{"id":5053,"date":"2026-11-26T09:43:06","date_gmt":"2026-11-26T01:43:06","guid":{"rendered":"https:\/\/cnkuangya.com\/?p=5053"},"modified":"2026-11-26T09:48:23","modified_gmt":"2026-11-26T01:48:23","slug":"circuit-breaker-auxiliary-vs-alarm-contacts-of-sd-and-sde","status":"publish","type":"post","link":"https:\/\/cnkuangya.com\/pt\/blog\/circuit-breaker-auxiliary-vs-alarm-contacts-of-sd-and-sde\/","title":{"rendered":"Circuit Breaker Auxiliary vs Alarm Contacts: OF, SD and SDE"},"content":{"rendered":"<p>OF reports breaker position. SD reports a trip. On supported models, SDE identifies an electrical fault trip. Use trip-unit diagnostics, where available, to investigate the specific cause.<\/p>\n<h2>What OF, SD and SDE report<\/h2>\n<p>In Schneider Electric\u2019s <a href=\"https:\/\/productinfo.se.com\/compactnsxdclegacyuserguide\/doca0066-compact-nsx-dc-legacy-user-guide\/English\/DOCA0066EN-05.pdf\" rel=\"noopener\">ComPact NSX DC user guide<\/a>, OF indicates main contact position. SD indicates a trip, including operation by a shunt trip or undervoltage release, the push-to-trip button, or the trip unit. SDE indicates a trip due to an electrical fault detected by the trip unit. These definitions describe the cited product and configuration. Other families can use different labels or support fewer functions.<\/p>\n<table>\n<thead>\n<tr>\n<th>What the operator needs to know<\/th>\n<th>Signal to look for<\/th>\n<th>What to confirm<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Is the breaker open or closed?<\/td>\n<td>Position indication, such as OF<\/td>\n<td>Contact state in ON, OFF and tripped conditions<\/td>\n<\/tr>\n<tr>\n<td>Did the breaker trip?<\/td>\n<td>Trip indication, such as SD<\/td>\n<td>Which releases and test operations activate it<\/td>\n<\/tr>\n<tr>\n<td>Did the trip unit detect an electrical fault?<\/td>\n<td>Electrical fault indication, such as SDE<\/td>\n<td>Which protection functions activate the output<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<h2>Example: a remote panel reports a breaker open<\/h2>\n<p>An open-position signal alone cannot establish why a feeder opened. In the documented ComPact NSX DC arrangement, an active SD signal distinguishes a trip from ordinary manual switching. The table shows logical indications, not PLC input levels. Verify the actual NO\/NC terminals and input mapping for your installation.<\/p>\n<table>\n<thead>\n<tr>\n<th>Event or state<\/th>\n<th>OF position<\/th>\n<th>SD trip<\/th>\n<th>SDE electrical fault trip<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>Manual OFF with no active trip indication<\/td>\n<td>Open<\/td>\n<td>Inactive<\/td>\n<td>Inactive<\/td>\n<\/tr>\n<tr>\n<td>Shunt trip or undervoltage release operates<\/td>\n<td>Open<\/td>\n<td>Active<\/td>\n<td>Inactive<\/td>\n<\/tr>\n<tr>\n<td>Trip unit detects an electrical fault and trips<\/td>\n<td>Open<\/td>\n<td>Active<\/td>\n<td>Active<\/td>\n<\/tr>\n<tr>\n<td>Trip reset, breaker still open and indications cleared<\/td>\n<td>Open<\/td>\n<td>Inactive<\/td>\n<td>Inactive<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p>The last row can look identical to manual OFF at the PLC. Log and timestamp signal transitions to preserve the trip event. Use available trip-unit records to distinguish causes such as overload and short circuit.<\/p>\n<h2>Check compatibility before ordering<\/h2>\n<ol>\n<li>Record the breaker series, frame, exact part number and any trip unit or release fitted.