VSP1S40 series

Location of Use : Sub-Distribution Boards

Network Systems : 1S:TN-S / TN-C / TT

2S/4S :TN-S

3S: TN-C (3S)

Mode of Protection: 1S: L-PE + N-PE + L-PEN + L-N

2S / 4S: L-PE + N-PE

3S: L-PEN

Surge Ratings: I  = 20 kA (8/20 µs)

n

IEC/EN Category : Class II / Type 2

Protective Elements: High Energy MOV

Housing: Pluggable Design

Compliance : IEC 61643-11

EN 61643-11

Richiedi un preventivo

VSP1S40-XXX/1(S), VSP1S40-XXX/2(S), VSP1S40-XXX/3(S), VSP1S40-XXX/4(S)

Location of Use: Sub-Distribution Boards • Network Systems: TT, TN-S, TN-C • Mode of Protection: L-N, L-PE, N-PE

The voltage grade

75 V

is only available for models VSP1S40-XXX/1(S) and VSP1S40-XXX/2(S).

IEC Electrical Data

Parametro 75 V 150 V 275 V 320 V 385 V 440 V
Nominal AC Voltage (50/60 Hz) — U

o

/U

n
60 V 120 V 230 V 230 V 230 V 400 V
Max. Continuous Operating Voltage (AC) — U

c
75 V 150 V 275 V 320 V 385 V 440 V
Nominal Discharge Current (8/20 µs) — I

n
20 kA 20 kA 20 kA 20 kA 20 kA 20 kA
Maximum Discharge Current (8/20 µs) — I

massimo
40 kA 40 kA 40 kA 40 kA 40 kA 40 kA
Voltage Protection Level — U

p
400 V 1000 V 1500 V 1600 V 1800 V 2000 V
Residual Current at U

c

— I

PE
< 0.5 mA
Response Time — t

A
< 25 ns
Fusibile di riserva (max) 125 A gL / gG
Short-Circuit Current Rating (AC) — I

SCCR
25 kA
TOV Withstand 5 s — U

T
90 V 180 V 335 V 335 V 440 V 580 V
TOV Withstand 120 min — U

T
115 V 230 V 440 V 440 V 440 V 765 V
TOV Mode Withstand Withstand Safe Fail Safe Fail Safe Fail Safe Fail

Mechanical & Environmental Data

Parametro Valore
Operating Temperature Range — T

a
-40 °F to +158 °F [-40 °C to +70 °C]
Permissible Operating Humidity — RH 5% … 95%
Atmospheric Pressure / Altitude 80 kPa … 106 kPa / -500 m … 2000 m
Terminal Screw Torque — M

massimo
39.9 lbf·in [4.5 Nm]
Conductor Cross Section (max) 2 AWG (Solid, Stranded) / 4 AWG (Flexible) — 35 mm² (Solid, Stranded) / 25 mm² (Flexible)
Montaggio 35 mm DIN Rail, EN 60715
Grado di protezione IP 20 (built-in)
Materiale dell'alloggiamento Thermoplastic: Extinguishing Degree UL 94V-0
Protezione termica
Operating State / Fault Indication Green OK / Red Defect
Remote Contacts (RC) Opzionale
RC Switching Capacity AC: 250 V / 0.5 A; DC: 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
RC Conductor Cross Section (max) 16 AWG (Solid) / 1.5 mm² (Solid)

Internal Configuration & Connection Diagrams



L — Line Conductor Terminal


N — Neutral Conductor Terminal


PE — Ground Conductor Terminal


S — Signalling Contacts (Optional)

VSP1S40-XXXX/1S — TN-S, TN-C, TT (Single-phase, 1+0)
Terminals: L, N, PE, S (11-12-14)
Cablaggio:
Phase conductor → L terminal
Neutral conductor → N terminal
Ground conductor → PE terminal
Signal contacts → S (11, 12, 14) [Remote contact, optional]
Internal Configuration:
MOV between L and N (F1 path)
MOV between L/N and PE (F2 path)
Backup Fuse:
F1 (L): In series with Line conductor
F2 (L/N): Between L-N and PE junction
Protection Mode: L-N, N-PE

VSP1S40-XXXX/2S — TN-S (Single-phase, 2+0)
Terminals: L, N, PE, S (11-12-14)
Cablaggio:
Phase conductor → L terminal
Neutral conductor → N terminal
Ground conductor → PE terminal
Signal contacts → S (11, 12, 14) [Remote contact, optional]
Internal Configuration:
Dual MOV modules: MOV1 (L’ → L), MOV2 (N’ → N)
L and N each independently referenced to PE
Backup Fuse:
F1 (L’): In series with L’ conductor
F2 (N’): In series with N’ conductor
Protection Mode: L-PE, N-PE

