How to Select the Right Surge Protective Device (SPD) for Industrial and Renewable Applications

Updated: · Reading time: ~18–22 min

Selecting the correct Surge Protective Device (SPD) is among the highest-ROI decisions in LV distribution, PV/ESS, EV charging, and industrial automation. This guide compiles standards-driven criteria (IEC/UL/NEC), placement rules, and BOM tips for both AC and DC systems. See the reference tables and sources at the end.

1) Why SPD investment pays for itself

Unplanned downtime often costs USD 1–5M/hour; severe cases approach USD 300k/min. Surges from lightning/switching are predictable & engineerable; coordinated SPDs clamp high-energy impulses and protect PLCs/VFDs/IT.

U.S. detection networks record tens to hundreds of millions of lightning events annually; Florida often leads in density, Texas in totals. Use geography-aware specs (see §8) to justify higher Iimp/In ratings.

Lightning context (CC BY-SA)

2) Standards landscape (IEC / UL / NEC)

IEC 61643 defines performance & waveforms; UL 1449 lists safety/compliance for North America; NEC 2023 Article 242 mandates use in several contexts.

IEC 61643

Type 1: 10/350 μs (Iimp) · Type 2: 8/20 μs (In/Imax) · Type 3: Combination (Uoc). PV/DC: IEC 61643-31 ≤1500 VDC.

IEC Webstore

UL 1449

UL listing for permanently connected SPDs; 4th Ed. (2016) refined markings.

Intertek · Schneider PDF

NEC 2023

Article 242 governs overvoltage protection. Follow listing & placement rules.

NFPA 70

3) Decoding SPD “Type” vs. test waveforms

Choose the type by exposure & board hierarchy; coordinate residual voltage (Up) across stages.

Type 1 (Class I)

Test: 10/350 μs (Iimp). Install at service entrance when LPS/overhead.

Type 2 (Class II)

Test: 8/20 μs (In/Imax). Sub-boards backbone protection.

Type 3 (Class III)

Test: Combination (Uoc). Close to sensitive loads (PLCs, VFDs, IT).

SPD photo (CC BY-SA)

Hybrid Type 1+2 = high energy + low residual. Selectors: AC · DC

4) AC vs. DC (PV/ESS) — same physics, different constraints

AC side (IEC 61643-11 / UL 1449): choose Type 1/2/3 by exposure and board hierarchy, then size Uc, In/Imax, Up. DC side (IEC 61643-31): PV arrays up to 1500 VDC with different temperature, polarity and reverse-current behaviors vs. AC devices.

In modern BOS, PV combiner boxes often integrate Type 2 DC SPD, gPV fuses and DC disconnects—reducing enclosure count and simplifying field work.

Solar PV field
Image: Solar PV field (Wikimedia Commons, CC BY-SA). Consider SPDs at combiner and inverter DC inputs per IEC 61643-31.

5) Layered protection “recipe”

  1. Service entrance / MSB: Type 1 (or 1+2) with sufficient Iimp; shortest, straightest earth path.
  2. Sub-distribution boards: Type 2 sized for branch fault level and cable lengths; coordinate Up with MSB stage.
  3. Sensitive endpoints: Type 3 near device inlets (PLCs, VFDs, servers).

This cascade mirrors IEC 60364-5-53 selection/erection principles and common manufacturer guidance.

6) Nine-point sizing checklist

  • Codes/Listing: UL 1449 (U.S.), NEC 242.
  • Type: 1 / 1+2 / 2 / 3 by exposure & board level.
  • Uc (MCOV): > worst-case continuous voltage.
  • Iimp / In / Imax: match lightning density & entry points.
  • Up: stage-by-stage coordination.
  • Pole & Earthing: TN/TT/IT and N-PE needs.
  • SCCR / Backup OCPD: match fault current & vendor tables.
  • Environment: Altitude, IP/NEMA, lead length.
  • Maintenance: Replaceable modules, status window, remote alarm.
Panel wiring placeholder
Replace with your project photo (combiner/MSB wiring).

7) Where to install SPDs in PV, ESS, and EV projects

  • PV arrays: At combiner boxes and inverter DC inputs; long runs or exposed terrain may require both.
  • ESS: DC bus near battery/DC-DC interface, plus AC side at PCS.
  • EV charging: Type 1 or 1+2 at service (if LPS/overhead), Type 2 at distribution, Type 3 near terminals.

See also: PV Combiner Boxes · High-Voltage gPV Fuses

8) Data snapshot: lightning exposure & why it changes your BOM

Lightning exposure is not uniform. U.S. lightning reports routinely cite 90–240+ million events annually (in-cloud + CG) depending on methodology. Texas often leads total counts while Florida frequently leads density. For wind farms and tall infrastructure, stroke counts per site can exceed thousands.

