{"id":2267,"date":"2025-12-12T02:14:03","date_gmt":"2025-12-12T02:14:03","guid":{"rendered":"https:\/\/cnkuangya.com\/?p=2267"},"modified":"2026-11-05T11:14:06","modified_gmt":"2026-11-05T03:14:06","slug":"why-every-pv-string-needs-surge-protection","status":"publish","type":"post","link":"https:\/\/cnkuangya.com\/pt\/blog\/why-every-pv-string-needs-surge-protection\/","title":{"rendered":"Prote\u00e7\u00e3o contra Surtos de String PV: Quando e Onde os DPS s\u00e3o Necess\u00e1rios"},"content":{"rendered":"<p><strong>Resposta r\u00e1pida:<\/strong> Not every PV string needs its own surge protective device (SPD). Whether DC-side surge protection is required, and whether a second SPD belongs near the array or combiner, depends on the local rules, lightning exposure, cable route, inverter arrangement and the installation&#8217;s lightning protection system. A PV-rated SPD near the inverter may be enough for a short DC run; longer runs may need a second device near the array.<\/p>\n<h2>Onde a prote\u00e7\u00e3o contra surtos fotovoltaicos deve ser instalada<\/h2>\n<p>Assess the DC side and AC side separately. On the DC side, identify the array, string combiner boxes, inverter inputs, cable lengths and equipotential bonding path. Schneider Electric&#8217;s <a href=\"https:\/\/www.electrical-installation.org\/enwiki\/SPD_for_photovoltaic_applications\" rel=\"noopener\">Guia de Instala\u00e7\u00f5es El\u00e9tricas para DPS fotovoltaicos<\/a> describes an SPD near the inverter and, when the array-to-inverter cable route exceeds about 10 m in its design example, an additional SPD near the modules or array box. Apply that guidance with the project&#8217;s adopted rules and equipment instructions; the distance is not a universal requirement to fit an SPD on every string.<\/p>\n<p>Para a sa\u00edda CA e o quadro de distribui\u00e7\u00e3o principal, selecione DPS com classifica\u00e7\u00e3o CA para a rede relevante e o risco de raios. Um DPS CA n\u00e3o substitui um dispositivo classificado para o circuito CC fotovoltaico.<\/p>\n<h2>Por que os circuitos fotovoltaicos precisam de uma avalia\u00e7\u00e3o espec\u00edfica do local<\/h2>\n<p>Os m\u00f3dulos fotovoltaicos s\u00e3o frequentemente instalados em telhados expostos ou terrenos abertos, enquanto longos percursos de condutores podem transportar sobretens\u00f5es transit\u00f3rias para inversores e equipamentos de monitoramento. Um evento de raio pr\u00f3ximo pode induzir um surto sem uma descarga direta no arranjo. A probabilidade e a gravidade dependem do local; nenhuma dist\u00e2ncia fixa de uma descarga, tens\u00e3o de dano, custo de reparo ou perda de vida \u00fatil pode ser garantida para todas as instala\u00e7\u00f5es.<\/p>\n<p>Um DPS limita a tens\u00e3o transit\u00f3ria e desvia a corrente de surto sob as suas condi\u00e7\u00f5es de teste declaradas. N\u00e3o pode prevenir todos os danos causados por raios e n\u00e3o substitui um sistema de prote\u00e7\u00e3o contra raios, liga\u00e7\u00e3o equipotencial, prote\u00e7\u00e3o contra sobrecorrente ou isolamento seguro.<\/p>\n<h2>Como avaliar a prote\u00e7\u00e3o a n\u00edvel de string e de arranjo.<\/h2>\n<ol>\n<li><strong>Confirmar as regras aplic\u00e1veis e o projeto de prote\u00e7\u00e3o contra raios.<\/strong> Registrar a jurisdi\u00e7\u00e3o, a norma adotada, o sistema externo de prote\u00e7\u00e3o contra raios e se a dist\u00e2ncia de separa\u00e7\u00e3o \u00e9 mantida.<\/li>\n<li><strong>Mapear os condutores.<\/strong> Medir o percurso pr\u00e1tico do cabo entre o arranjo ou combinador e o inversor, e identificar locais onde uma sobretens\u00e3o pode entrar ou onde equipamentos sens\u00edveis necessitam de prote\u00e7\u00e3o.<\/li>\n<li><strong>Escolher os pontos de instala\u00e7\u00e3o.<\/strong> Comparar um DPS no lado do inversor com um DPS adicional no lado do arranjo utilizando a orienta\u00e7\u00e3o do projeto. Um combinador pode proteger m\u00faltiplos circuitos quando o seu arranjo e cablagem suportam esse projeto; um DPS separado para cada string n\u00e3o \u00e9 uma regra autom\u00e1tica.