VSP1S40-XXXX/3(S) — TN-C (Three-phase, 3+0)
Terminals: L1, L2, L3, PEN, PE, S (11-12-14)
Cablaggio:
Phase A conductor → L1 terminal
Phase B conductor → L2 terminal
Phase C conductor → L3 terminal
Combined PEN conductor → PEN terminal
Ground conductor → PE terminal
Signal contacts → S (11, 12, 14) [Remote contact, optional]
Internal Configuration:
Three MOV modules (one per phase), all connected in parallel to PEN
L1, L2, L3 fused via F1 (L1′, L2′, L3′) then referenced to PEN/PE
Backup Fuse:
F1: Three-pole fuse on L1′, L2′, L3′ input lines
Protection Mode: L-PEN (3+0 circuit, TN-C network)

VSP1S40-XXXX/4(S) — TN-S (Three-phase, 4+0)
Terminals: L1, L2, L3, N, PE, S (11-12-14)
Cablaggio:
Phase A conductor → L1 terminal
Phase B conductor → L2 terminal
Phase C conductor → L3 terminal
Neutral conductor → N terminal
Ground conductor → PE terminal
Signal contacts → S (11, 12, 14) [Remote contact, optional]
Internal Configuration:
Three MOV modules (L1, L2, L3), all connected in parallel to N
N referenced to PE
Backup Fuse:
F1: Five-pole fuse block on L1′, L2′, L3′, N’, PE’ input lines
Protection Mode: L-N, N-PE (4+0 circuit, TN-S network)

VSP1S40/1(S)+1 & VSP1S40/3(S)+1

Class II • Type 2 • Location of Use: Sub-Distribution Boards • Network Systems: TT, TN-S •
Mode of Protection: L-N, N-PE • Surge Ratings: I

n

= 20 kA (8/20 µs)

Protective Elements: High Energy MOV and GDT • Housing: Pluggable Design • Compliance: IEC 61643-11 / EN 61643-11

The voltage grade

75 V

is only available for model VSP1S40/1(S)+1.

IEC Electrical Data

Parametro 75 V 150 V 275 V 320 V 385 V 440 V
Nominal AC Voltage (50/60 Hz) 60 V 120 V 230 V 230 V 230 V 400 V
Max. Continuous Operating Voltage (L-N) — U

c
75 V 150 V 275 V 320 V 385 V 440 V
Max. Continuous Operating Voltage (N-PE) — U

c
255 V
Nominal Discharge Current (8/20 µs) (L-N) / (N-PE) — I

n
20 kA / 20 kA
Maximum Discharge Current (8/20 µs) (L-N) / (N-PE) — I

massimo
40 kA / 40 kA
Voltage Protection Level (L-N) / (N-PE) — U

p
0.4 kV / 1.5 kV 1.0 kV / 1.5 kV 1.5 kV / 1.5 kV 1.6 kV / 1.5 kV 1.8 kV / 1.5 kV 2.0 kV / 1.5 kV
Follow Current Interrupt Rating (N-PE) — I

fi
100 A

RMS
Residual Current at U

c

— I

PE
none
Response Time (L-N) / (N-PE) — t

A
< 25 ns / < 100 ns
Fusibile di riserva (max) 125 A gL / gG
Short-Circuit Current Rating (AC) (L-N) — I

SCCR
25 kA
TOV Withstand 5 s (L-N) — U

T
90 V 180 V 335 V 335 V 440 V 580 V
TOV Withstand 120 min (L-N) — U

T
115 V 230 V 440 V 440 V 440 V 765 V
TOV Mode (L-N) Withstand Withstand Safe Fail Safe Fail Safe Fail Safe Fail
TOV Withstand 200 ms (N-PE) — U

T
1200 V

Mechanical & Environmental Data

Parametro Valore
Operating Temperature Range — T

a
-40 °F to +158 °F [-40 °C to +70 °C]
Permissible Operating Humidity — RH 5% … 95%
Atmospheric Pressure / Altitude 80 kPa … 106 kPa / -500 m … 2000 m
Terminal Screw Torque — M

massimo
39.9 lbf·in [4.5 Nm]
Conductor Cross Section (max) 2 AWG (Solid, Stranded) / 4 AWG (Flexible) — 35 mm² (Solid, Stranded) / 25 mm² (Flexible)
Montaggio 35 mm DIN Rail, EN 60715
Grado di protezione IP 20 (built-in)
Materiale dell'alloggiamento Thermoplastic: Extinguishing Degree UL 94V-0
Protezione termica
Operating State / Fault Indication Green OK / Red Defect
Remote Contacts (RC) Opzionale
RC Switching Capacity AC: 250 V / 0.5 A; DC: 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
RC Conductor Cross Section (max) 16 AWG (Solid) / 1.5 mm² (Solid)

Internal Configuration & Connection Diagrams



L — Line Conductor Terminal


N — Neutral Conductor Terminal


PE — Ground Conductor Terminal


S — Signalling Contacts (Optional)

