RCCB VFL002B - Interruttore automatico per correnti di guasto (tipo B/B+)

  • rccb tipo b for AC, pulsating DC, and smooth DC residual currents; B+ variant adds extended high-frequency response.

  • 2P/4P, 16–100 A; IΔn 30/100/300/500 mA; Ue 230/240 V (2P), 400/415 V (4P).

  • Inc 10 kA; Im 1500 A; Uimp 4 kV; surge withstand 3 kA (8/20 μs) / 5 kA for S type; IEC/EN 61008-1, OVE E8601; UKCA/CE.

Richiedi un preventivo

Categoria:

Panoramica

The Kuangya VFL002B is an rccb tipo b designed for installations where smooth DC and mixed-frequency leakage can occur. Typical applications include EV charging points, PV inverters, UPS systems, drives with frequency converters, medical imaging (X-ray/CT), test benches, cranes, elevators, and variable-speed machinery. The B version covers AC + pulsating DC + smooth DC; the B+ variant extends the frequency response up to 20 kHz for modern power-electronics environments.

Detection & operation

  • Tipo B — sensitive to sinusoidal AC, pulsating DC, and smooth DC residual currents.
  • Type B+ — all B functions plus extended high-frequency behavior up to 20 kHz.
  • Electronics — B/B+ functions are voltage-dependent with electronic control; A-class behavior is voltage-independent.

Caratteristiche principali

  • Pali: 2P / 4P; In: 16, 25, 32, 40, 63, 80, 100 A.
  • IΔn (instantaneous): 30 / 100 / 300 / 500 mA.
  • Ue (Un): 2P: 230/240 V AC; 4P: 400/415 V AC; fn: 50/60 Hz.
  • Electronic supply: 50–264 V AC; test-circuit voltage range: 2P 184–264 V AC; 4P 184–440 V AC.
  • Ui: 500 V; Uimp: 4 kV (1.2/50 μs).
  • Inc (conditional short-circuit): 10 kA; Im (making/breaking): 1500 A.
  • Surge withstand: 3 kA (8/20 μs); Selective S type withstands 5 kA.
  • High-frequency behavior: up to 1 kHz (B) / up to 20 kHz (B+).
  • Endurance (ops): ≥ 2000 electrical / ≥ 4000 mechanical.
  • Terminals: open-mounted / lift type; cable and pin-type busbar; terminal protection IP20.
  • Ambiente: −25 °C…+55 °C (daily avg ≤ 35 °C); storage −40 °C…+70 °C.
  • Mounting: 35 mm DIN rail (EN 60715), fast clip; top or bottom supply; any mounting position.
  • Standards/Approvals: IEC/EN 61008-1, OVE E8601; UKCA, CE.

Technical Data

StandardIEC/EN 61008-1; OVE E8601
ModelloVFL002B (Type B); VFL002B+ (Type B+)
Pali2P, 4P
Rated voltage Ue (Un)2P: 230/240 V AC; 4P: 400/415 V AC
Rated frequency fn50/60 Hz
Electronic operation voltage50–264 V AC
Voltage range (test circuit)2P: 184–264 V AC; 4P: 184–440 V AC
Rated current In16, 25, 32, 40, 63, 80, 100 A
Rated sensitivity IΔn30 / 100 / 300 / 500 mA (instantaneous)
Insulation voltage Ui500 V
Impulse withstand Uimp4 kV
Conditional short-circuit Inc10 kA
Capacità di produzione/rottura Im1500 A
Surge withstand3 kA (8/20 μs); 5 kA (Selective S type)
High-frequency behaviorB: up to 1 kHz; B+: up to 20 kHz
Electrical isolation> 4 mm contact gap
Back-up fuse (ref.)gG/gL 100 A
Resistenza≥ 2000 electrical; ≥ 4000 mechanical operations
Terminal capacity1–25 mm² (cable); busbar 0.8–2 mm
Terminal torque2–2.5 N·m
Protection degreeIP20 (terminals)
Temperatura di esercizio−25 °C…+55 °C (avg ≤ 35 °C)
Storage temperature−40 °C…+70 °C
MontaggioDIN rail EN 60715 (35 mm); any position
ConnectionTop or bottom
ApprovalsUKCA, CE

Applicazioni

  • EV charging points and wallboxes requiring rccb tipo b sensitivity to smooth DC leakage.
  • PV/UPS/inverter-driven systems, test benches, and medical imaging equipment.
  • Industrial machinery with variable-speed drives and rectifiers.

Certificazioni

Conforms to IEC/EN 61008-1 and OVE E8601; approved UKCA and CE.

FAQ

When to choose B vs. B+?

Select B+ when the installation contains significant high-frequency components (up to 20 kHz); otherwise B is sufficient for AC, pulsating DC, and smooth DC leakage.

How to coordinate the conditional short-circuit rating?

Use an upstream SCPD so the installation respects Inc = 10 kA under fault conditions.