Type 2+3 Surge Protective Device for Equipment KYSPD-20T2+3-1+1 | Kuangya

  • Type 2+3 surge protective device for equipment, designed for single-phase 230 V AC systems.

  • Surge ratings: In 10 kA (8/20 µs), Imax 20 kA (8/20 µs), Up ≤ 1.5 kV en función de Uc.

  • Topología 1+1 (L-N MOV + N-PE GDT) for coordinated equipment-level protection, pluggable cartridge, optional RC contacts.

Solicitar presupuesto

Categoría:
The Kuangya KYSPD-20T2+3-1+1 is a Type 2+3 surge protective device for equipment
specifically designed to protect sensitive electronic and electrical devices connected to single-phase 230 V AC systems.
It combines Type 2 protection against switching surges with Type 3 fine protection for terminal equipment.The SPD uses a 1+1 topology, employing MOV suppression between L–N and a GDT discharge path between N–PE.
Its pluggable module design ensures easy maintenance, while integrated thermal disconnectors and status indicators enhance operational safety.
Optional RC contacts provide remote fault signaling for monitoring systems.

Características principales

  • Type 2+3 SPD with 1+1 topology: L–N (MOV), N–PE (GDT).
  • Nominal discharge current (In): 10 kA (8/20 μs).
  • Maximum discharge current (Imax): 20 kA (8/20 μs).
  • Voltage protection level (Up): ≤ 1.5 kV depending on Uc.
  • Continuous operating voltage (Uc): 230 V AC typical.
  • Tiempo de respuesta: < 25 ns (L-N), < 100 ns (N-PE).
  • Back-up fuse: max 63 A gL/gG; ISCCR 10 kA AC.
  • Pluggable cartridges with thermal disconnector and green/red fault status indicator.
  • Optional RC signaling contacts for BMS/PLC integration.
  • Housing: UL94 V-0 thermoplastic, IP20; operating temperature -40 °C to +70 °C.
  • Mounting: DIN rail (35 mm, EN 60715); IEC/EN 61643-11 compliant.

Especificaciones

Código del productoKYSPD-20T2+3-1+1
CategoríaType 2+3 surge protective device for equipment
Tensión nominal del sistema230 V AC
Topología1+1 (L-N MOV, N-PE GDT)
Tensión de funcionamiento continuo (Uc)230 V
Corriente nominal de descarga (In, 8/20 μs)10 kA
Corriente de descarga máxima (Imax, 8/20 μs)20 kA
Nivel de protección de tensión (arriba)≤ 1.5 kV
Tiempo de respuesta< 25 ns (L–N), < 100 ns (N–PE)
Fusible de reserva (máx.)63 A gL/gG
Corriente nominal de cortocircuito (ISCCR)10 kA AC
Temperatura de funcionamiento-40 °C to +70 °C
MontajeDIN rail 35 mm, EN 60715
Cerramiento / ProtecciónTermoplástico UL94 V-0 / IP20
Señalización remota (RC)Optional; AC 250 V / 0.5 A; DC 250 V / 0.1 A
NormasCEI/EN 61643-11

Cableado y dimensiones

Connection diagram type 2+3 surge protective device KYSPD-20T2+3-1+1

Connection diagram type 2+3 surge protective device KYSPD-20T2+3-1+1

Dimensions type 2+3 surge protective device KYSPD-20T2+3-1+1

Dimensions type 2+3 surge protective device KYSPD-20T2+3-1+1

Aplicaciones

  • Protection of sensitive equipment in residential and commercial buildings.
  • Applied in single-phase panels requiring both Type 2 and Type 3 coordination.
  • Used for downstream protection of electronics, IT hardware, and control devices.

PREGUNTAS FRECUENTES

  • What topology does KYSPD-20T2+3-1+1 use? It uses a 1+1 topology: L–N MOV, N–PE GDT.
  • What is its surge discharge capacity? In 10 kA, Imax 20 kA.
  • Where is it applied? Equipment-level protection in single-phase 230 V AC networks.
  • Does it support remote signaling? Sí, hay disponibles contactos RC opcionales.
  • What is the maximum back-up fuse? 63 A gL/gG.
Para precios detallados y asistencia técnica, por favor ContactoExplore más soluciones Kuangya: DC SPD, Protección contra sobretensiones de CA.

Valoraciones

No hay valoraciones aún.

Sé el primero en valorar “Type 2+3 Surge Protective Device for Equipment KYSPD-20T2+3-1+1 | Kuangya”

Tu dirección de correo electrónico no será publicada. Los campos obligatorios están marcados con *