RCCB de type B ou type A + RDC-DD ? Le guide des coûts européens 2026 pour choisir la bonne protection de recharge pour VE

For AC EV charging, the practical choice is usually between a Type B RCD et un Type A or Type F RCD combined with a 6 mA RDC-DD. Both arrangements can be suitable, but they are not interchangeable in every installation. The EV charger design, built-in DC residual-current protection, manufacturer instructions and national wiring rules determine which option is permitted.

Réponse rapide : use a Type B RCD when the charging equipment can produce smooth DC residual current and no suitable 6 mA RDC-DD is provided. A Type A or Type F RCD may be used with an IEC 62955-compliant RDC-DD when the EVSE manufacturer and local rules allow that combination. Do not select either solution from charger power alone.

Type B RCD compared with Type A RCD and 6 mA RDC-DD for EV charging

Type B RCD vs Type A + RDC-DD: Quick Comparison

Selection pointType B RCDType A/F + 6 mA RDC-DD
AC and pulsating DC residual currentDetectedDetected by the Type A or Type F RCD
Smooth DC residual currentDetected by the Type B RCDRDC-DD detects DC residual current and initiates disconnection before it can impair the upstream RCD
Equipment dependencyLower when installed as a separate protective deviceDepends on a compatible, correctly integrated RDC-DD and switching arrangement
Typical hardware costUsually higherOften lower when the charger already includes the RDC-DD
Best starting pointNo compliant RDC-DD, uncertain charger design, or manufacturer requires Type BEVSE includes compliant 6 mA DC detection and instructions permit Type A or Type F upstream

This table is a selection aid, not a substitute for the EVSE installation manual or the rules that apply in the country of installation.

Why EV Chargers Need DC Residual-Current Protection

An EV contains power-electronic circuits that can introduce a smooth DC component into a residual fault current. Excessive smooth DC can affect the magnetic operation of an upstream Type A RCD and prevent it from responding as intended to other residual-current waveforms. The installation therefore needs a defined method of dealing with this DC component.

For Mode 3 AC charging, two widely used approaches are a Type B RCD or a Type A/Type F RCD used with an RDC-DD conforming to IEC 62955. The correct arrangement must also provide any required 30 mA additional protection and suitable overcurrent protection.

How a Type B RCD Protects an EV Charging Circuit

A Type B RCCB is designed to respond to sinusoidal AC, pulsating DC and smooth DC residual currents, together with other specified waveforms and frequencies within its product standard. This makes Type B a broad residual-current protection solution for equipment using rectifiers, inverters and power converters.

The device’s rated residual operating current, such as 30 mA, must not be confused with the 6 mA DC threshold associated with an RDC-DD. A Type B RCD operates according to its specified Type B characteristics; it is not simply a “10 mA DC detector.” Always use the manufacturer’s declared curves, ratings and standards.

When Type B Is the Stronger Choice

  • The EVSE does not include compliant 6 mA DC residual-current detection.
  • The EVSE manufacturer explicitly requires a Type B RCD.
  • The possible residual-current waveform is not adequately covered by Type A or Type F plus the charger’s DC detection.
  • The designer wants residual-current protection that is less dependent on the charger’s internal monitoring and switching system.
  • Local installation rules require Type B for the proposed arrangement.

How Type A or Type F Works with a 6 mA RDC-DD

An RDC-DD is a residual direct current detecting device for Mode 3 EV charging. IEC 62955 covers RDC-DDs for permanently connected AC charging stations. Depending on its construction, the RDC-DD monitors or protects and initiates disconnection through the EVSE’s switching device when the specified DC residual-current condition occurs.

The commonly referenced 6 mA value is intended to prevent a harmful DC component from compromising the operation of the Type A or Type F RCD. The Type A/F device still performs the required residual-current protection for the waveforms within its classification; the RDC-DD addresses the DC component that the Type A device is not designed to handle by itself.

Checks Before Choosing This Combination

  • Confirm that the EVSE includes an IEC 62955-compliant RDC-DD.
  • Confirm whether the RDC-DD is an RDC-MD or RDC-PD and how disconnection is achieved.
  • Follow the EVSE manufacturer’s required upstream RCD type and rating.
  • Verify that the charger performs any required automatic monitoring or self-test.
  • Check that the complete assembly meets national wiring rules.

A Five-Step EV Charger RCD Selection Process

1. Read the EVSE Installation Manual

Find the specified upstream RCD type, rated residual operating current, overcurrent protection and whether 6 mA DC detection is built in. Marketing phrases such as “DC leakage protection” are not enough; check the declared standard and operating arrangement.

2. Identify the Charging Mode and Supply

Distinguish Mode 2 portable charging, Mode 3 AC EVSE and Mode 4 DC charging. Single-phase versus three-phase affects pole configuration and current rating, but three-phase supply alone does not automatically prove that Type B is mandatory.

3. Check Local Installation Rules

IEC standards provide an international framework, while national regulations determine the enforceable installation requirements. BS 7671, HD 60364 implementations and other national rules can differ in detail and amendment status.

4. Select Current Rating and Overcurrent Protection

An RCCB provides residual-current protection but does not replace the required overload and short-circuit protection. Coordinate it with a suitable circuit breaker or fuse. An RCBO combines residual-current and overcurrent functions, but it still needs the correct residual-current type for the EV application.

5. Verify Upstream and Downstream Coordination

Check every RCD in series. The downstream device should clear the fault without unnecessarily disconnecting unrelated circuits. Consider residual-current sensitivity, time delay, normal leakage, device type and manufacturer selectivity data. Do not assume that replacing a main Type A RCD with Type B automatically creates correct selectivity.

