rcbo single pole (1P+N) RCBO for residential & commercial branches, In 5–40A, curves B/C.
Typ AC / Typ A, sensitivities IΔn 6 / 10 / 30 / 100 / 300 mA; Icn up to 10 kA @ 240 V (VKL003) / 15 kA @ 120 V (VKL003N).
SEMKO / UKCA / CE / SAA certified; electrical & mechanical endurance 2,000 cycles; DIN-rail mounting with front test button.
rcbo einpolig VKL003 / VKL003N is a compact 1P+N residual-current circuit breaker with overcurrent protection, rated 5–40 A with Type AC/A, multiple sensitivities, and B/C curves for residential and commercial distribution circuits.
VKL003 and VKL003N provide combined protection against overload, short circuit, and
residual current faults on single-phase branches. Both share the same 1P+N form factor
and current range (5–40 A). VKL003 targets 240 V systems with breaking capacity
up to 10 kA, while VKL003N is optimized for 120 V systems with
15 kA Icn. Type AC and Type A options plus five sensitivity levels enable precise
coordination across lighting and socket circuits.
Parameter | VKL003 | VKL003N |
---|---|---|
Pole | 1P+N (single-pole + neutral) | |
Nennstrom (In) | 5–40 A | 5–40 A |
Nennspannung (Ue) | AC 240 V | AC 120 V |
Frequenz | 50/60 Hz | |
Fehlerstrom-Typ | Typ AC / Typ A | |
Bemessungsfehlerstrom (IΔn) | 6 / 10 / 30 / 100 / 300 mA | |
Tripping characteristic (MCB curve) | B: 3–5 × In; C: 5–10 × In | |
Ausschaltvermögen (Icn) | 4.5 / 6 / 10 kA @ 240 V | 15 kA @ 120 V |
Ausdauer | Electrical 2,000 cycles; Mechanical 2,000 cycles | |
Einrichtung | DIN-Schiene; Frontverdrahtung; Testtaste (T) | |
Recommended applications | Residential & commercial lighting and socket branches | |
Zertifizierungen | SEMKO, UKCA, CE, SAA | |
Normen | IEC/EN 61009-1 |
Conforms to IEC/EN 61009-1. Certified by SEMKO, UKCA, CE, SAA.
Coordinate with upstream protection and follow local codes for selectivity and fault levels.
Both are 1P+N, 5–40 A with Type AC/A and five IΔn levels. VKL003 is for 240 V (up to 10 kA Icn); VKL003N is for 120 V (15 kA Icn).
Use curve B (3–5×In) for resistive/lightly inductive loads; use curve C (5–10×In) for circuits with higher inrush such as motors or transformers.
The compact 1P+N layout saves rail width while providing full residual and overcurrent protection—ideal for lighting and socket branches.