{"id":2295,"date":"2025-12-18T00:41:40","date_gmt":"2025-12-18T00:41:40","guid":{"rendered":"https:\/\/cnkuangya.com\/?p=2295"},"modified":"2026-04-24T15:52:44","modified_gmt":"2026-04-24T07:52:44","slug":"dc-protection-wiring-mistakes","status":"publish","type":"post","link":"https:\/\/cnkuangya.com\/ar\/blog\/dc-protection-wiring-mistakes\/","title":{"rendered":"10 Common DC Protection Wiring Mistakes (And How to Avoid Them)"},"content":{"rendered":"\n<p>The call came in on a Monday morning\u2014the kind of call every electrical engineer dreads. A 100kW commercial rooftop system, commissioned just six months prior, was dead. The site manager described a &#8220;burning plastic smell&#8221; wafting from the main DC combiner box. When I arrived at the site, the cause wasn&#8217;t a defective component or a lightning strike. The inside of the combiner box was a charred, melted mess because a high-end DC circuit breaker had its line and load connections reversed.<\/p>\n\n\n\n<p>In my 15+ years as a senior application engineer in the electrical automation industry, I have analyzed countless system failures. The hard truth is that most catastrophic DC-side issues aren&#8217;t caused by cheap equipment; they are caused by&nbsp;<strong>dc protection wiring mistakes<\/strong>.<\/p>\n\n\n\n<p>Unlike AC (Alternating Current), which is forgiving thanks to its zero-crossing nature, DC (Direct Current) is relentless. It is a continuous flow of energy that, if mishandled, becomes a fire hazard in milliseconds. This guide is born from those hard-won field lessons. We will walk through the top 10 mistakes I see in the field and provide the actionable engineering frameworks you need to avoid them.<\/p>\n\n\n\n<hr class=\"wp-block-separator has-alpha-channel-opacity\"\/>\n\n\n\n<h2 class=\"wp-block-heading\">Mistake 1: Reversed Polarity &amp; Ignoring DC Directionality<\/h2>\n\n\n\n<p>This is, without a doubt, the single most frequent and dangerous error in DC installations.<\/p>\n\n\n\n<p><strong>The Problem:<\/strong><br>In AC circuits, the current changes direction 100 or 120 times a second. In DC circuits, current flows one way. Many high-performance DC circuit breakers are &#8220;polarized.&#8221; They contain permanent magnets designed to push the electrical arc&nbsp;<em>into<\/em>&nbsp;the arc-extinguishing chute when the breaker trips.<\/p>\n\n\n\n<p>If you wire these backward (swapping Line and Load), the internal magnetic field will pull the arc&nbsp;<em>away<\/em>&nbsp;from the chute and into the delicate mechanical components of the breaker. Instead of extinguishing, the arc sustains, melting the breaker and potentially igniting the enclosure.<\/p>\n\n\n\n<p><strong>The Solution:<\/strong><\/p>\n\n\n\n<ol class=\"wp-block-list\">\n<li><strong>Check for Polarity Markings:<\/strong>\u00a0Look for\u00a0<code>+<\/code>\u00a0and\u00a0<code>-<\/code>\u00a0symbols or\u00a0<code>LINE<\/code>\u00a0and\u00a0<code>LOAD<\/code>\u00a0markings on the device.<\/li>\n\n\n\n<li><strong>Verify Flow Direction:<\/strong>\u00a0Remember that in a source circuit (like solar), current flows\u00a0<em>from<\/em>\u00a0the panels\u00a0<em>to<\/em>\u00a0the inverter. In a battery circuit, current can flow both ways (charging and discharging).<\/li>\n\n\n\n<li><strong>Use Non-Polarized Breakers for Batteries:<\/strong>\u00a0If the current is bidirectional, you\u00a0<em>must<\/em>\u00a0use a non-polarized DC breaker or a polarized breaker specifically wired in a configuration (like a bridge) that handles bidirectional flow.<\/li>\n<\/ol>\n\n\n\n<p>![Image: Close-up of a DC circuit breaker clearly showing polarity (+\/-) and Line\/Load markings]<\/p>\n\n\n\n<p><strong>Key Takeaway: For polarized DC breakers, correct polarity isn&#8217;t a suggestion\u2014it&#8217;s a requirement for the physics of arc quenching to work. Always double-check with a multimeter before energizing.