Selection by Installation Scenario

ScénarioPractical starting pointVerify before installation
Home wallbox with certified 6 mA RDC-DDType A or Type F, if permitted by the manufacturer and local rulesRDC-DD standard, disconnection method, 30 mA requirement and dedicated-circuit protection
Wallbox without suitable DC detectionType B RCDType B rating, poles, short-circuit backup and EVSE instructions
Three-phase 11 kW or 22 kW AC chargerEither approved arrangement may be possibleDo not decide by power alone; verify the charger’s DC protection and local rules
Multiple charging pointsIndividual protection for each point plus a coordinated upstream designNormal leakage, diversity, selectivity, monitoring and continuity of service
Existing Type A installationRetain only if the new EVSE arrangement is explicitly compatibleExisting device type, shared circuits, RDC-DD integration and board capacity
DC fast-charging equipmentFollow the equipment manufacturer’s dedicated designAC-input protection does not protect the DC output; different standards and risks apply

Cost Comparison Without Misleading Fixed Prices

A Type B RCD normally has a higher device cost than a Type A RCD. However, comparing only those two prices is incomplete. A Type A solution also depends on the cost and certification of the RDC-DD, its switching device, integration, testing and replacement strategy. If a compliant RDC-DD is already built into the charger, the Type A/F combination can reduce external hardware cost.

  • Compare the complete installed system, not one protective device.
  • Include enclosure space, contactors, wiring, commissioning and periodic testing.
  • Consider downtime and fault-finding costs for multi-point sites.
  • Request a current quotation because device prices vary by rating, pole count, certification and market.

Normes pertinentes

StandardRelevance
IEC 62955RDC-DDs for permanently connected Mode 3 AC EV charging stations
IEC 61851-1General requirements for conductive EV charging systems
IEC 60364-7-722 / national adoptionElectrical installations supplying electric vehicles
IEC 62423Additional requirements for Type F and Type B RCDs
IEC 61008-1RCCBs without integral overcurrent protection
IEC 61009-1RCBOs with integral overcurrent protection

Always check the edition and national amendments in force for the project. Compliance with a product standard does not by itself prove that a particular installation arrangement complies with local wiring rules.

Questions fréquemment posées

Can I use a Type A RCD for an EV charger?

Yes, when the EVSE includes suitable 6 mA DC residual-current detection, its manufacturer permits Type A upstream, and the complete arrangement satisfies local installation rules. Type A alone is not a universal solution for an EV charger that can produce smooth DC residual current.

Does every EV charger require a Type B RCD?

No. A Type A or Type F RCD used with an IEC 62955-compliant RDC-DD is a recognised arrangement for many Mode 3 chargers. The charging-station instructions and national rules decide whether it is acceptable for a specific installation.

What does the 6 mA rating mean?

It refers to the DC residual-current detection used to initiate disconnection before smooth DC can compromise the upstream Type A or Type F RCD. It is different from the 30 mA rated residual operating current commonly used for additional protection.

Is an RDC-DD the same as an RCD?

No. IEC 62955 distinguishes residual direct current monitoring and protective arrangements. An RDC-DD addresses DC residual-current conditions in the EV charging system; the installation can still require a Type A, Type F or other RCD for residual-current protection.

Is Type B always safer than Type A plus RDC-DD?

Type B covers a broader set of residual-current waveforms in one RCD, but safety depends on correct selection, installation and coordination. A compliant Type A/F plus RDC-DD arrangement can be appropriate when it is designed and installed as specified.

Does a three-phase charger automatically need Type B?

No. Three-phase chargers can be available with integrated 6 mA RDC-DD protection as well as Type B solutions. Check the actual EVSE architecture and installation manual rather than deciding from phase count alone.

Un RCCB protège-t-il contre les surcharges ?

No. An RCCB needs coordinated overcurrent protection from an MCB, fuse or other suitable device. An RCBO combines residual-current, overload and short-circuit protection in one unit.

Final Selection Checklist

  • Charging mode and AC or DC charger type confirmed
  • EVSE manufacturer instructions reviewed
  • Built-in 6 mA RDC-DD and IEC 62955 compliance verified
  • Type A, Type F or Type B selected for the expected residual-current waveform
  • 30 mA additional protection requirement checked
  • Rated current, poles and overcurrent protection selected
  • Upstream RCD selectivity and normal leakage assessed
  • National wiring rules and current amendments confirmed

The best option is the one verified for the complete charging system. Choose Type B when broad DC-sensitive protection is required or the EVSE lacks a suitable RDC-DD. Choose Type A or Type F with a 6 mA RDC-DD only when the charger documentation and applicable rules support that combination.

For current Type B RCCB specifications, pole configurations and project selection support, review KUANGYA’s de disjoncteurs différentiels résiduels (RCCB) ou contact the technical team.

elaine
elaine

Responsable du marketing chez Kuangya, axé sur la promotion mondiale des solutions de protection électrique et de distribution d'énergie.● Domaines principaux : Développement de la marque sur les marchés du photovoltaïque, du stockage de l'énergie et de l'alimentation industrielle.● Produits professionnels : Fusibles, dispositifs de protection contre les surtensions (SPD), disjoncteurs miniatures (MCB) et commutateurs de transfert.● Proposition de valeur : Servir le marché mondial des énergies renouvelables avec "Sécurité, fiabilité et innovation" comme pierres angulaires.Bienvenue pour se connecter et collaborer pour faire avancer conjointement le progrès de la technologie de distribution d'énergie intelligente.