<\/li>\n<li>Check the accessory part number, mounting position and how many compatible slots are available. Schneider\u2019s <a href=\"https:\/\/productinfo.se.com\/gv5pbgv6pbdocumentation\/viewer?docidentity=Chapter4-015872D5&amp;extension=xml&amp;lang=en&amp;manualidentity=DocumentTypeProductCategoryRangeNam-FCAF67FC\" rel=\"noopener\">GV5PB\/GV6PB documentation<\/a> shows why mounting location can determine which signal an accessory provides.<\/li>\n<li>Match the contact\u2019s voltage and current ratings to the control circuit. For a low current PLC input, check the specified minimum switching load where published. Verify NO and NC states from the device diagram.<\/li>\n<li>Document the expected input states for manual OFF, trip and reset. Have qualified personnel confirm the states with the manufacturer\u2019s approved commissioning procedure and proper isolation. A PLC indication cannot establish that conductors are de-energized.<\/li>\n<\/ol>\n<h2>Can the signal distinguish a trip from a broken wire?<\/h2>\n<p>With a single dry contact input, a broken wire can look like an intentional contact opening. If the circuit signals an alarm by closing the contact, a broken wire can prevent the PLC from seeing a genuine trip. Where the operator must distinguish these states, specify a compatible supervised circuit. Include normal operation, a trip and a signal-loop break in the commissioning checks, and verify that each produces the intended indication.<\/p>\n<h2>What should a panel builder send to KUANGYA?<\/h2>\n<p>Send the breaker part number, desired events, control voltage, PLC input details and number of signals. Start with the <a href=\"https:\/\/cnkuangya.com\/pt\/ac-circuit-breaker\/\">AC circuit breaker range<\/a> ou <a href=\"https:\/\/cnkuangya.com\/pt\/mcb\/\">AC MCB range<\/a>. For an application where source terminal orientation also matters, see our <a href=\"https:\/\/cnkuangya.com\/pt\/blog\/can-you-backfeed-a-solar-inverter-breaker-line-and-load-explained\/\">breaker reverse feed guide<\/a>.<\/p>","protected":false},"excerpt":{"rendered":"<p>OF reports breaker position. SD reports a trip. On supported models, SDE identifies an electrical fault trip. Use trip-unit diagnostics, where available, to investigate the specific cause. What OF, SD and SDE report In Schneider Electric\u2019s ComPact NSX DC user guide, OF indicates main contact position. SD indicates a trip, including operation by a shunt [&hellip;]<\/p>\n","protected":false},"author":4,"featured_media":0,"comment_status":"closed","ping_status":"closed","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[35,55],"tags":[],"class_list":["post-5053","post","type-post","status-publish","format-standard","hentry","category-blog","category-circuit-breakers"],"blocksy_meta":[],"_links":{"self":[{"href":"https:\/\/cnkuangya.com\/pt\/wp-json\/wp\/v2\/posts\/5053","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/cnkuangya.com\/pt\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/cnkuangya.com\/pt\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/cnkuangya.com\/pt\/wp-json\/wp\/v2\/users\/4"}],"replies":[{"embeddable":true,"href":"https:\/\/cnkuangya.com\/pt\/wp-json\/wp\/v2\/comments?post=5053"}],"version-history":[{"count":2,"href":"https:\/\/cnkuangya.com\/pt\/wp-json\/wp\/v2\/posts\/5053\/revisions"}],"predecessor-version":[{"id":5056,"href":"https:\/\/cnkuangya.com\/pt\/wp-json\/wp\/v2\/posts\/5053\/revisions\/5056"}],"wp:attachment":[{"href":"https:\/\/cnkuangya.com\/pt\/wp-json\/wp\/v2\/media?parent=5053"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/cnkuangya.com\/pt\/wp-json\/wp\/v2\/categories?post=5053"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/cnkuangya.com\/pt\/wp-json\/wp\/v2\/tags?post=5053"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}