Type A RCCB for people/fire protection; also supports Type AC.
2P/4P, 16–100A, sensitivities 10/30/100/300 mA;Ue 240V (2P) / 415V (4P)。
IΔm up to 1000A, Inc=IΔc 6kA/10kA, Uimp 6kV;DIN-rail EN 60715;CE/UKCA。
The Kuangya VFL001 is a Type A RCCB designed to detect sinusoidal AC and pulsating DC residual currents, providing reliable protection against electric shock and electrical fires. It also supports Type AC operation for AC-only applications. With 2P/4P configurations, rated current from 16A to 100A, and sensitivities of 10/30/100/300 mA, VFL001 fits residential, commercial and light industrial distribution boards. Popular selections include rccb 16a 30ma, rccb 25a 30ma, rccb 40a 30maそして RCCB 63A 30MA.
When the residual current exceeds the preset threshold (IΔn), the internal toroidal sensor and trip unit of this タイプA RCCB actuate the mechanism to disconnect the circuit within the specified breaking time. Short-time delay (ASi/G/KV) and selective (S) characteristics are available to coordinate with upstream/downstream devices and reduce nuisance tripping.
スタンダード | IEC/EN 61008-1 |
---|---|
モデル番号 | VFL001 |
ポール | 2P、4P |
Rated current In | 16A、25A、32A、40A、63A、80A、100A |
Rated Sensitivity IΔn | 10 mA (2P/4P 16A–40A), 30 mA, 100 mA, 300 mA |
Rated voltage Ue | 2P: 240V~ 4P: 415V~ |
Insulation voltage Ui | 500 V |
定格周波数 | 50/60 Hz |
Rated residual making & breaking capacity IΔm | 500 A (In=16A, 25A, 32A, 40A); 630 A (In=63A); 800 A (In=80A); 1000 A (In=100A) |
Short-circuit current Inc = IΔc | 6000 A, 10000 A |
Type (waveform sensed) | AC, A |
Tripping time | Instantaneous / Short time delay / Selective |
Break time under IΔn | ≤100 ms (normal type) |
Short time delay | 10–300 ms (ASi, G, KV type) |
選択タイプ | 150–500 ms (S type) |
Rated impulse withstand voltage (1.2/50) Uimp | 6 kV |
Dielectric test voltage at ind. freq. (1 min) | 2.5 kV |
Pollution degree | 2 |
Electrical life | ≥2000 |
Mechanical life | ≥2000 |
Fault current indicator | Yes |
端子保護度 | IP20 |
Ambient temperature (daily avg ≤35 °C) | -25 °C ~ +55 °C |
保存温度 | -40 °C ~ +70 °C |
Terminal connection type | ケーブル / ピン型バスバー |
Terminal size top/bottom for cable | 25–35 mm² (typ.); 18–3 / 18–2 AWG notes per size class |
Terminal size top/bottom for busbar | Pin-type; 10/16 mm² (typ.); 18–8 / 18–5 AWG notes |
締め付けトルク | 2.5 N·m (≈ 22 in-lbs) |
取り付け | On DIN rail EN 60715 (35 mm) by fast clip device |
Connection | From top and bottom |
適合規格 IEC/EN 61008-1; CE & UKCA approvals. Terminal safety to IP20; pollution degree 2.
Type AC detects sinusoidal AC only; タイプA also detects pulsating DC components, which are common with modern power electronics.
Use short-time delay (10–300 ms) to ride through transient leakage or inrush; use S type (150–500 ms) to coordinate with downstream RCCBs and avoid nuisance tripping.
Select an SCPD so that the conditional residual short-circuit current rating Inc = IΔc of 6 kA or 10 kA is respected under fault conditions.