<\/strong><\/p>\n\n\n\n<hr class=\"wp-block-separator has-alpha-channel-opacity\"\/>\n\n\n\n<h2 class=\"wp-block-heading\">Mistake 2: Ignoring Torque Specifications<\/h2>\n\n\n\n<p>A secure connection is a safe connection. Unfortunately, the &#8220;good-n-tight&#8221; hand-tightening method is a recipe for thermal failure.<\/p>\n\n\n\n<p><strong>The Problem:<\/strong><\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li><strong>Under-Torquing:<\/strong>\u00a0Creates a high-resistance joint. As current flows, $I^2R$ losses generate heat. This heat causes the metal to expand and contract (thermal cycling), loosening the connection further until it melts or arcs.<\/li>\n\n\n\n<li><strong>Over-Torquing:<\/strong>\u00a0Cracks the breaker housing or shears the screw threads, rendering the connection mechanically unstable.<\/li>\n<\/ul>\n\n\n\n<p><strong>The Solution:<\/strong><br>Adopt a &#8220;Zero-Tolerance&#8221; policy for un-torqued connections. You must use a calibrated torque screwdriver.<\/p>\n\n\n\n<p><strong>Pro-Tip: The &#8220;Mark and Move&#8221; Method<\/strong><br>After applying the manufacturer-specified torque (usually printed on the side of the breaker in N\u00b7m or lb-in), apply a dot of &#8220;torque seal&#8221; or inspector&#8217;s lacquer across the screw and the housing. This provides visual proof the work was done and makes it easy to spot if a screw has vibrated loose during future inspections.<\/p>\n\n\n\n<p>![Image: A technician using a calibrated yellow torque screwdriver on a DC terminal, applying torque seal paint]<\/p>\n\n\n\n<hr class=\"wp-block-separator has-alpha-channel-opacity\"\/>\n\n\n\n<h2 class=\"wp-block-heading\">Mistake 3: Confusing AC and DC Protection Devices<\/h2>\n\n\n\n<p>Using an AC breaker in a DC circuit is like trying to stop a runaway freight train with bicycle brakes.<\/p>\n\n\n\n<p><strong>The Problem:<\/strong><br>AC power naturally crosses zero volts 100+ times per second. An AC breaker relies on this &#8220;zero-crossing&#8221; to extinguish the arc. DC has no zero-crossing. If you use an AC breaker on a 600V DC string, the breaker might open, but the arc will bridge the contacts, continuing to burn until the device is destroyed.<\/p>\n\n\n\n<p><strong>Table 1: AC vs. DC Circuit Breaker Specifications<\/strong><\/p>\n\n\n\n<figure class=\"wp-block-table\"><table class=\"has-fixed-layout\"><tbody><tr><th>Feature<\/th><th>Standard AC Circuit Breaker<\/th><th>DC-Rated Circuit Breaker<\/th><th>Why it Matters for DC Protection<\/th><\/tr><tr><td><strong>Arc Quenching<\/strong><\/td><td>Zero-Crossing Reliance<\/td><td>Magnetic Blowouts &amp; Arc Chutes<\/td><td>DC arcs are continuous; they must be physically stretched and cooled to stop.<\/td><\/tr><tr><td><strong>Contact Gap<\/strong><\/td><td>Smaller<\/td><td>Significantly Larger<\/td><td>Larger gaps are needed to break the DC arc.<\/td><\/tr><tr><td><strong>Polarization<\/strong><\/td><td>Non-Polarized<\/td><td>Often Polarized<\/td><td>Directional magnets guide the arc into the chute.<\/td><\/tr><tr><td><strong>Interrupt Rating<\/strong><\/td><td>Rated in AC Amps<\/td><td>Rated in DC Amps<\/td><td>AC ratings are&nbsp;<strong>invalid<\/strong>&nbsp;for DC applications.<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<p><strong>The Solution:<\/strong><br>Never rely on the physical fit of the breaker (e.g., DIN rail mount). Always verify the datasheet explicitly states the&nbsp;<strong>DC Voltage Rating<\/strong>&nbsp;and&nbsp;<strong>DC Interrupting Capacity<\/strong>.<\/p>\n\n\n\n<hr class=\"wp-block-separator has-alpha-channel-opacity\"\/>\n\n\n\n<h2 class=\"wp-block-heading\">Mistake 4: Conductor and Overcurrent Device Sizing Errors<\/h2>\n\n\n\n<p>Sizing DC protection isn&#8217;t just about matching the wire ampacity; it requires adhering to the &#8220;125% Rule&#8221; and accounting for continuous duty.