For budgeting, use county-level maps from NOAA/NCEI or annual reports from Vaisala/AEM to justify Iimp/In choices and site placement.

9) Quick-reference tables

Copy these rows into your spec sheets as a starting point.

SPD TypePrimary TestKey RatingsTypical LocationNotes
Type 110/350 μs (Iimp)Uc, Iimp, UpService entrance / MSBPartial direct lightning current
Type 28/20 μs (In/Imax)Uc, In/Imax, UpSub-distribution boardsBackbone protection
Type 3Combination (Uoc)Uc, Uoc, UpNear sensitive loadsFinal clamp, coordinate with Type 2
Optional image: test waveforms diagram / product lineup

Table B — Minimum data you must specify on every SPD

ParameterWhy it mattersTypical pitfalls
Uc (MCOV)Must exceed worst-case continuous system voltageChoosing too close to nominal → thermal stress & early end-of-life
Iimp / In / ImaxMatch expected surge environmentUnder-rating at service entrance; misusing Type 2 where Type 1 is needed
UpDetermines residual stress on insulation/electronicsNot coordinating Up across stages → equal-level protection
SCCR / Backup OCPDSafety & selectivityMismatch with available fault current; ignoring vendor backup device tables
Pole count & EarthingTN/TT/IT change module set and N-PE needsMissing N-PE on TT; miswiring PEN in TN-C
Environment & MountingTemperature, altitude, IP/NEMA; conductor routingLong lead lengths; sharp bends increase inductance (raise terminal Up)

10) Earthing, wiring, and lead-length rules

  • Keep SPD-to-earth and SPD-to-bus conductors short, straight, adjacent.
  • Avoid loops or pretty cable dressing that increases inductance at surge time.
  • Use vendor torque specs; loose terminations run hot under repetitive surges.
  • On TT systems, ensure proper N-PE modules and bonding so currents return via the intended path.

Global erection rules reference: IEC 60364-5-53.

11) NEC-triggered placements (U.S.)

The 2023 NEC (NFPA 70) strengthens SPD use in several contexts (e.g., whole-home protection at dwellings, fire pump controllers). Article 242 covers overvoltage protection for ≤1000 V installations; always match UL 1449 listing and installation location.

Reference: NFPA 70 (NEC) · UL 1449 explainer

12) Worked examples — choosing ratings quickly

A. Industrial plant, overhead service, no LPS, 400/230 VAC TN-S

  • MSB: Type 1 (or 1+2) with Iimp ≈ 12.5–25 kA/pole typical; Uc ≥ 275 VAC (L-N) for 230 V systems; Up ≤ 1.5 kV.
  • Sub-DBs: Type 2 at In 20–40 kA, Imax 40–80 kA per board risk.
  • Endpoints: Type 3 at VFDs/PLCs/IT loads.

B. 1000 VDC PV array (long strings, ground mount)

  • Combiner box: Type 2 DC SPD to IEC 61643-31; Uc ≥ Vstring(max at Tmin); coordinate Up with inverter.
  • Inverter DC input: Add a second DC stage if cable distances are large or terrain is highly exposed.

C. EV charging plaza (commercial)

  • Service: Type 1 or 1+2 where LPS/overhead exists.
  • Distribution: Type 2 feeding charger groups; Type 3 near charger inputs (if supported).

13) FAQ (engineering-level answers)

Do I always need Type 1 at the service entrance?

If you have external LPS or overhead service, Type 1 (or 1+2) is the standard approach to handle partial direct lightning current. Underground-fed buildings sometimes justify robust Type 2, but assess risk (lightning density, entry routes) and local code.

How do UL and IEC naming differ?

UL 1449 is a listing/safety standard; IEC 61643 defines performance tests and types. Many data sheets display both. The 4th Edition of UL 1449 (2016) standardized newer markings and requirements.

What numbers should I optimize for?

In order: Uc (right, not low) → Iimp/In/Imax (enough) → Up (as low as coordination allows) → SCCR/backupmaintenance features.

What if I can only afford one stage today?

Put budget at the service entrance (Type 1 or 1+2), then add Type 2/3 later. This blocks catastrophic energy from penetrating deep into the facility.

How does geography change my spec?

High-density corridors (e.g., Gulf Coast, Central Florida) justify higher Iimp/In and tighter Up targets. Use NCEI/Vaisala/AEM maps to quantify baseline flash densities for AHJ or insurance discussions.

Credits & Sources