–100 A; IΔn 10/30/100/300 mA; Ue 240 V (2P) / 415 V (4P); Ui 500 V; 50/60 Hz
Uimp 4/6 kV (per variant); Inc = IΔc 6/10 kA (with upstream SCPD); IP20 terminals; DIN-rail EN 60715
VKL11 (B/B+) is a b type rccb designed to disconnect the circuit when residual current exceeds
the threshold, helping prevent electric shock and fire hazards due to insulation faults. The Type B/B+ variants
are suitable for leakage containing smooth DC and higher-frequency components often present with frequency
converters, inverters, PV/EV equipment, and VFD-driven motors. Pole options include 2P for single-phase and
4P for three-phase systems.
| Modelo | VKL11 (B/B+) |
|---|---|
| Padrão | IEC/EN 61008-1 |
| Postes | 2P, 4P |
| Corrente nominal (In) | 16A, 25A, 32A, 40A, 63A, 80A, 100A |
| Sensibilidade nominal (IΔn) | 10 mA, 30 mA, 100 mA, 300 mA |
| Tensão nominal (Ue) | 2P: 240 V~; 4P: 415 V~ |
| Tensão de isolamento (Ui) | 500 V |
| Frequência nominal | 50/60 Hz |
| Criação e quebra residual (IΔm) | 500 A (em 16-40 A); 630 A (63 A); 800 A (80 A); 1000 A (100 A) |
| Curto-circuito condicional (Inc = IΔc) | 6000 A; 10000 A |
| Resistência a impulsos (Uimp) | 4 kV / 6 kV (per variant) |
| Grau de proteção do terminal | IP20 |
| Ambient temperature | −25 °C to +55 °C (daily avg ≤ 35 °C) |
| Temperatura de armazenamento | -40 °C a +70 °C |
| Conexão do terminal | Cabo / barramento tipo pino |
| Tamanho do terminal (cabo) | 25–35 mm² |
| Tamanho do terminal (barramento) | 10/16 mm² |
| Torque de aperto | 2.5 N·m |
| Montagem | Trilho DIN EN 60715 (35 mm) |
| Conexão | Parte superior e inferior |
| Waveform classes | Type B / B+ (DC-capable); AC, A (where applicable by variant) |

Avaliações