Surge Protection Device for Elevators KYSPD-40T2-3+1 | Kuangya

  • Surge protection device for elevators, designed for three-phase + N (3+1 topology) at 230/400 V AC.

  • Surge ratings: In 20 kA (8/20 µs), Imax 40 kA (8/20 µs), Up ≤ 1.5–2.0 kV en función de Uc.

  • Características L–N MOV + N–PE GDT coordinated protection, pluggable modules, thermal disconnector, optional RC signaling contacts.

Solicitar presupuesto

Categoría:
The Kuangya KYSPD-40T2-3+1 is a specialized dispositivo de protección contra sobretensiones para ascensores,
designed to safeguard lift control systems, drives, and associated electrical panels
in residential, commercial, and industrial buildings. Using a 3+1 topology, it provides
coordinated protection for L-N (MOV) and N-PE (GDT) paths in 230/400 V AC networks.This device is built for high reliability in vertical transport applications,
where electrical disturbances may cause malfunction or downtime. Its pluggable design,
thermal disconnector, and clear status indicators simplify service and ensure safety.
Optional RC contacts allow real-time monitoring and integration with building management systems.

Características principales

  • Optimized surge protection for elevator systems (control panels, drives, motors).
  • 3+1 topology: MOV protection L–N and coordinated GDT+MOV protection N–PE.
  • Nominal discharge current (In): 20 kA (8/20 μs); Maximum discharge current (Imax): 40 kA (8/20 μs).
  • Voltage protection level (Up): ≤ 1.5–2.0 kV depending on Uc.
  • Fast response time < 25 ns for L–N; < 100 ns for N–PE.
  • Fusible de reserva: máx. 125 A gL/gG; ISCCR 25 kA CA.
  • Optional RC remote signaling contacts: AC 250 V / 0.5 A; DC 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A.
  • Housing IP20, thermoplastic UL94 V-0; operating temperature -40 °C to +80 °C.
  • Montaje en carril DIN (35 mm, EN 60715); conforme a IEC/EN 61643-11.

Especificaciones

Código del productoKYSPD-40T2-3+1
CategoríaSurge protection device for elevators
Tensión nominal del sistema230/400 V CA
Topología3+1 (L–N MOV, N–PE GDT+MOV)
Tensión de funcionamiento continuo (Uc)230 V / 320 V / 385 V
Corriente nominal de descarga (In, 8/20 μs)20 kA
Corriente de descarga máxima (Imax, 8/20 μs)40 kA
Nivel de protección de tensión (arriba)≤ 1.5–2.0 kV
Tiempo de respuesta< 25 ns (L-N) / < 100 ns (N-PE)
Fusible de reserva (máx.)125 A gL/gG
Corriente nominal de cortocircuito (ISCCR)25 kA CA
Temperatura de funcionamiento-40 °C a +80 °C
MontajeCarril DIN de 35 mm, EN 60715
Cerramiento / ProtecciónTermoplástico UL94 V-0 / IP20
Señalización remota (RC)Opcional; CA 250 V / 0,5 A; CC 250 V / 0,1 A; 125 V / 0,2 A; 75 V / 0,5 A
NormasCEI/EN 61643-11

Cableado y dimensiones

Connection diagram surge protection device for elevators KYSPD-40T2-3+1

Connection diagram surge protection device for elevators KYSPD-40T2-3+1

Dimensions surge protection device for elevators KYSPD-40T2-3+1

Dimensions surge protection device for elevators KYSPD-40T2-3+1

Aplicaciones

  • Elevator control panels and drive systems in residential and commercial buildings.
  • Protection of lift equipment from lightning-induced and switching surges.
  • Building electrical panels requiring coordinated 3+1 surge protection with monitoring.

PREGUNTAS FRECUENTES

  • Why is this SPD suitable for elevators? It uses a 3+1 topology optimized for protecting sensitive elevator controls and drives.
  • What is its surge capacity? In 20 kA, Imax 40 kA per path.
  • Does it support monitoring? Yes, optional RC contacts provide remote fault indication.
  • What is the backup fuse rating? Maximum 125 A gL/gG.
  • ¿Qué normas cumple? IEC/EN 61643-11.
Para precios detallados y asistencia técnica, por favor Contacto.Explore more Kuangya products: DC SPD, Protección contra sobretensiones de CA.

Valoraciones

No hay valoraciones aún.

Sé el primero en valorar “Surge Protection Device for Elevators KYSPD-40T2-3+1 | Kuangya”

Tu dirección de correo electrónico no será publicada. Los campos obligatorios están marcados con *