Dispositif de protection contre les surtensions de type 1 KYSPD-25T1-1P | Kuangya

  • Class I / Type 1 SPD for service entrance, 230/400 V AC systems.

  • Impulse current Iimp 25 kA (10/350 μs), In 25 kA, Imax 100 kA.

  • Pluggable module with visual indicator, DIN-rail, optional remote signaling (RC).

Obtenir un devis

Catégorie :
Le dispositif de protection contre les surtensions de type 1 KYSPD-25T1-1P is designed for main distribution boards and service entrances. It protects low-voltage AC installations against direct lightning currents and high-energy surges per IEC/EN 61643-11. With an impulse discharge current rating of 25 kA per pole (10/350 μs), it provides robust first-stage protection in coordinated systems.

Caractéristiques principales

  • Conforme à la norme IEC/EN 61643-11, Classe I / Type 1.
  • Impulse discharge current Iimp: 25 kA (10/350 μs); In 25 kA; Imax 100 kA.
  • Uc options: 320 V, 385 V, 440 V AC; nominal system Uo/Un 230/400 V AC.
  • Pluggable cartridge with thermal disconnector and green/red status window.
  • Optional RC terminals for remote status signaling.
  • Housing UL94 V-0, IP20 (built-in); 35 mm DIN rail mounting.
  • Suitable for TN-S / TN-C / TT systems (correct L-N / N-PE wiring).
  • Ideal as a dispositif de protection contre les surtensions de type 1 at the service entrance in coordinated SPD schemes.

Spécifications

ParamètresValeur
Code produitKYSPD-25T1-1P
CatégorieType 1 / Classe I SPD
Tension nominale du système (Uo/Un)230 / 400 V AC
Tension de fonctionnement continu (Uc) Tension de fonctionnement continu (Uc)320 / 385 / 440 V AC
Courant de décharge nominal (In, 8/20 μs)25 kA
Courant de décharge max. Courant de décharge (Imax, 8/20 μs)100 kA
Courant de décharge par impulsion (Iimp, 10/350 μs)25 kA par pôle
Niveau de protection de la tension (vers le haut)~1.6–2.0 kV (by variant)
Temps de réponse< 25 ns
Suivre Courant d'interruption nominal100 A RMS
Courant nominal de court-circuit (ISCCR)50 kA
Fusible de secours (max)315 A gL/gG
Température de fonctionnement-40 °C ... +70 °C
MontageRail DIN 35 mm (EN 60715)
EnceinteThermoplastique, UL94 V-0
Degré de protectionIP20 (intégré)
Signalisation à distanceContacts RC en option
NormesIEC 61643-11 / EN 61643-11

Câblage et dimensions

  • Schéma de connexion : kyspd-25t1-connection
  • SPD-T1-1P-wiring-diagram
  • Dimensions : kyspd-25t1-dimensions
  • SPD-T1-1P-Dimension

Applications

  • Service entrance / main distribution (LPZ 0→1) — first stage dispositif de protection contre les surtensions de type 1.
  • Industrial & commercial buildings with high lightning exposure.
  • Upstream in coordinated protection with downstream Type 2 / Type 3 SPDs.

FAQ

Where should this SPD be installed?

At the service entrance or main distribution board, as the first protection stage.

Does it support TT and TN systems?

Yes, with proper wiring modes L-N and N-PE.

Quel est le fusible de secours nécessaire ?

Maximum 315 A gL/gG, as recommended in technical data.

Can it be replaced easily?

Yes, the cartridge is pluggable and field-replaceable.

Une surveillance à distance est-elle disponible ?

Yes, RC contacts are optional for status signaling.

Qu'est-ce que la notation ISCCR ?

50 kA short-circuit withstand capacity.

Que se passe-t-il en cas de défaillance du module ?

The thermal disconnector isolates it and the indicator turns red.

What standards does it meet?

IEC/EN 61643-11 pour les dispositifs de protection contre les surtensions.

Obtenir un devis - En rapport : AC MCB, Commutateur de transfert manuel