Three-phase Überspannungsschutzgerät für Schalttafel in 3+1 topology (L-N + N-PE) for TT / TN-S networks at 230/400 V AC.
Surge ratings (L-N / N-PE): Iimp 12.5 kA / 50 kA (10/350 µs), In 20 kA / 50 kA (8/20 µs), Imax 50 kA / 100 kA (8/20 µs); typical Nach oben options from 1.0/1.5 kV up to 2.0/1.5 kV by variant.
Pluggable modules, thermal disconnector with green/red status, optional RC remote contacts; IP20 housing, UL94-V0 thermoplastic, 35 mm DIN-rail mount.
Produkt-Code | KYSPD-12.5T1+2-3+1 |
---|---|
Kategorie | Surge protection device for electrical panel |
Nominal System Voltage (Uo/Un) | 230/400 V AC |
Network / Topology | TT, TN-S / 3+1 (L-N + N-PE) |
Max. Continuous Operating Voltage (Uc) | (L-N) 150/275/320/385/440 V; (N-PE) 255 V |
Nenn-Entladestrom (In, 8/20 μs) | (L-N / N-PE) 20 kA / 50 kA |
Maximum Discharge Current (Imax, 8/20 μs) | (L-N / N-PE) 50 kA / 100 kA |
Impulse Discharge Current (Iimp, 10/350 μs) | (L-N / N-PE) 12.5 kA / 50 kA |
Spannungsschutzstufe (Up) | 1.0/1.5 kV, 1.5/1.5 kV, 1.6/1.5 kV, 1.8/1.5 kV, 2.0/1.5 kV |
Follow Current Interrupt Rating (Ifi) | 100 A RMS (N-PE) |
Reaktionszeit | < 25 ns / < 100 ns (L-N / N-PE) |
Backup Fuse (max) | 160 A gL/gG |
ISCCR | 25 kA AC |
Betriebstemperatur | -40 °C to +70 °C |
Montage | 35 mm DIN rail (EN 60715) |
Gehäuse / Schutz | Thermoplastischer Kunststoff UL94 V-0 / IP20 |
Fernsignalisierung (RC) | Optional; AC 250 V / 0,5 A; DC 250 V / 0,1 A; 125 V / 0,2 A; 75 V / 0,5 A |
Normen | IEC/EN 61643-11 |
Connection diagram surge protection device for electrical panel 3+1
Dimensions surge protection device for electrical panel 3+1