第1種サージ防護デバイス KYSPD-25T1-2P|Kuangya

  • Two-pole 第1種サージ保護装置 for service entrance, tested to IEC/EN 61643-11.

  • Handles Iimp 25 kA (10/350 μs) per pole, In 25 kA, Imax 100 kA; Uo/Un 230/400 V AC; Uc 320/385/440 V.

  • Pluggable cartridge with visual status indicator, DIN-rail mounting, optional RC remote signaling.

お見積もり

カテゴリー:
The Kuangya KYSPD-25T1-2P is a two-pole 第1種サージ保護装置 designed for service entrance and main distribution boards. It protects low-voltage AC systems against direct lightning currents with an impulse discharge current rating of 25 kA per pole (10/350 μs). This device ensures robust first-stage protection and coordinates with downstream Type 2 and Type 3 surge protective devices for a complete layered defense.

主な特徴

  • Class I / Type 1 according to IEC/EN 61643-11; suitable for LPZ 0→1 boundary.
  • Two-pole design; Iimp 25 kA (10/350 μs) per pole; In 25 kA; Imax 100 kA.
  • Nominal system voltage Uo/Un: 230/400 V AC; Max. continuous operating voltage (Uc): 320 / 385 / 440 V AC.
  • Voltage protection level (Up): typically 1.6–2.0 kV depending on variant.
  • Response time < 25 ns; thermal disconnector with green/red indicator window.
  • Pluggable replaceable module; optional RC remote signaling contacts.
  • Housing: UL94 V-0 thermoplastic; IP20 built-in; DIN 35 mm rail mount (EN 60715).
  • Compatible with TN-S, TN-C, and TT earthing systems.
  • Reliable first stage 第1種サージ保護装置 for coordinated SPD systems.

仕様

パラメータ価値
商品コードKYSPD-25T1-2P
カテゴリーType 1 / Class I SPD
Nominal System Voltage (Uo/Un)230 / 400 V AC
Max. Continuous Operating Voltage (Uc)320 / 385 / 440 V AC
公称放電電流(In、8/20 μs)25 kA
Max. Discharge Current (Imax, 8/20 μs)100 kA
Impulse Discharge Current (Iimp, 10/350 μs)25 kA per pole
電圧保護レベル(上)~1.6–2.0 kV
応答時間< 25 ns
Follow Current Interrupt Rating100 A RMS
短絡電流定格(ISCCR)50 kA
Backup Fuse (max)315 A gL/gG
動作温度-40 °C … +70 °C
取り付け35 mm DIN rail (EN 60715)
エンクロージャーThermoplastic, UL94 V-0
保護等級IP20 (built-in)
Remote SignalingOptional RC contacts
規格IEC 61643-11 / EN 61643-11

配線と寸法

  • Connection diagram: kyspd-25t1-2p-connection
  • type 1 surge protective device wiring diagram
  • 寸法: kyspd-25t1-2p-dimensions
  • type 1 surge protective device 2-pole dimensions

アプリケーション

  • Service entrance / main distribution boards (LPZ 0→1).
  • Industrial and commercial facilities exposed to lightning surges.
  • First-stage 第1種サージ保護装置 in coordinated protection with downstream SPDs.

よくあるご質問

Where should KYSPD-25T1-2P be installed?

At the service entrance or main distribution board, as the first stage of protection.

Does it support different earthing systems?

Yes, TN-S, TN-C, and TT systems are supported with correct wiring.

What backup fuse is required?

A maximum 315 A gL/gG fuse is recommended.

How do I replace the module?

The cartridge is pluggable. Isolate power, remove the old module, insert the new one, and restore power.

Is remote monitoring available?

Yes, optional RC terminals provide remote status signaling.

What is the ISCCR rating?

The device withstands up to 50 kA short-circuit current.

What happens if the module fails?

The thermal disconnector trips and the status indicator turns red.

What standards apply?

IEC/EN 61643-11 for low-voltage surge protective devices.