<\/li>\n<li><strong>Coordenar os dispositivos.<\/strong> Confirmar o tipo de DPS, tens\u00e3o nominal, capacidade de descarga, n\u00edvel de prote\u00e7\u00e3o, prote\u00e7\u00e3o de backup e fia\u00e7\u00e3o aprovada pelo fabricante para cada ponto.<\/li>\n<\/ol>\n<p>IEC <a href=\"https:\/\/webstore.iec.ch\/en\/publication\/26931\" rel=\"noopener\">61643-31<\/a> especifica requisitos e testes para DPS destinados ao lado CC de instala\u00e7\u00f5es fotovoltaicas at\u00e9 1.500 V CC. IEC <a href=\"https:\/\/webstore.iec.ch\/en\/publication\/30774\" rel=\"noopener\">61643-32<\/a> aborda sele\u00e7\u00e3o, instala\u00e7\u00e3o e coordena\u00e7\u00e3o para sistemas fotovoltaicos. Leia as edi\u00e7\u00f5es atuais e a ado\u00e7\u00e3o local antes de tratar um guia de projeto como um requisito legal.<\/p>\n<h2>Quatro classifica\u00e7\u00f5es para verificar em um DPS CC fotovoltaico<\/h2>\n<h3>1. Tens\u00e3o m\u00e1xima de opera\u00e7\u00e3o cont\u00ednua<\/h3>\n<p>Calculate the highest possible PV string open-circuit voltage using the module datasheet, series module count and the lowest expected cell temperature. Check that the selected SPD&#8217;s declared DC continuous operating voltage is suitable for that value and the circuit configuration. Also confirm the inverter&#8217;s maximum DC input voltage; an SPD cannot correct an oversized string.<\/p>\n<h3>2. N\u00edvel de prote\u00e7\u00e3o de tens\u00e3o<\/h3>\n<p>Compare o n\u00edvel de prote\u00e7\u00e3o contra surtos declarado (Up), incluindo o efeito dos cabos de instala\u00e7\u00e3o, com a capacidade de suportar impulsos do equipamento protegido. Utilize as folhas de dados do inversor e do DPS. Um valor fixo de Up para cada sistema de 1.000 V ou 1.500 V n\u00e3o \u00e9 confi\u00e1vel.<\/p>\n<h3>3. Tipo de DPS e capacidade de descarga<\/h3>\n<p>Type 1 and Type 2 ratings relate to different declared test duties. The selection depends on the lightning protection concept and exposure, not simply whether the array is on a roof or on the ground. Compare Iimp, In and Imax only with their stated test waveforms and the manufacturer&#8217;s declared configuration.<\/p>\n<h3>4. Prote\u00e7\u00e3o contra curto-circuito e prote\u00e7\u00e3o de backup<\/h3>\n<p>Verify the SPD&#8217;s declared short-circuit capability, disconnector and required backup fuse or breaker for the available PV fault current. Follow the manufacturer wiring diagram, including its polarity and earthing instructions. Do not assume that MOV, GDT or a combined design is always superior: the complete certified device and its application rating matter.<\/p>\n<h2>Instala\u00e7\u00e3o e manuten\u00e7\u00e3o<\/h2>\n<p>Keep SPD connections to the protected circuit and bonding bar short and direct. Schneider Electric&#8217;s guide illustrates a total connection length of less than 50 cm where practical. Check conductor cross-section, enclosure rating, torque, backup protection and bonding against the device instructions and local rules. The protective-earth arrangement is especially important when external lightning protection is present.<\/p>\n<p>During maintenance, inspect the SPD&#8217;s status indication and any remote alarm in accordance with the manufacturer&#8217;s schedule. Replace a device when its indicator or testing shows failure, or when the manufacturer requires replacement after an event. There is no universal five-year or ten-year replacement date.<\/p>\n<figure><img decoding=\"async\" src=\"https:\/\/cnkuangya.com\/wp-content\/uploads\/2025\/12\/4ab379d36bf4a0c32d80a6ae500f21f8531ceb7e22179984ed5359e6cfd66626-687x1024.jpg\" alt=\"Fotografia do produto do dispositivo de prote\u00e7\u00e3o contra surtos FV da Kuangya\" loading=\"lazy\"><figcaption>Utilize a folha de dados e o diagrama de conex\u00e3o exatos do modelo para o DPS PV DC selecionado.