{"id":1561,"date":"2025-09-15T07:59:53","date_gmt":"2025-09-15T07:59:53","guid":{"rendered":"https:\/\/cnkuangya.com\/?post_type=product&#038;p=1561"},"modified":"2025-09-27T14:29:09","modified_gmt":"2025-09-27T14:29:09","slug":"vrl22-2-pole-rcbo","status":"publish","type":"product","link":"https:\/\/cnkuangya.com\/ar\/product\/vrl22-2-pole-rcbo\/","title":{"rendered":"VRL22 RCBO \u2014 2P \/ 4P, 6\u201363A (AC\/A\/ASi, Type B\/B+, EV Type A\/F)"},"content":{"rendered":"<p><!-- Make sure the Focus KW appears at the very beginning --><\/p>\n<p><strong>2 pole rcbo<\/strong> VRL22 is a versatile RCBO platform available in 2P and 4P configurations, rated 6\u201363 A for 240\/415 V, 50\/60 Hz systems. The family spans Type AC\/A\/ASi, advanced <em>Type B \/ B+<\/em> variants for smooth DC and high-frequency residuals, and EV-focused models (VRL22A EV \/ VRL22F EV) with 6 mA DC detection per IEC 62955 (RDC-PD).<\/p>\n<section id=\"overview\">\n<h2>\u0644\u0645\u062d\u0629 \u0639\u0627\u0645\u0629<\/h2>\n<p>VRL22 integrates overload, short-circuit and residual-current protection into a single device for<br \/>\nsingle- and three-phase boards. The platform supports selective coordination through B\/C curves and<br \/>\nmultiple sensitivities, while its variant family addresses special waveforms (VFDs, PV inverters, EVSE).<br \/>\n2P targets single-phase lines at 240 V; 4P targets three-phase at 415 V, with shared current range up to 63 A.<\/p>\n<\/section>\n<section id=\"features\">\n<h2>\u0627\u0644\u0645\u064a\u0632\u0627\u062a \u0627\u0644\u0631\u0626\u064a\u0633\u064a\u0629<\/h2>\n<ul>\n<li>Poles: <strong>2P<\/strong> (single-phase) and <strong>4P<\/strong> (three-phase)<\/li>\n<li>Rated current (In): <strong>6\u201363 A<\/strong><\/li>\n<li>Rated voltage (Ue): <strong>AC 240 V<\/strong> (2P) \/ <strong>AC 415 V<\/strong> (4P), <strong>50\/60 \u0647\u0631\u062a\u0632<\/strong><\/li>\n<li>Residual current options:\n<ul>\n<li><strong>Type AC \/ Type A \/ ASi<\/strong> (platform\/base)<\/li>\n<li><strong>Type B \/ B+<\/strong> variant for smooth DC &amp; high frequency (B+ extended HF coverage)<\/li>\n<li><strong>EV variants<\/strong>: <strong>VRL22A EV<\/strong> (Type A EV) &amp; <strong>VRL22F EV<\/strong> (Type F EV) with 6 mA DC detection<\/li>\n<\/ul>\n<\/li>\n<li>Sensitivity (I\u0394n): platform typical options 30 \/ 100 \/ 300 \/ 500 mA; EV includes 30 mA + RDC-PD 6 mA DC per IEC 62955<\/li>\n<li>Tripping curves: <strong>B (3\u20135\u00d7In)<\/strong>, <strong>C (5\u201310\u00d7In)<\/strong><\/li>\n<li>Standards: <strong>IEC\/EN 61009-1<\/strong> (platform), <strong>IEC\/EN 62423<\/strong> (Type B), <strong>IEC 62955<\/strong> (EV), <strong>VDE 0664-400<\/strong> (B\/B+)<\/li>\n<li>Certifications: <strong>SEMKO, UKCA, CE, SAA<\/strong><\/li>\n<li>DIN-rail mounting; front test button (T); front wiring<\/li>\n<\/ul>\n<\/section>\n<section id=\"technical-data\">\n<h2>2 Pole RCBO Technical Data \u2014 VRL22 Platform<\/h2>\n<table>\n<thead>\n<tr>\n<th>\u0627\u0644\u0645\u0639\u0644\u0645\u0629<\/th>\n<th>VRL22 (Base: AC\/A\/ASi)<\/th>\n<th>VRL22A EV \/ VRL22F EV<\/th>\n<th>VRL22B \/ VRL22 B+<\/th>\n<\/tr>\n<\/thead>\n<tbody>\n<tr>\n<td>\u0627\u0644\u0623\u0639\u0645\u062f\u0629<\/td>\n<td>2 \u0641-2\/\u0641-4<\/td>\n<td>2 \u0641-2\/\u0641-4<\/td>\n<td>2 \u0641-2\/\u0641-4<\/td>\n<\/tr>\n<tr>\n<td>Rated current (In)<\/td>\n<td>6\u201363 A<\/td>\n<td>6\u201363 A<\/td>\n<td>6\u201363 A<\/td>\n<\/tr>\n<tr>\n<td>Rated voltage (Ue)<\/td>\n<td>2P: AC 240 V; 4P: AC 415 V<\/td>\n<td>2P: AC 240 V; 4P: AC 415 V<\/td>\n<td>2P: AC 240 V; 4P: AC 415 V<\/td>\n<\/tr>\n<tr>\n<td>\u0627\u0644\u062a\u0631\u062f\u062f<\/td>\n<td colspan=\"3\">50\/60 \u0647\u0631\u062a\u0632<\/td>\n<\/tr>\n<tr>\n<td>\u0646\u0648\u0639 \u0627\u0644\u062a\u064a\u0627\u0631 \u0627\u0644\u0645\u062a\u0628\u0642\u064a<\/td>\n<td>Type AC \/ Type A \/ ASi<\/td>\n<td>Type A EV \/ Type F EV (with 6 mA DC RDC-PD)<\/td>\n<td>Type B \/ B+ (smooth DC &amp; high frequency)<\/td>\n<\/tr>\n<tr>\n<td>Rated residual current (I\u0394n)<\/td>\n<td>30 \/ 100 \/ 300 \/ 500 mA (typical)<\/td>\n<td>30 mA AC + 6 mA DC detection (RDC-PD)<\/td>\n<td>30 \/ 100 \/ 300 \/ 500 mA (typical)<\/td>\n<\/tr>\n<tr>\n<td>HF\/DC response<\/td>\n<td>AC &amp; pulsating DC (ASi improves immunity)<\/td>\n<td>AC + pulsating DC + smooth DC \u2265 6 mA (EV)<\/td>\n<td>B: up to ~1 kHz; B+: extended up to ~20 kHz<\/td>\n<\/tr>\n<tr>\n<td>MCB tripping curve<\/td>\n<td colspan=\"3\">B (3\u20135\u00d7In) \/ C (5\u201310\u00d7In)<\/td>\n<\/tr>\n<tr>\n<td>\u0627\u0644\u0627\u0645\u062a\u062b\u0627\u0644<\/td>\n<td>IEC\/EN 61009-1<\/td>\n<td>IEC\/EN 61009-1; IEC 62955 (RDC-PD)<\/td>\n<td>IEC\/EN 61009-1; IEC\/EN 62423; VDE 0664-400<\/td>\n<\/tr>\n<tr>\n<td>\u0627\u0644\u0634\u0647\u0627\u062f\u0627\u062a<\/td>\n<td>SEMKO, UKCA, CE, SAA<\/td>\n<td>UKCA, CE, SAA (region-specific)<\/td>\n<td>CE\/UKCA; region-specific<\/td>\n<\/tr>\n<tr>\n<td>\u0627\u0644\u062a\u0631\u0643\u064a\u0628<\/td>\n<td colspan=\"3\">DIN-rail; front wiring; front test button (T)<\/td>\n<\/tr>\n<tr>\n<td>Recommended use<\/td>\n<td>General distribution (residential\/commercial)<\/td>\n<td>EVSE &amp; EV charging circuits (AC + 6 mA DC)<\/td>\n<td>VFD-driven loads, PV inverters, medical\/lab gear<\/td>\n<\/tr>\n<\/tbody>\n<\/table>\n<p style=\"font-size: 0.95em; opacity: .85;\">Notes: exact option sets (I\u0394n, curves, approvals) may vary by region and sub-model. Check the model code &amp; datasheet for your market.