엘리베이터용 서지 보호 장치 KYSPD-40T2-3+1 | 쿠앙야

  • Surge protection device for elevators설계 대상 three-phase + N (3+1 topology) at 230/400 V AC.

  • 서지 등급: In 20 kA (8/20 µs), Imax 40 kA (8/20 µs), Up ≤ 1.5–2.0 kV Uc에 따라 다릅니다.

  • Features L–N MOV + N–PE GDT coordinated protection, pluggable modules, thermal disconnector, optional RC signaling contacts.

견적 받기

카테고리:
The Kuangya KYSPD-40T2-3+1 is a specialized 엘리베이터용 서지 보호 장치,
designed to safeguard lift control systems, drives, and associated electrical panels
in residential, commercial, and industrial buildings. Using a 3+1 topology, it provides
coordinated protection for L-N (MOV) and N-PE (GDT) paths in 230/400 V AC networks.This device is built for high reliability in vertical transport applications,
where electrical disturbances may cause malfunction or downtime. Its pluggable design,
thermal disconnector, and clear status indicators simplify service and ensure safety.
Optional RC contacts allow real-time monitoring and integration with building management systems.

주요 기능

  • Optimized surge protection for elevator systems (control panels, drives, motors).
  • 3+1 topology: MOV protection L–N and coordinated GDT+MOV protection N–PE.
  • Nominal discharge current (In): 20 kA (8/20 μs); Maximum discharge current (Imax): 40 kA (8/20 μs).
  • Voltage protection level (Up): ≤ 1.5–2.0 kV depending on Uc.
  • Fast response time < 25 ns for L–N; < 100 ns for N–PE.
  • Back-up fuse: max 125 A gL/gG; ISCCR 25 kA AC.
  • Optional RC remote signaling contacts: AC 250 V / 0.5 A; DC 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A.
  • Housing IP20, thermoplastic UL94 V-0; operating temperature -40 °C to +80 °C.
  • DIN 레일 장착(35mm, EN 60715), IEC/EN 61643-11 준수.

사양

제품 코드KYSPD-40T2-3+1
카테고리Surge protection device for elevators
공칭 시스템 전압230/400 V AC
토폴로지3+1 (L–N MOV, N–PE GDT+MOV)
연속 작동 전압(Uc)230 V / 320 V / 385 V
공칭 방전 전류(In, 8/20 μs)20 kA
최대 방전 전류(Imax, 8/20 μs)40 kA
전압 보호 수준(상향)≤ 1.5–2.0 kV
응답 시간< 25 ns (L–N) / < 100 ns (N–PE)
백업 퓨즈(최대)125 A gL/gG
단락 전류 정격(ISCCR)25 kA AC
작동 온도-40 °C to +80 °C
마운팅35mm DIN 레일, EN 60715
인클로저 / 보호열가소성 플라스틱 UL94 V-0 / IP20
원격 신호(RC)옵션; AC 250V/0.5A; DC 250V/0.1A; 125V/0.2A; 75V/0.5A
표준IEC/EN 61643-11

배선 및 치수

Connection diagram surge protection device for elevators KYSPD-40T2-3+1

Connection diagram surge protection device for elevators KYSPD-40T2-3+1

Dimensions surge protection device for elevators KYSPD-40T2-3+1

Dimensions surge protection device for elevators KYSPD-40T2-3+1

애플리케이션

  • Elevator control panels and drive systems in residential and commercial buildings.
  • Protection of lift equipment from lightning-induced and switching surges.
  • Building electrical panels requiring coordinated 3+1 surge protection with monitoring.

자주 묻는 질문

  • Why is this SPD suitable for elevators? It uses a 3+1 topology optimized for protecting sensitive elevator controls and drives.
  • 서지 용량은 얼마인가요? In 20 kA, Imax 40 kA per path.
  • 모니터링을 지원하나요? Yes, optional RC contacts provide remote fault indication.
  • 백업 퓨즈 정격은 어떻게 되나요? Maximum 125 A gL/gG.
  • 어떤 표준을 준수하나요? IEC/EN 61643-11.
자세한 가격 및 기술 지원은 다음을 참조하세요. 문의하기.Explore more Kuangya products: DC SPD, AC 서지 보호.