  • Type 2 surge protective device for 230 V AC single-phase systems with L+N protection (2P).

  • Rated discharge current In 20 kA (8/20 µs), maximum discharge Imax 40 kA (8/20 µs); voltage protection level Up ≤ 1.3–2.0 kV depending on Uc.

  • Pluggable design, thermal disconnector with fault indicator, optional RC remote contacts, DIN-rail mounting.

お見積もり

カテゴリー:
The Kuangya KYSPD-40T2-2P is a two-pole サージ防護デバイス タイプ2
designed for single-phase AC systems at 230 V. It provides coordinated protection
for L and N conductors against transient overvoltages from switching operations
and indirect lightning strikes.Built with high-energy MOV technology, this SPD delivers reliable protection in
residential, commercial, and light industrial applications. It features pluggable
modules for easy maintenance, a thermal disconnector with green/red fault indicator,
and optional remote contacts for monitoring integration with BMS or PLC systems.

主な特徴

  • Class II / Type 2 surge protective device (2P, L+N).
  • Nominal discharge current (In): 20 kA (8/20 μs).
  • Maximum discharge current (Imax): 40 kA (8/20 μs).
  • Voltage protection level (Up): ≤ 1.3–2.0 kV depending on variant.
  • Response time < 25 ns for fast transient suppression.
  • Max back-up fuse: 125 A gL/gG; ISCCR 25 kA AC.
  • Pluggable, serviceable cartridges with visible fault indicator (green/red).
  • Optional RC signaling contacts: AC 250 V / 0.5 A; DC 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A.
  • Thermoplastic UL94-V0 housing, IP20; operating temperature -40 °C to +80 °C.
  • DIN rail mounting (35 mm, EN 60715); complies with IEC/EN 61643-11.

仕様

Product CodeKYSPD-40T2-2P
CategorySurge protective device type 2
Nominal System Voltage230 V AC
ポール2P (L+N)
Continuous Operating Voltage (Uc)230 V / 320 V / 385 V
Nominal Discharge Current (In, 8/20 μs)20 kA
Maximum Discharge Current (Imax, 8/20 μs)40 kA
Voltage Protection Level (Up)≤ 1.3–2.0 kV
応答時間< 25 ns
Back-Up Fuse (max)125 A gL/gG
Short-Circuit Current Rating (ISCCR)25 kA AC
動作温度-40 °C to +80 °C
取り付け35 mm DIN rail, EN 60715
Enclosure / ProtectionThermoplastic UL94 V-0 / IP20
Remote Signaling (RC)オプション; AC 250 V / 0.5 A; DC 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
規格IEC/EN 61643-11

配線と寸法

Connection diagram surge protective device type 2 KYSPD-40T2-2P

Connection diagram surge protective device type 2 KYSPD-40T2-2P

Dimensions surge protective device type 2 KYSPD-40T2-2P

Dimensions surge protective device type 2 KYSPD-40T2-2P

アプリケーション

  • Single-phase 230 V AC distribution panels in residential and commercial sites.
  • Coordination with upstream Type 1 arresters in TT/TN networks.
  • Panels requiring reliable 2P surge protection with optional RC monitoring.

よくあるご質問

  • KYSPD-40T2-2PはどのクラスのSPDですか? It is Class II, Type 2 according to IEC/EN 61643-11.
  • What is its discharge capacity? In 20 kA, Imax 40 kA.
  • Can it be used in single-phase systems? Yes, it is designed for 230 V AC L+N applications.
  • Does it support remote signaling? Yes, optional RC contacts are available.
  • What is the maximum backup fuse rating? 125 A gL/gG.
For detailed pricing and technical support, please お問い合わせ.Explore more Kuangya products: DC SPD, AC Surge Protection.

レビュー

レビューはまだありません。

“Surge protective device type 2 KYSPD-40T2-2P | Kuangya” の口コミを投稿します

メールアドレスが公開されることはありません。 が付いている欄は必須項目です