<\/p>\n\n\n\n<p><strong>The Problem:<\/strong><br>NEC Article 690.8 requires that solar circuit currents be considered &#8220;continuous.&#8221; This means the conductors and Overcurrent Protection Devices (OCPD) must be sized at 125% of the calculated maximum circuit current. If you have a string with an Isc (Short Circuit Current) of 10A, you cannot use a 10A fuse. It will eventually fatigue and nuisance trip due to thermal stress.<\/p>\n\n\n\n<p><strong>The Solution:<\/strong><br>Follow this 3-Step Selection Method:<\/p>\n\n\n\n<ol class=\"wp-block-list\">\n<li><strong>Calculate Max Current:<\/strong>\u00a0$I_{max} = I_{sc} \\times 1.25$<\/li>\n\n\n\n<li><strong>Select OCPD:<\/strong>\u00a0Choose the next standard size\u00a0<em>above<\/em>\u00a0$I_{max}$.<\/li>\n\n\n\n<li><strong>Check Conductor:<\/strong>\u00a0Ensure the wire&#8217;s derated ampacity is greater than the OCPD rating.<\/li>\n<\/ol>\n\n\n\n<p><strong>Table 2: gPV Fuse Sizing Calculation Example<\/strong><\/p>\n\n\n\n<figure class=\"wp-block-table\"><table class=\"has-fixed-layout\"><tbody><tr><th>Parameter<\/th><th>Value<\/th><th>Calculation \/ Logic<\/th><\/tr><tr><td><strong>Module Isc<\/strong><\/td><td>12A<\/td><td>From Solar Panel Datasheet<\/td><\/tr><tr><td><strong>Safety Factor<\/strong><\/td><td>1.25<\/td><td>NEC Continuous Duty Requirement<\/td><\/tr><tr><td><strong>Min Fuse Rating<\/strong><\/td><td>15A<\/td><td>$12A \\times 1.25 = 15A$<\/td><\/tr><tr><td><strong>Ambient Temp Derating<\/strong><\/td><td>0.90<\/td><td>Assumes 50\u00b0C internal box temp<\/td><\/tr><tr><td><strong>Final Fuse Selection<\/strong><\/td><td><strong>20A<\/strong><\/td><td>A 15A fuse derated by 0.90 is only 13.5A (too close to Isc). Upsize to 20A to prevent nuisance blows.<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<hr class=\"wp-block-separator has-alpha-channel-opacity\"\/>\n\n\n\n<h2 class=\"wp-block-heading\">Mistake 5: Improper SPD Placement and Wiring<\/h2>\n\n\n\n<p>Surge Protective Devices (SPDs) are vital, but their effectiveness is dictated by physics, specifically inductance.<\/p>\n\n\n\n<p><strong>The Problem:<\/strong><br>Inductance in a wire resists changes in current. Lightning causes a massive, instantaneous change in current ($di\/dt$). According to the formula $V = L \\times (di\/dt)$, even a small length of wire ($L$) creates a massive voltage drop ($V$) during a surge. If your SPD leads are long and coiled, the voltage spike will bypass the SPD and go straight into your inverter, rendering the protection useless.<\/p>\n\n\n\n<p><strong>The Solution:<\/strong><br>Keep leads&nbsp;<strong>short and straight<\/strong>. Avoid sharp 90-degree bends.<\/p>\n\n\n\n<p><strong>Mermaid Diagram 1: Correct vs. Incorrect SPD Wiring<\/strong><\/p>\n\n\n\n<p><strong>Key Takeaway: Every centimeter of wire adds inductance. Connecting an SPD with 1 meter of wire effectively disconnects it during a fast-rise surge event.<\/strong><\/p>\n\n\n\n<hr class=\"wp-block-separator has-alpha-channel-opacity\"\/>\n\n\n\n<h2 class=\"wp-block-heading\">Mistake 6: Incorrect Cable Selection &amp; Management<\/h2>\n\n\n\n<p>Using standard building wire (THHN) on a rooftop is a ticking time bomb.<\/p>\n\n\n\n<p><strong>The Problem:<\/strong><br>DC cables on solar arrays are exposed to extreme UV radiation, temperature swings (freezing to baking), and moisture. Standard PVC insulation will crack and flake off after a few years of UV exposure, leading to dangerous ground faults and potential arc flashes.<\/p>\n\n\n\n<p><strong>The Solution:<\/strong><\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li><strong>Use PV Wire:<\/strong>\u00a0Specifically rated for sunlight resistance (UL 4703) and often rated for 1000V or 2000V DC. It has thicker, cross-linked insulation.