RCCB VFL008 - Interruptor diferencial residual

  • Circuit breaker RCCB type protection for residential, commercial, and light-industrial systems

  • 2P/4P options, rated current 16–100 A, sensitivities 30/100/300 mA, Ue 240 V (2P) / 415 V (4P)

  • IEC/EN 61008-1 compliance, high endurance, DIN-rail mounting, CE & UKCA

Solicitar presupuesto

Categoría:

Visión general

The Kuangya VFL008 disyuntor tipo rccb disconnects the circuit when residual current exceeds the
preset threshold, preventing electric shock and fire hazards due to insulation faults. Available in both 2-pole and
4-pole versions, this circuit breaker rccb type suits single-phase and three-phase distribution boards in homes,
offices, and light-industrial facilities.

Características principales

  • Postes: 2P / 4P
  • Corriente nominal (In): 16, 25, 32, 40, 63, 80, 100 A
  • Sensibilidad nominal (IΔn): 30 / 100 / 300 mA
  • Tensión nominal (Ue): 240 V~ (2P) / 415 V~ (4P)
  • Tensión de aislamiento (Ui): 500 V |   Frecuencia: 50/60 Hz
  • Fabricación y rotura residual (IΔm): 500 A (En 16-40 A); 630 A (63 A); 800 A (80 A); 1000 A (100 A)
  • Conditional short-circuit current (Inc = IΔc): 6 kA / 10 kA (with upstream SCPD coordination)
  • Resistencia al impulso (Uimp): 6 kV; Prueba dieléctrica: 2,5 kV (1 min)
  • Resistencia: ≥20,000 mechanical / ≥2000 electrical operations
  • Protección de terminales: IP20; fault current indicator
  • Ambient: −25 °C to +55 °C (daily avg ≤ 35 °C); Storage: -40 °C a +70 °C
  • Cableado: cable 25–35 mm² or pin-type busbar; top/bottom connection
  • Montaje: DIN rail EN 60715 (35 mm), fast clip
  • Standards/Approvals: IEC/EN 61008-1; CE / UKCA

Datos técnicos

ModeloVFL008
Postes2P, 4P
Corriente nominal (In)16A, 25A, 32A, 40A, 63A, 80A, 100A
Sensibilidad nominal (IΔn)30 mA, 100 mA, 300 mA
Tensión nominal (Ue)2P: 240 V~; 4P: 415 V~
Tensión de aislamiento (Ui)500 V
Frecuencia nominal50/60 Hz
Fabricación y rotura de residuos (IΔm)500 A (In = 16–40 A); 630 A (In = 63 A); 800 A (In = 80 A); 1000 A (In = 100 A)
Cortocircuito condicional (Inc = IΔc)6000 A, 10000 A
Tripping time classesInstantaneous / Short time delay (10–300 ms) / Selective S (150–500 ms)
Break time under IΔn (Normal)≤ 100 ms
Resistencia al impulso (Uimp)6 kV
Dielectric test voltage2,5 kV (1 min)
Pollution degree2
Electrical life≥ 2000 operations
Mechanical life≥ 2000 operations
Grado de protección de los terminalesIP20
Ambient temperature (avg ≤ 35 °C)−25 °C to +55 °C
Temperatura de almacenamiento-40 °C a +70 °C
Conexión de terminalesCable / Barra colectora con pasador
Tamaño del terminal (cable)25–35 mm²; 18–3 / 18–2 AWG
Tamaño del terminal (barra colectora)10/16 mm²; 18–8 / 18–5 AWG
Par de apriete2.5 N·m (≈ 22 in-lbs)
MontajeCarril DIN EN 60715 (35 mm)
ConexiónArriba y abajo
ApprovalsCE, UKCA

Aplicaciones

  • Residential distribution boards (30 mA additional protection)
  • Commercial buildings requiring coordinated leakage and short-circuit protection
  • Light-industrial panels; consider short-time-delay or S-selective per coordination study

circuit breaker rccb type VFL008 Kuangya 2P/4P 16–100A 30/100/300 mA