Dispositivo de protección contra sobretensiones de 240 V KYSPD-20T2+3-3P+1N | Kuangya

  • 240V surge protection device con 3+1 topology (L1-L2-L3-N) for 230/400 V AC networks.

  • Surge ratings: In 10 kA (8/20 µs), Imax 20 kA (8/20 µs), Up ≤ 0.3–1.8 kV en función de Uc.

  • Combines MOV + GDT technology for L–N and N–PE coordinated protection, pluggable modules, optional RC signaling contacts.

Solicitar presupuesto

Categoría:
The Kuangya KYSPD-20T2+3-3+1 is a 240V surge protection device designed for three-phase + neutral systems at 230/400 V AC. It uses a 3+1 topology, with MOV protection for L–N and coordinated GDT+MOV protection for N–PE, offering reliable suppression of transient overvoltages from lightning and switching surges.Its compact pluggable cartridge design allows easy replacement, while integrated thermal disconnectors ensure safe operation. Visual green/red indicators provide status feedback, and optional RC contacts enable remote fault monitoring.

Características principales

  • Class II+III / Type 2+3 surge protection device with 3+1 topology.
  • Nominal discharge current (In): 10 kA (8/20 μs).
  • Maximum discharge current (Imax): 20 kA (8/20 μs).
  • Voltage protection level (Up): ≤ 0.3–1.8 kV depending on Uc (75–440 V).
  • Tiempo de respuesta: < 25 ns (L-N), < 100 ns (N-PE).
  • Back-up fuse: max 63 A gL/gG; ISCCR 10 kA AC.
  • Pluggable module, thermal disconnector, green/red fault status indicator.
  • Optional RC remote signaling contacts for BMS/PLC integration.
  • Housing IP20, UL94 V-0 thermoplastic; operating temperature -40 °C to +70 °C.
  • Montaje en carril DIN (35 mm, EN 60715); conforme a IEC/EN 61643-11.

Especificaciones

Código del productoKYSPD-20T2+3-3+1
Categoría240V surge protection device
Tensión nominal del sistema230/400 V CA
Topología3+1 (L–N MOV, N–PE GDT+MOV)
Tensión de funcionamiento continuo (Uc)75 / 150 / 275 / 320 / 385 / 440 V
Corriente nominal de descarga (In, 8/20 μs)10 kA
Corriente de descarga máxima (Imax, 8/20 μs)20 kA
Nivel de protección de tensión (arriba)≤ 0.3–1.8 kV
Tiempo de respuesta< 25 ns (L–N), < 100 ns (N–PE)
Fusible de reserva (máx.)63 A gL/gG
Corriente nominal de cortocircuito (ISCCR)10 kA AC
Temperatura de funcionamiento-40 °C to +70 °C
MontajeCarril DIN de 35 mm, EN 60715
Cerramiento / ProtecciónTermoplástico UL94 V-0 / IP20
Señalización remota (RC)Opcional; CA 250 V / 0,5 A; CC 250 V / 0,1 A; 125 V / 0,2 A; 75 V / 0,5 A
NormasCEI/EN 61643-11

Cableado y dimensiones

Connection diagram 240V surge protection device KYSPD-20T2+3-3+1

Connection diagram 240V surge protection device KYSPD-20T2+3-3+1

Dimensions 240V surge protection device KYSPD-20T2+3-3+1

Dimensions 240V surge protection device KYSPD-20T2+3-3+1

Aplicaciones

  • Main distribution boards in residential and commercial buildings (240V systems).
  • Protection of elevators, industrial control systems, and sensitive electronics.
  • Panels requiring coordinated 3+1 surge protection in TT/TN-S networks.

PREGUNTAS FRECUENTES

  • What topology does KYSPD-20T2+3-3+1 use? It uses 3+1 topology: L–N MOV, N–PE GDT+MOV.
  • What is its surge discharge capacity? In 10 kA, Imax 20 kA.
  • Where is it applied? In 230/400 V AC three-phase + N systems, especially 240V distribution panels.
  • Does it support monitoring? Yes, optional RC contacts provide remote signaling.
  • What is the maximum back-up fuse rating? 63 A gL/gG.