VSP1S40/1(S)+1 — TN-S, TT (Single-phase, 1+1)
Terminals: L, N, PE, S (11-12-14)
Cablaggio:
Phase conductor → L terminal
Neutral conductor → N terminal
Ground conductor → PE terminal
Signal contacts → S (11, 12, 14) [Remote contact, optional]
Internal Configuration:
MOV module between L and N (F1 path: L → L’)
GDT module between N and PE (F2 path: N → N’)
Backup Fuse:
F1 (L): In series with L conductor (MOV protection)
F2 (N): In series with N conductor (GDT protection)
Protection Mode: L-N (MOV), N-PE (GDT)

VSP1S40/3(S)+1 — TN-S, TT (Three-phase, 3+1)
Terminals: L1, L2, L3, N, PE, S (11-12-14)
Cablaggio:
Phase A conductor → L1 terminal
Phase B conductor → L2 terminal
Phase C conductor → L3 terminal
Neutral conductor → N terminal
Ground conductor → PE terminal
Signal contacts → S (11, 12, 14) [Remote contact, optional]
Internal Configuration:
Three MOV modules (L1, L2, L3), all connected in parallel to N (F1 path: L1′, L2′, L3′, N’)
GDT module between N and PE (F2 path: L1, L2, L3, N referenced to PE)
Backup Fuse:
F1: Four-pole fuse on L1′, L2′, L3′, N’ input lines (MOV protection)
F2: Four-pole fuse on L1, L2, L3, N lines (GDT protection)
Protection Mode: L-N (MOV), N-PE (GDT)

Dimensions & Packaging

Individual module dimensions and multi-pole configurations for all models in the SLP40 series.

VSP1S40/1S — Width
28 mm
VSP1S40/1S — Height
34.5 mm
VSP1S40/1S — Depth
65.8 mm
VSP1S40/2S — Width
36 mm
VSP1S40/2S — Height
34.5 mm
VSP1S40/2S — Depth
65.8 mm
VSP1S40/3S — Width
49 mm
VSP1S40/3S — Height
34.5 mm
VSP1S40/3S — Depth
65.8 mm
VSP1S40/4S — Width
72 mm
VSP1S40/4S — Height
34.5 mm
VSP1S40/4S — Depth
65.8 mm
VSP1S40/1(S)+1 — Width
28 mm
VSP1S40/1(S)+1 — Height
34.5 mm
VSP1S40/1(S)+1 — Depth
65.8 mm
VSP1S40/3(S)+1 — Width
54 mm
VSP1S40/3(S)+1 — Height
34.5 mm
VSP1S40/3(S)+1 — Depth
65.8 mm
DIN Rail Pitch
45 mm
Terminal Height Offset
12.3 mm
Module Body Width
9 mm per pole

All dimensions are nominal. Multi-pole units use standard 9 mm per pole pitch on 35 mm DIN rail (EN 60715).
Height: 34.5 mm (body) × 49 mm (overall). Depth: 65.8 mm (overall including terminals).
Terminal block offset: 12.3 mm. Common pitch: 18 mm (2-pole equivalent).

Order Information

Modello Descrizione Voltage Grades Available Network System Pali
VSP1S40-XXX/1S Type 2 SPD, single-phase 1+0 75, 150, 275, 320, 385, 440 TN-S, TN-C, TT 1
VSP1S40-XXX/2S Type 2 SPD, single-phase 2+0 75, 150, 275, 320, 385, 440 TN-S 2
VSP1S40-XXX/3S Type 2 SPD, three-phase 3+0 150, 275, 320, 385, 440 TN-C 3
VSP1S40-XXX/4S Type 2 SPD, three-phase 4+0 150, 275, 320, 385, 440 TN-S 4
VSP1S40/1(S)+1 Type 2 SPD, single-phase 1+1 (L-N, N-PE) 75, 150, 275, 320, 385, 440 TT, TN-S 1+1
VSP1S40/3(S)+1 Type 2 SPD, three-phase 3+1 (L-N, N-PE) 150, 275, 320, 385, 440 TT, TN-S 3+1

Ordering Example:

VSP1S40-275/4S = 275 V rated, 4-pole (4+0), Type 2 SPD for TN-S three-phase systems.



N-PE variants:

VSP1S40/3(S)+1-275 = 275 V rated, 3+1 configuration with GDT N-PE protection for TT/TN-S systems.



RC option:

Append “(S)” suffix for remote signalling contacts (e.g. VSP1S40-275/4S with RC).

Product Label Reference

Each module is labelled with the following markings (example for 255 V variant):

Label Fields — VSP1S40 Series
KUANGYA
VSP1S40-255          Surge Protective Device
Ue: 255 V~        Uc: 255 V~
In: 20 kA         Imax: 40 kA
Up: 1.5 kV         Class II / Type 2
IEC 61643-11 / EN 61643-11
Label Fields — VSP1S40/+1 Series
KUANGYA
VSP1S40-255           Surge Protective Device
L-N: Uc: 255 V~     N-PE: Uc: 255 V~
In: 20 kA          Imax: 40 kA
Up: 1.5 kV          Class II / Type 2
IEC 61643-11 / EN 61643-11