<\/p>\n<\/section>\n<section id=\"applications\">\n<h2>\u0627\u0644\u062a\u0637\u0628\u064a\u0642\u0627\u062a<\/h2>\n<ul>\n<li>Residential &amp; commercial distribution boards (2P at 240 V)<\/li>\n<li>Three-phase panels and feeders (4P at 415 V)<\/li>\n<li>EV charging: wallboxes, AC EVSE (VRL22A EV \/ VRL22F EV)<\/li>\n<li>VFD\/drive systems, PV inverters, UPS and SMPS (Type B \/ B+)<\/li>\n<\/ul>\n<\/section>\n<section id=\"media\">\n<h2>Downloads &amp; Images<\/h2>\n<p><img decoding=\"async\" src=\"REPLACE-WITH-YOUR-IMAGE.jpg\" alt=\"2 pole rcbo VRL22 2P\/4P, 6\u201363A, Type AC\/A\/ASi, Type B\/B+, EV (VRL22A EV \/ VRL22F EV) with 6 mA DC detection\" \/><\/p>\n<\/section>\n<section id=\"certs\">\n<h2>\u0627\u0644\u0645\u0639\u0627\u064a\u064a\u0631 \u0648\u0627\u0644\u0627\u0645\u062a\u062b\u0627\u0644<\/h2>\n<p>Platform: <strong>IEC\/EN 61009-1<\/strong>. Type B: <strong>IEC\/EN 62423<\/strong>, <strong>VDE 0664-400<\/strong>.<br \/>\nEV variants: <strong>IEC 62955<\/strong> (RDC-PD 6 mA DC). Certifications include<br \/>\n<strong>SEMKO, UKCA, CE, SAA<\/strong> (availability per region).<\/p>\n<\/section>\n<section id=\"faq\">\n<h2>\u0627\u0644\u0623\u0633\u0626\u0644\u0629 \u0627\u0644\u0634\u0627\u0626\u0639\u0629<\/h2>\n<details>\n<summary>What is the difference between VRL22 base, VRL22B\/B+ and EV models?<\/summary>\n<div>\n<p>Base covers Type AC\/A\/ASi for common loads. <strong>VRL22B\/B+<\/strong> detects smooth DC and higher-frequency leakage for VFD\/PV\/medical loads. <strong>VRL22A EV \/ VRL22F EV<\/strong> add 6 mA DC detection per IEC 62955 for AC EV charging.<\/p>\n<\/div>\n<\/details>\n<details>\n<summary>When should I choose 4P instead of 2P?<\/summary>\n<div>\n<p>\u0627\u0644\u0627\u0633\u062a\u062e\u062f\u0627\u0645 <strong>4P<\/strong> on three-phase systems (415 V) or when neutral switching\/isolation is required. <strong>2P<\/strong> fits single-phase (240 V) circuits.<\/p>\n<\/div>\n<\/details>\n<details>\n<summary>Type B vs Type A \u2014 which one do I need?<\/summary>\n<div>\n<p><strong>\u0627\u0644\u0646\u0648\u0639 \u0623<\/strong> detects AC + pulsating DC and suits most electronic loads. <strong>\u0627\u0644\u0646\u0648\u0639 \u0628<\/strong> (and B+) is required for smooth DC and high-frequency leakage typical of VFDs, PV inverters or certain medical equipment.<\/p>\n<\/div>\n<\/details>\n<details>\n<summary>How do EV variants meet DC leakage requirements?<\/summary>\n<div>\n<p>EV models integrate RDC-PD functionality (IEC 62955), providing <strong>6 mA DC<\/strong> detection in addition to 30 mA AC residual protection to comply with EVSE standards.