Type 1 Surge Protective Device 1+1 KYSPD-25T1-1+1 | Kuangya

  • Type 1 surge protective device 1+1 conçu pour single-phase TN/TT systems at 230 V AC.

  • Surge ratings: Iimp 12.5 kA (10/350 µs), In 20 kA (8/20 µs), Up ≤ 1.5–2.0 kV depending on Uc.

  • Combines MOV for L–N et GDT for N–PE, pluggable modules, thermal disconnector, optional RC contacts.

Obtenir un devis

Catégorie :
The Kuangya KYSPD-25T1-1+1 is a dispositif de protection contre les surtensions de type 1 1+1
designed for installation at the service entrance of low-voltage AC systems.
It uses a 1+1 topology: MOV protection between L–N and coordinated GDT protection
between N–PE, ensuring effective discharge of lightning current impulses (10/350 μs).It is ideal for main distribution boards in residential, commercial, and industrial
buildings, providing primary protection against direct lightning strikes and high-energy surges.
The pluggable cartridge design simplifies replacement, while integrated thermal disconnectors
and status indicators ensure safe operation. Optional RC contacts enable remote monitoring.

Caractéristiques principales

  • Type 1 SPD with 1+1 topology (L–N MOV, N–PE GDT).
  • Impulse current (Iimp): 12.5 kA (10/350 μs).
  • Nominal discharge current (In): 20 kA (8/20 μs).
  • Voltage protection level (Up): ≤ 1.5–2.0 kV depending on Uc.
  • Continuous operating voltage (Uc): 230 V AC.
  • Back-up fuse: max 160 A gL/gG; ISCCR 25 kA AC.
  • Response time < 100 ns (N–PE path).
  • Optional RC contacts: AC 250 V / 0.5 A; DC 250 V / 0.1 A.
  • Thermoplastic housing UL94 V-0, IP20; operating temperature -40 °C to +80 °C.
  • DIN rail mounting (EN 60715); IEC/EN 61643-11 compliant.

Spécifications

Product CodeKYSPD-25T1-1+1
CategoryType 1 surge protective device 1+1
Nominal System Voltage230 V AC
Topology1+1 (L–N MOV, N–PE GDT)
Impulse Current (Iimp, 10/350 μs)12.5 kA
Nominal Discharge Current (In, 8/20 μs)20 kA
Voltage Protection Level (Up)≤ 1.5–2.0 kV
Continuous Operating Voltage (Uc)230 V AC
Temps de réponse< 100 ns (N–PE)
Back-Up Fuse (max)160 A gL/gG
Short-Circuit Current Rating (ISCCR)25 kA AC
Température de fonctionnement-40 °C to +80 °C
Montage35 mm DIN rail, EN 60715
Enclosure / ProtectionThermoplastic UL94 V-0 / IP20
Remote Signaling (RC)Optional; AC 250 V / 0.5 A; DC 250 V / 0.1 A
NormesIEC/EN 61643-11

Câblage et dimensions

Connection diagram type 1 surge protective device 1+1 KYSPD-25T1-1+1

Connection diagram type 1 surge protective device 1+1 KYSPD-25T1-1+1

Dimensions type 1 surge protective device 1+1 KYSPD-25T1-1+1

Dimensions type 1 surge protective device 1+1 KYSPD-25T1-1+1

Applications

  • Main distribution boards in residential, commercial, and industrial facilities.
  • Service entrance protection against lightning-induced surges.
  • Panels in TT and TN systems requiring 1+1 SPD configuration.

FAQ

  • What topology does KYSPD-25T1-1+1 use? 1+1 topology: L–N MOV and N–PE GDT.
  • What is its surge rating? Iimp 12.5 kA (10/350 µs), In 20 kA (8/20 µs).
  • Which systems is it suitable for? Single-phase TN and TT 230 V AC systems.
  • Does it support monitoring? Yes, optional RC contacts are available.
  • What is the maximum backup fuse? 160 A gL/gG.
For detailed pricing and technical support, please contact us.Explore more Kuangya solutions: DC SPD, AC Surge Protection.

Avis

Il n’y a pas encore d’avis.

Soyez le premier à laisser votre avis sur “Type 1 Surge Protective Device 1+1 KYSPD-25T1-1+1 | Kuangya”

Votre adresse e-mail ne sera pas publiée. Les champs obligatoires sont indiqués avec *