AFDD-3 Arc Fault Detection Device (Magnetic Type) | 1P+N RCBO Type A 6kA

  • Magnetic Type AFDD integrating AFDD + MCB + RCCB (Type A) in one 1P+N module
  • 6A–40A rated current, B/C curves, 6 kA short-circuit capacity
  • Conforme a EN62606 & EN61009-1; ideal for residential, commercial & public buildings
Richiedi un preventivo

Categoria:
Il AFDD-3 Magnetic Type integrates arc-fault detection (AFDD),
overcurrent protection (MCB), e residual current protection (RCCB, Type A) in a compact
1P+N module. Designed with a magnetic tripping mechanism, it delivers stable
operation across varying loads. Compliant with EN62606 e EN61009-1, the device
offers 6 kA short-circuit capacity and early detection of series/parallel arc faults to reduce fire risk.

Caratteristiche principali

  • Triple protection: AFDD + MCB + RCCB (Type A)
  • Magnetico tripping mechanism for reliable performance
  • Tripping characteristics: B/C; short-circuit capacity: 6 kA
  • LED indication for device status and tripping reason; continuous self-monitoring
  • Compatto 1P+N (1 module) design; screw terminals (top/bottom), strain-relief clamps
  • Easy mounting on Guida DIN da 35 mm
  • Endurance: ≥ 20,000 mechanical / ≥ 4,000 electrical cycles

Technical Data

SerieAFDD
ModelloAFDD-3
Pali1P+N (1 Module)
Rated current (AC)6A, 10A, 13A, 16A, 20A, 25A, 32A, 40A
Tipo di corrente residuaTipo A
Rated residual current IΔn10 mA, 30 mA
Min./Max. test circuit voltage196 V / 253 V
Tripping characteristicB, C
Operating frequency50 Hz
Impulse withstand voltage (Uimp)4 kV
Rated voltage (AC)240 V
Rated short-circuit current (Icn)6 kA
Surge current strength0.25 kA
Max. total switching capacity6 kA
Rated insulation voltage250 V
Heat loss per pole3 W
Short-circuit backup fuse (SCPD)100 A
Backup fuse typegG
Overvoltage classIII
TerminalsScrew-type, top & bottom (load circuit)
Neutral conductor positionLeft / Right
Max. connection cable length70 m (distribution board ↔ outer socket)
Clamping area1–25 mm²
Tightening torque2.0–2.4 Nm
Mechanical endurance≥ 20,000 cycles
Electrical endurance≥ 4,000 cycles
Storage / Operating temperature-35℃…+60℃ / -25℃…+40℃
Housing type / materialDistribution board housing / Thermoplastic
MontaggioDIN rail (35 mm)
Protection classIP20 (installed: IP40)
StandardEN62606, EN61009-1
Power limitation category3
Pollution degree (EN60664)2
CertificazioniUKCA, CE

Applicazioni

  • Fire protection for final circuits up to 40A in residential, commercial and public buildings
  • Suitable networks: TN-S e TN-C-S
  • Not permitted: TN-C systems or circuits with smooth DC residual currents

Certificazioni

  • UKCA, CE
  • Standards: EN62606 (AFDD), EN61009-1 (RCBO)

FAQ

What differentiates AFDD-3 from AFDD-1?

AFDD-3 adopts a magnetic tripping mechanism for stable performance under varying loads; AFDD-1 is a standard electronic design. Electrical ratings are otherwise similar.

Does AFDD-3 comply with EN standards?

Yes. It complies with EN62606 (arc fault detection) and EN61009-1 (RCBO).

Which leakage type is detected?

Type A — sinusoidal AC and pulsating DC residual currents.