Indirizzo
304 Nord Cardinale
St. Dorchester Center, MA 02124
Orario di lavoro
Da lunedì a venerdì: dalle 7.00 alle 19.00
Fine settimana: 10.00 - 17.00
Indirizzo
304 Nord Cardinale
St. Dorchester Center, MA 02124
Orario di lavoro
Da lunedì a venerdì: dalle 7.00 alle 19.00
Fine settimana: 10.00 - 17.00






rcbo single pole (1P+N) modular RCBO for single-phase branches, In 6–50A, tripping curves B/C.
Tipo AC / Tipo A, sensitivities IΔn 10 / 30 / 100 / 300 mA; Icn 6 kA / 10 kA @ 240 V, 50/60 Hz.
Certified SEMKO / UKCA / CE; standard IEC/EN 61009-1; front test button, DIN-rail mounting.
rcbo unipolare VRL01 / VRL02 / VRL03 integrates residual-current and overcurrent protection in a compact 1P+N format, rated 6–50 A for 240 V, 50/60 Hz systems with Type AC/A and multiple IΔn options.
The VRL01 / VRL02 / VRL03 family is designed for single-phase distribution branches where
reliable residual-current protection and coordinated overcurrent performance are required.
Each variant shares the same 1P+N footprint and broad current range up to 50 A, with
selectable tripping curves (B/C), multiple residual sensitivities, and high breaking
capacity options (6/10 kA) to match fault levels on 240 V systems.
| Parametro | VRL01 | VRL02 | VRL03 |
|---|---|---|---|
| Pali | 1P+N (single-pole + neutral) | ||
| Corrente nominale (In) | 6–50 A | 6–50 A | 6–50 A |
| Tensione nominale (Ue) | AC 240 V | AC 240 V | AC 240 V |
| Frequenza | 50/60 Hz | ||
| Tipo di corrente residua | Tipo AC / Tipo A | ||
| Corrente residua nominale (IΔn) | 10 / 30 / 100 / 300 mA | ||
| MCB tripping curve | B: 3–5 × In; C: 5–10 × In | ||
| Capacità di rottura (Icn) | 6 kA / 10 kA @ 240 V | 6 kA / 10 kA @ 240 V | 6 kA / 10 kA @ 240 V |
| Installazione | Guida DIN; cablaggio anteriore; pulsante di prova (T) | ||
| Uso consigliato | Residential & commercial branches (lighting / sockets) within 1P+N and ≤50 A | ||
| Standard | IEC/EN 61009-1 | ||
| Certificazioni | SEMKO, UKCA, CE | ||
Conforme a IEC/EN 61009-1 with certifications SEMKO, UKCA, CE.
Coordinate with upstream protective devices; follow local codes for selectivity and fault levels.
All three share the same 1P+N format, 6–50 A range, Type AC/A residual options and B/C curves. They are part of the same platform with high breaking-capacity options (6/10 kA) for 240 V systems.
30 mA is most common for socket/lighting circuits. 10 mA is for higher touch-safety; 100/300 mA may be used per coordination and local code requirements.
Use curve B (3–5×In) for resistive/lightly inductive loads; use curve C (5–10×In) for circuits with higher inrush such as motors or transformers.
Recensioni
Ancora non ci sono recensioni.