Type A RCCB for people/fire protection; also supports Type AC.
2P/4P, 16–100A, sensitivities 10/30/100/300 mA;Ue 240V (2P) / 415V (4P)。
IΔm up to 1000A, Inc=IΔc 6kA/10kA, Uimp 6kV;DIN-rail EN 60715;CE/UKCA。
The Kuangya VFL001 is a Type A RCCB designed to detect sinusoidal AC and pulsating DC residual currents, providing reliable protection against electric shock and electrical fires. It also supports Type AC operation for AC-only applications. With 2P/4P configurations, rated current from 16A to 100A, and sensitivities of 10/30/100/300 mA, VFL001 fits residential, commercial and light industrial distribution boards. Popular selections include rccb 16a 30ma, rccb 25a 30ma, rccb 40a 30ma, e rccb 63a 30ma.
When the residual current exceeds the preset threshold (IΔn), the internal toroidal sensor and trip unit of this tipo a rccb actuate the mechanism to disconnect the circuit within the specified breaking time. Short-time delay (ASi/G/KV) and selective (S) characteristics are available to coordinate with upstream/downstream devices and reduce nuisance tripping.
| Standard | IEC/EN 61008-1 |
|---|---|
| Model No. | VFL001 |
| Pali | 2P, 4P |
| Rated current In | 16A, 25A, 32A, 40A, 63A, 80A, 100A |
| Rated Sensitivity IΔn | 10 mA (2P/4P 16A–40A), 30 mA, 100 mA, 300 mA |
| Rated voltage Ue | 2P: 240V~ 4P: 415V~ |
| Insulation voltage Ui | 500 V |
| Rated frequency | 50/60 Hz |
| Rated residual making & breaking capacity IΔm | 500 A (In=16A, 25A, 32A, 40A); 630 A (In=63A); 800 A (In=80A); 1000 A (In=100A) |
| Short-circuit current Inc = IΔc | 6000 A, 10000 A |
| Type (waveform sensed) | AC, A |
| Tripping time | Instantaneous / Short time delay / Selective |
| Break time under IΔn | ≤100 ms (normal type) |
| Short time delay | 10–300 ms (ASi, G, KV type) |
| Tipo selettivo | 150–500 ms (S type) |
| Rated impulse withstand voltage (1.2/50) Uimp | 6 kV |
| Dielectric test voltage at ind. freq. (1 min) | 2.5 kV |
| Pollution degree | 2 |
| Electrical life | ≥2000 |
| Mechanical life | ≥2000 |
| Fault current indicator | Yes |
| Terminal protection degree | IP20 |
| Ambient temperature (daily avg ≤35 °C) | −25 °C to +55 °C |
| Storage temperature | −40 °C to +70 °C |
| Terminal connection type | Cavo / sbarra di tipo Pin |
| Terminal size top/bottom for cable | 25–35 mm² (typ.); 18–3 / 18–2 AWG notes per size class |
| Terminal size top/bottom for busbar | Pin-type; 10/16 mm² (typ.); 18–8 / 18–5 AWG notes |
| Tightening torque | 2.5 N·m (≈ 22 in-lbs) |
| Montaggio | On DIN rail EN 60715 (35 mm) by fast clip device |
| Connection | From top and bottom |
Conforme a IEC/EN 61008-1; CE & UKCA approvals. Terminal safety to IP20; pollution degree 2.
Type AC detects sinusoidal AC only; Tipo A also detects pulsating DC components, which are common with modern power electronics.
Use short-time delay (10–300 ms) to ride through transient leakage or inrush; use S type (150–500 ms) to coordinate with downstream RCCBs and avoid nuisance tripping.
Select an SCPD so that the conditional residual short-circuit current rating Inc = IΔc of 6 kA or 10 kA is respected under fault conditions.