Two-pole dispositivo de protección contra sobretensiones de tipo 1 for service entrance, tested to IEC/EN 61643-11.
Handles Iimp 25 kA (10/350 μs) per pole, In 25 kA, Imax 100 kA; Uo/Un 230/400 V AC; Uc 320/385/440 V.
Pluggable cartridge with visual status indicator, DIN-rail mounting, optional RC remote signaling.
Parámetro | Value |
---|---|
Código del producto | KYSPD-25T1-2P |
Categoría | Type 1 / Class I SPD |
Nominal System Voltage (Uo/Un) | 230 / 400 V AC |
Max. Continuous Operating Voltage (Uc) | 320 / 385 / 440 V AC |
Corriente nominal de descarga (In, 8/20 μs) | 25 kA |
Max. Discharge Current (Imax, 8/20 μs) | 100 kA |
Impulse Discharge Current (Iimp, 10/350 μs) | 25 kA per pole |
Nivel de protección de tensión (arriba) | ~1.6–2.0 kV |
Tiempo de respuesta | < 25 ns |
Follow Current Interrupt Rating | 100 A RMS |
Corriente nominal de cortocircuito (ISCCR) | 50 kA |
Backup Fuse (max) | 315 A gL/gG |
Temperatura de funcionamiento | -40 °C … +70 °C |
Montaje | 35 mm DIN rail (EN 60715) |
Enclosure | Thermoplastic, UL94 V-0 |
Protection Degree | IP20 (built-in) |
Remote Signaling | Optional RC contacts |
Normas | IEC 61643-11 / EN 61643-11 |
At the service entrance or main distribution board, as the first stage of protection.
Yes, TN-S, TN-C, and TT systems are supported with correct wiring.
A maximum 315 A gL/gG fuse is recommended.
The cartridge is pluggable. Isolate power, remove the old module, insert the new one, and restore power.
Yes, optional RC terminals provide remote status signaling.
The device withstands up to 50 kA short-circuit current.
The thermal disconnector trips and the status indicator turns red.
IEC/EN 61643-11 for low-voltage surge protective devices.