RCCB VFL008 - Interruttore automatico per correnti di guasto

  • Circuit breaker RCCB type protection for residential, commercial, and light-industrial systems

  • 2P/4P options, rated current 16–100 A, sensitivities 30/100/300 mA, Ue 240 V (2P) / 415 V (4P)

  • IEC/EN 61008-1 compliance, high endurance, DIN-rail mounting, CE & UKCA

Richiedi un preventivo

Categoria:

Panoramica

The Kuangya VFL008 interruttore automatico tipo rccb disconnects the circuit when residual current exceeds the
preset threshold, preventing electric shock and fire hazards due to insulation faults. Available in both 2-pole and
4-pole versions, this circuit breaker rccb type suits single-phase and three-phase distribution boards in homes,
offices, and light-industrial facilities.

Caratteristiche principali

  • Pali: 2P / 4P
  • Corrente nominale (In): 16, 25, 32, 40, 63, 80, 100 A
  • Rated sensitivity (IΔn): 30 / 100 / 300 mA
  • Tensione nominale (Ue): 240 V~ (2P) / 415 V~ (4P)
  • Insulation voltage (Ui): 500 V   |   Frequency: 50/60 Hz
  • Residual making & breaking (IΔm): 500 A (In 16–40 A); 630 A (63 A); 800 A (80 A); 1000 A (100 A)
  • Conditional short-circuit current (Inc = IΔc): 6 kA / 10 kA (with upstream SCPD coordination)
  • Impulse withstand (Uimp): 6 kV; Dielectric test: 2.5 kV (1 min)
  • Resistenza: ≥20,000 mechanical / ≥2000 electrical operations
  • Terminal protection: IP20; fault current indicator
  • Ambient: −25 °C to +55 °C (daily avg ≤ 35 °C); Storage: −40 °C to +70 °C
  • Cablaggio: cable 25–35 mm² or pin-type busbar; top/bottom connection
  • Mounting: DIN rail EN 60715 (35 mm), fast clip
  • Standards/Approvals: IEC/EN 61008-1; CE / UKCA

Technical Data

ModelloVFL008
Pali2P, 4P
Corrente nominale (In)16A, 25A, 32A, 40A, 63A, 80A, 100A
Rated sensitivity (IΔn)30 mA, 100 mA, 300 mA
Tensione nominale (Ue)2P: 240 V~; 4P: 415 V~
Insulation voltage (Ui)500 V
Rated frequency50/60 Hz
Residual making & breaking (IΔm)500 A (In = 16–40 A); 630 A (In = 63 A); 800 A (In = 80 A); 1000 A (In = 100 A)
Conditional short-circuit (Inc = IΔc)6000 A, 10000 A
Tripping time classesInstantaneous / Short time delay (10–300 ms) / Selective S (150–500 ms)
Break time under IΔn (Normal)≤ 100 ms
Impulse withstand (Uimp)6 kV
Dielectric test voltage2.5 kV (1 min)
Pollution degree2
Electrical life≥ 2000 operations
Mechanical life≥ 2000 operations
Terminal protection degreeIP20
Ambient temperature (avg ≤ 35 °C)−25 °C to +55 °C
Storage temperature−40 °C to +70 °C
Terminal connectionCavo / sbarra di tipo Pin
Terminal size (cable)25–35 mm²; 18–3 / 18–2 AWG
Terminal size (busbar)10/16 mm²; 18–8 / 18–5 AWG
Tightening torque2.5 N·m (≈ 22 in-lbs)
MontaggioDIN rail EN 60715 (35 mm)
ConnectionTop and bottom
ApprovalsCE, UKCA

Applicazioni

  • Residential distribution boards (30 mA additional protection)
  • Commercial buildings requiring coordinated leakage and short-circuit protection
  • Light-industrial panels; consider short-time-delay or S-selective per coordination study