Inverseur de source automatique modulaire sur rail DIN G2R-63 6A–63A

$14.93

Compact 2P/4P DIN rail automatic transfer switch for 6A–63A AC systems. Provides rapid automatic or manual changeover between normal and standby power, with clear status indication and voltage protection.

G2R-63 DIN Rail Modular Automatic Transfer Switch provides reliable automatic changeover between a normal power source and a standby source. Designed for low-voltage AC systems, it helps maintain power continuity for residential, commercial, industrial and solar backup applications.

Caractéristiques principales

  • Fast automatic transfer in less than 50 ms
  • Rated current options from 6A to 63A
  • 2P and 4P configurations for single-phase and three-phase systems
  • Automatic and manual operating modes
  • Over-voltage and under-voltage protection
  • DIN rail modular design for compact installation
  • Clear source and load status indication

G2R-63 Connection & Component Guide

Pure technical line drawing — select a callout to view its function.

KUANGYAG2R-63SOURCE IISOURCE ICHARGER Backup power input (II) Normal power input (I) Source I / II indicators Auto / Manual selector Transfer position indication Manual operating handle Load status indication Load output terminals

Interactive component guide

Select a label or connection line to display its function.

DIN Rail Mounting Diagram

35 mm DIN rail interfaceClip onto rail

Reference Dimensions

Overall width: 94 mmOverall height: 78 mmBody height: 70 mmRail opening: 35 mmTerminal span: 45 mmReference torque: 2,5 N-m

Verify dimensions and tightening requirements for the ordered configuration.


Technical Parameters

ModèleG2R-63
Type de produitPC-class automatic transfer switch
Courant assigné d'emploi6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A
Tension assignée d'emploiAC 110V / AC 220V
Fréquence50/60Hz
Pôles2P / 4P
Tension d'isolation nominale690V
Tension assignée de tenue aux chocs8kV
Temps de transfert<50 ms
Durée de vie mécanique≥8,000 operations
Durée de vie électrique≥1,500 operations
MontageRail DIN

Comment ça marche

When the normal power source fails or moves outside the permitted voltage range, the G2R-63 automatically transfers the load to the standby power source. When normal power is restored, the switch returns the load according to its operating logic. A manual mode is also available for commissioning and maintenance.

Applications

  • Solar and generator backup systems
  • Tableaux de distribution résidentiels
  • Commercial buildings and offices
  • Data, communication and monitoring equipment
  • Industrial control and critical auxiliary circuits

Ordering Information

Select the required rated current, operating voltage and pole configuration when requesting a quotation. Contact KUANGYA for OEM labeling, packaging and project support.

FAQ

Quelle est la différence entre les versions 2P et 4P ?

La version 2P est généralement utilisée dans les systèmes monophasés, tandis que la version 4P est conçue pour les systèmes triphasés nécessitant une coupure du neutre.

L'interrupteur peut-il être actionné manuellement ?

Oui. Le sélecteur frontal prend en charge le fonctionnement automatique et manuel.

Est-il adapté aux systèmes de secours solaires ?

Yes. It can transfer a load between normal utility power and a compatible standby source such as a generator or solar backup supply.