The Kuangya KYSPD-40T2-3P is a 240Vサージ保護装置
designed for three-phase systems (L1, L2, L3). It provides Type 2
protection against transient overvoltages caused by indirect lightning
and switching operations in 230/400 V AC TN-S, TN-C, and TT networks.Equipped with high-capacity MOV elements, the device ensures reliable
surge suppression with a pluggable module structure for easy service.
Integrated thermal disconnectors and clear fault indicators guarantee safety,
while optional RC contacts enable monitoring integration with building
management systems (BMS) or PLC.主な特徴
- Class II / Type 2 surge protection for 240 V three-phase systems.
- Nominal discharge current (In): 20 kA (8/20 μs).
- Maximum discharge current (Imax): 40 kA (8/20 μs).
- Voltage protection level (Up): ≤ 1.3–2.0 kV depending on Uc (230–385 V).
- Response time < 25 ns, ensuring rapid surge suppression.
- Back-up fuse: max 125 A gL/gG; ISCCR up to 25 kA AC.
- Pluggable module with thermal disconnector and visible green/red status.
- Optional RC remote signaling contacts: AC 250 V / 0.5 A; DC 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A.
- Housing IP20, thermoplastic UL94 V-0; operating temperature -40 °C to +80 °C.
- Mounting: 35 mm DIN rail (EN 60715); complies with IEC/EN 61643-11.
仕様
| Product Code | KYSPD-40T2-3P |
|---|
| Category | 240Vサージ保護装置 |
|---|
| Nominal System Voltage | 230/400 V AC |
|---|
| ポール | 3P (L1, L2, L3) |
|---|
| Continuous Operating Voltage (Uc) | 230 V / 320 V / 385 V |
|---|
| Nominal Discharge Current (In, 8/20 μs) | 20 kA |
|---|
| Maximum Discharge Current (Imax, 8/20 μs) | 40 kA |
|---|
| Voltage Protection Level (Up) | ≤ 1.3–2.0 kV |
|---|
| 応答時間 | < 25 ns |
|---|
| Back-Up Fuse (max) | 125 A gL/gG |
|---|
| Short-Circuit Current Rating (ISCCR) | 25 kA AC |
|---|
| 動作温度 | -40 °C to +80 °C |
|---|
| 取り付け | 35 mm DIN rail, EN 60715 |
|---|
| Enclosure / Protection | Thermoplastic UL94 V-0 / IP20 |
|---|
| Remote Signaling (RC) | オプション; AC 250 V / 0.5 A; DC 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A |
|---|
| 規格 | IEC/EN 61643-11 |
|---|
配線と寸法
Connection diagram 240v surge protection device KYSPD-40T2-3P

Dimensions 240v surge protection device KYSPD-40T2-3P

アプリケーション
- Three-phase 240 V AC distribution boards in residential, commercial, and industrial facilities.
- Coordination with upstream Type 1 arresters in TT and TN systems.
- Electrical panels requiring reliable 3P surge protection with monitoring options.
よくあるご質問
- What class of SPD is KYSPD-40T2-3P? It is Class II, Type 2 according to IEC/EN 61643-11.
- What is its discharge capacity? In 20 kA, Imax 40 kA per phase.
- Can it be used in 240 V three-phase systems? Yes, it is designed for L1-L2-L3 protection in 230/400 V AC networks.
- Does it provide remote signaling? Yes, optional RC contacts are available.
- What is the maximum backup fuse rating? 125 A gL/gG.