<\/p>\n<\/div>\n<\/details>\n<\/section>","protected":false},"excerpt":{"rendered":"<ul data-start=\"514\" data-end=\"913\">\n<li data-start=\"514\" data-end=\"612\">\n<p data-start=\"516\" data-end=\"612\"><strong data-start=\"516\" data-end=\"531\">2 pole rcbo<\/strong> \/ 4-pole platform covering <strong data-start=\"559\" data-end=\"568\">6\u201363A<\/strong>, <strong data-start=\"570\" data-end=\"577\">\u0628\/\u062c<\/strong> curves, <strong data-start=\"586\" data-end=\"599\">240\/415 V<\/strong>, 50\/60 Hz.<\/p>\n<\/li>\n<li data-start=\"613\" data-end=\"762\">\n<p data-start=\"615\" data-end=\"762\">Residual options: <strong data-start=\"633\" data-end=\"659\">Type AC \/ Type A \/ ASi<\/strong>; <strong data-start=\"661\" data-end=\"676\">Type B \/ B+<\/strong> variant; <strong data-start=\"686\" data-end=\"692\">EV<\/strong> variants (<strong data-start=\"703\" data-end=\"716\">VRL22A EV<\/strong>, <strong data-start=\"718\" data-end=\"731\">VRL22F EV<\/strong>) with <strong data-start=\"738\" data-end=\"749\">6 mA DC<\/strong> detection.<\/p>\n<\/li>\n<li data-start=\"763\" data-end=\"913\">\n<p data-start=\"765\" data-end=\"913\">Standards &amp; certifications: <strong data-start=\"793\" data-end=\"811\">IEC\/EN 61009-1<\/strong>, <strong data-start=\"813\" data-end=\"829\">IEC\/EN 62423<\/strong> (Type B), <strong data-start=\"840\" data-end=\"853\">IEC 62955<\/strong> (EV RDC-PD), <strong data-start=\"867\" data-end=\"883\">VDE 0664-400<\/strong>; <strong data-start=\"885\" data-end=\"912\">SEMKO \/ UKCA \/ CE \/ SAA<\/strong>.<\/p>\n<\/li>\n<\/ul>","protected":false},"featured_media":1855,"comment_status":"open","ping_status":"closed","template":"","meta":[],"product_brand":[],"product_cat":[36],"product_tag":[],"class_list":{"0":"post-1561","1":"product","2":"type-product","3":"status-publish","4":"has-post-thumbnail","6":"product_cat-rcbo","8":"first","9":"instock","10":"shipping-taxable","11":"product-type-simple"},"_links":{"self":[{"href":"https:\/\/cnkuangya.com\/ar\/wp-json\/wp\/v2\/product\/1561","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/cnkuangya.com\/ar\/wp-json\/wp\/v2\/product"}],"about":[{"href":"https:\/\/cnkuangya.com\/ar\/wp-json\/wp\/v2\/types\/product"}],"replies":[{"embeddable":true,"href":"https:\/\/cnkuangya.com\/ar\/wp-json\/wp\/v2\/comments?post=1561"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/cnkuangya.com\/ar\/wp-json\/wp\/v2\/media\/1855"}],"wp:attachment":[{"href":"https:\/\/cnkuangya.com\/ar\/wp-json\/wp\/v2\/media?parent=1561"}],"wp:term":[{"taxonomy":"product_brand","embeddable":true,"href":"https:\/\/cnkuangya.com\/ar\/wp-json\/wp\/v2\/product_brand?post=1561"},{"taxonomy":"product_cat","embeddable":true,"href":"https:\/\/cnkuangya.com\/ar\/wp-json\/wp\/v2\/product_cat?post=1561"},{"taxonomy":"product_tag","embeddable":true,"href":"https:\/\/cnkuangya.com\/ar\/wp-json\/wp\/v2\/product_tag?post=1561"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}