RCCB VFL001 - 残留電流サーキットブレーカ

  • Type A RCCB for people/fire protection; also supports Type AC.

  • 2P/4P, 16–100A, sensitivities 10/30/100/300 mAUe 240V (2P) / 415V (4P)

  • IΔm up to 1000A, Inc=IΔc 6kA/10kA, Uimp 6kV;DIN-rail EN 60715;CE/UKCA

お見積もり

カテゴリー:

概要

The Kuangya VFL001 is a Type A RCCB designed to detect sinusoidal AC and pulsating DC residual currents, providing reliable protection against electric shock and electrical fires. It also supports Type AC operation for AC-only applications. With 2P/4P configurations, rated current from 16A to 100A, and sensitivities of 10/30/100/300 mA, VFL001 fits residential, commercial and light industrial distribution boards. Popular selections include rccb 16a 30ma, rccb 25a 30ma, rccb 40a 30maそして RCCB 63A 30MA.

How it works

When the residual current exceeds the preset threshold (IΔn), the internal toroidal sensor and trip unit of this タイプA RCCB actuate the mechanism to disconnect the circuit within the specified breaking time. Short-time delay (ASi/G/KV) and selective (S) characteristics are available to coordinate with upstream/downstream devices and reduce nuisance tripping.

主な特徴

  • Type A / AC residual-current detection (AC + pulsating DC for Type A).
  • ポール: 2P / 4P; In: 16, 25, 32, 40, 63, 80, 100 A.
  • IΔn options: 10 mA (2P/4P 16–40 A), 30 mA, 100 mA, 300 mA.
  • Ue: 240 V~ (2P) / 415 V~ (4P); Ui: 500 V; 50/60 Hz.
  • IΔm: 500 A (In 16–40 A), 630 A (63 A), 800 A (80 A), 1000 A (100 A).
  • Inc = IΔc: 6 kA or 10 kA (with upstream SCPD coordination).
  • Uimp: 6 kV; dielectric test 2.5 kV (1 min at power freq.).
  • 持久力: ≥20,000 mechanical / ≥10,000 electrical operations.
  • IP20 terminals with cable/pin-type busbar connection; DIN rail EN 60715.
  • Ambient −25 °C…+55 °C (daily avg ≤35 °C); storage −40 °C…+70 °C.

技術データ

スタンダードIEC/EN 61008-1
モデル番号VFL001
ポール2P、4P
Rated current In16A、25A、32A、40A、63A、80A、100A
Rated Sensitivity IΔn10 mA (2P/4P 16A–40A), 30 mA, 100 mA, 300 mA
Rated voltage Ue2P: 240V~    4P: 415V~
Insulation voltage Ui500 V
定格周波数50/60 Hz
Rated residual making & breaking capacity IΔm500 A (In=16A, 25A, 32A, 40A); 630 A (In=63A); 800 A (In=80A); 1000 A (In=100A)
Short-circuit current Inc = IΔc6000 A, 10000 A
Type (waveform sensed)AC, A
Tripping timeInstantaneous / Short time delay / Selective
Break time under IΔn≤100 ms (normal type)
Short time delay10–300 ms (ASi, G, KV type)
選択タイプ150–500 ms (S type)
Rated impulse withstand voltage (1.2/50) Uimp6 kV
Dielectric test voltage at ind. freq. (1 min)2.5 kV
Pollution degree2
Electrical life≥2000
Mechanical life≥2000
Fault current indicatorYes
端子保護度IP20
Ambient temperature (daily avg ≤35 °C)-25 °C ~ +55 °C
保存温度-40 °C ~ +70 °C
Terminal connection typeケーブル / ピン型バスバー
Terminal size top/bottom for cable25–35 mm² (typ.); 18–3 / 18–2 AWG notes per size class
Terminal size top/bottom for busbarPin-type; 10/16 mm² (typ.); 18–8 / 18–5 AWG notes
締め付けトルク2.5 N·m (≈ 22 in-lbs)
取り付けOn DIN rail EN 60715 (35 mm) by fast clip device
ConnectionFrom top and bottom

アプリケーション

  • Residential distribution boards (bathrooms, kitchens, EV chargers with proper coordination).
  • Commercial buildings (shops, offices, public facilities) requiring タイプA RCCB for mixed AC/pulsating DC loads.
  • Light industrial panels and machinery control, with selective or short-time delayed versions for coordination.

Installation & Selection Guide

  1. Select the pole number (2P/4P) according to system voltage: 240 V~ (single-phase) or 415 V~ (three-phase).
  2. 選ぶ IΔn by application: 10/30 mA for personal protection; 100/300 mA for fire protection/selectivity.
  3. For high inrush or EMC-sensitive loads, consider short-time delay (ASi/G/KV) or Selective S types.
  4. Coordinate with upstream SCPD to meet Inc = IΔc 6 kA / 10 kA requirements.
  5. Observe ambient limits (−25…+55 °C, daily avg ≤35 °C) and torque settings (2.5 N·m).

認証と規格

適合規格 IEC/EN 61008-1; CE & UKCA approvals. Terminal safety to IP20; pollution degree 2.

よくあるご質問

What is the difference between Type A and Type AC?

Type AC detects sinusoidal AC only; タイプA also detects pulsating DC components, which are common with modern power electronics.

When should I use short-time delay or S selective types?

Use short-time delay (10–300 ms) to ride through transient leakage or inrush; use S type (150–500 ms) to coordinate with downstream RCCBs and avoid nuisance tripping.

What upstream protection is required?

Select an SCPD so that the conditional residual short-circuit current rating Inc = IΔc of 6 kA or 10 kA is respected under fault conditions.

 