<\/figcaption><\/figure>\n<h2>Perguntas frequentes<\/h2>\n<h3>Cada string fotovoltaica requer um DPS?<\/h3>\n<p>N\u00e3o existe uma regra geral que exija um DPS por string. Determine o n\u00famero e a localiza\u00e7\u00e3o dos dispositivos com base na avalia\u00e7\u00e3o de risco do projeto, layout, normas adotadas e documenta\u00e7\u00e3o do equipamento. Verifique se um arranjo no lado da caixa de jun\u00e7\u00e3o (combiner box) e no lado do inversor oferece a prote\u00e7\u00e3o necess\u00e1ria.<\/p>\n<h3>Posso usar um DPS CA no lado CC fotovoltaico?<\/h3>\n<p>Utilize apenas um dispositivo explicitamente classificado pelo fabricante para essa aplica\u00e7\u00e3o e tens\u00e3o CC fotovoltaica. A norma IEC 61643-31 \u00e9 a norma de produto relevante para DPS CC fotovoltaicos em seu escopo. Uma marca\u00e7\u00e3o apenas para CA n\u00e3o \u00e9 prova de adequa\u00e7\u00e3o para CC fotovoltaico. Consulte nossa <a href=\"https:\/\/cnkuangya.com\/pt\/blog\/ac-spd-on-dc-system\/\">Explica\u00e7\u00e3o sobre DPS CA versus CC<\/a>.<\/p>\n<h3>Um valor de kA maior garante uma prote\u00e7\u00e3o melhor?<\/h3>\n<p>N\u00e3o. A forma de onda de teste, o tipo de DPS, Uc, Up, comportamento em curto-circuito, prote\u00e7\u00e3o de backup e condutores de instala\u00e7\u00e3o devem ser adequados ao circuito. Compare as fichas t\u00e9cnicas completas dos dispositivos em vez de apenas uma classifica\u00e7\u00e3o principal.<\/p>\n<h2>Escolha um dispositivo para a instala\u00e7\u00e3o real<\/h2>\n<p>Review Kuangya&#8217;s <a href=\"https:\/\/cnkuangya.com\/pt\/dc-spd\/\">Gama de SPD CC para FV<\/a> e <a href=\"https:\/\/cnkuangya.com\/pt\/pv-combiner-box\/\">Op\u00e7\u00f5es de caixas de jun\u00e7\u00e3o FV<\/a>. Para uma an\u00e1lise de sele\u00e7\u00e3o, <a href=\"https:\/\/cnkuangya.com\/pt\/contact-us\/\">envie \u00e0 equipa<\/a> o c\u00e1lculo da Voc da string, a tens\u00e3o do sistema, o percurso do cabo do painel para o inversor, a disposi\u00e7\u00e3o da prote\u00e7\u00e3o contra descargas atmosf\u00e9ricas e a localiza\u00e7\u00e3o necess\u00e1ria do SPD. A sele\u00e7\u00e3o e a instala\u00e7\u00e3o devem ser verificadas por um projetista ou instalador el\u00e9trico qualificado.<\/p>","protected":false},"excerpt":{"rendered":"<p>Quick answer: Not every PV string needs its own surge protective device (SPD). Whether DC-side surge protection is required, and whether a second SPD belongs near the array or combiner, depends on the local rules, lightning exposure, cable route, inverter arrangement and the installation&#8217;s lightning protection system. A PV-rated SPD near the inverter may be [&hellip;]<\/p>\n","protected":false},"author":4,"featured_media":0,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[44,42],"tags":[],"class_list":["post-2267","post","type-post","status-publish","format-standard","hentry","category-pv-modules-system-integration","category-surge-protection-lightning-safety"],"blocksy_meta":[],"_links":{"self":[{"href":"https:\/\/cnkuangya.com\/pt\/wp-json\/wp\/v2\/posts\/2267","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/cnkuangya.com\/pt\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/cnkuangya.com\/pt\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/cnkuangya.com\/pt\/wp-json\/wp\/v2\/users\/4"}],"replies":[{"embeddable":true,"href":"https:\/\/cnkuangya.com\/pt\/wp-json\/wp\/v2\/comments?post=2267"}],"version-history":[{"count":4,"href":"https:\/\/cnkuangya.com\/pt\/wp-json\/wp\/v2\/posts\/2267\/revisions"}],"predecessor-version":[{"id":4946,"href":"https:\/\/cnkuangya.com\/pt\/wp-json\/wp\/v2\/posts\/2267\/revisions\/4946"}],"wp:attachment":[{"href":"https:\/\/cnkuangya.com\/pt\/wp-json\/wp\/v2\/media?parent=2267"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/cnkuangya.com\/pt\/wp-json\/wp\/v2\/categories?post=2267"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/cnkuangya.com\/pt\/wp-json\/wp\/v2\/tags?post=2267"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}