<\/li>\n\n\n\n<li><strong>Manage Your Loops:<\/strong>\u00a0Secure cables with UV-rated clips or stainless steel ties. Loose cables rub against abrasive racking (wind flutter), wearing through the insulation.<\/li>\n<\/ul>\n\n\n\n<p>![Image: A professional solar installation showing neat cable management, with wires secured to the racking using metal clips, not drooping]<\/p>\n\n\n\n<hr class=\"wp-block-separator has-alpha-channel-opacity\"\/>\n\n\n\n<h2 class=\"wp-block-heading\">Mistake 7: Misinterpreting NEC Disconnect &amp; Labeling Rules<\/h2>\n\n\n\n<p>Code compliance regarding disconnects is primarily about the safety of first responders.<\/p>\n\n\n\n<p><strong>The Problem:<\/strong><br>NEC 690.13 requires a &#8220;readily accessible&#8221; disconnect. Hiding a disconnect inside a locked combiner box that requires a screwdriver to open, or placing it on a roof that requires a portable ladder to access, violates this rule. If a firefighter cannot find the switch or cannot reach it safely, they cannot de-energize the system.<\/p>\n\n\n\n<p><strong>The Solution:<\/strong><\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li><strong>Location:<\/strong>\u00a0Install the main DC disconnect at ground level or a permanently accessible location.<\/li>\n\n\n\n<li><strong>Labeling:<\/strong>\u00a0Every disconnect must be clearly labeled: &#8220;PHOTOVOLTAIC DC DISCONNECT.&#8221; If the line and load terminals are both energized in the open position (common in solar), a label warning &#8220;WARNING: ELECTRIC SHOCK HAZARD. TERMINALS ON THE LINE AND LOAD SIDES MAY BE ENERGIZED IN THE OPEN POSITION&#8221; is required.<\/li>\n<\/ul>\n\n\n\n<hr class=\"wp-block-separator has-alpha-channel-opacity\"\/>\n\n\n\n<h2 class=\"wp-block-heading\">Mistake 8: Temperature Derating Oversights<\/h2>\n\n\n\n<p>A fuse rated for 20A at 25\u00b0C does not hold 20A at 60\u00b0C.<\/p>\n\n\n\n<p><strong>The Problem:<\/strong><br>Combiner boxes on rooftops turn into ovens. Internal temperatures can easily exceed 60\u00b0C (140\u00b0F). As temperature rises, the metallic element inside a fuse or thermal-magnetic breaker softens, causing it to trip at a lower current than its rating. This leads to &#8220;phantom tripping&#8221; where the system shuts down on hot days exactly when solar production should be highest.<\/p>\n\n\n\n<p><strong>Table 3: Typical Cable Ampacity Derating Factors (90\u00b0C Rated Wire)<\/strong><\/p>\n\n\n\n<figure class=\"wp-block-table\"><table class=\"has-fixed-layout\"><tbody><tr><th>Ambient Temp (\u00b0C)<\/th><th>Ambient Temp (\u00b0F)<\/th><th>Correction Factor<\/th><th>Impact on 40A Cable<\/th><\/tr><tr><td>36-40<\/td><td>97-104<\/td><td>0.91<\/td><td>36.4A<\/td><\/tr><tr><td>46-50<\/td><td>114-122<\/td><td>0.82<\/td><td>32.8A<\/td><\/tr><tr><td><strong>56-60<\/strong><\/td><td><strong>132-140<\/strong><\/td><td><strong>0.71<\/strong><\/td><td><strong>28.4A<\/strong><\/td><\/tr><tr><td>66-70<\/td><td>151-158<\/td><td>0.58<\/td><td>23.2A<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<p><strong>The Solution:<\/strong><br>Always apply temperature correction factors from the manufacturer&#8217;s datasheet or NEC Table 310.15(B)(2)(a). If your box is in the sun, assume an internal temp of at least ambient + 15\u00b0C.<\/p>\n\n\n\n<hr class=\"wp-block-separator has-alpha-channel-opacity\"\/>\n\n\n\n<h2 class=\"wp-block-heading\">Mistake 9: Poor Coordination Between Protection Devices<\/h2>\n\n\n\n<p>When a fault occurs, only the device closest to the fault should trip. This is called &#8220;selectivity.&#8221;<\/p>\n\n\n\n<p><strong>The Problem:<\/strong><br>If you have a 15A fuse at the string level and a 20A breaker at the combiner output, a fault on one string might trip the main breaker instead of just blowing the string fuse. This knocks out the entire array instead of just one string.<\/p>\n\n\n\n<p><strong>The Solution:<\/strong><br>Ensure there is a sufficient ratio between upstream and downstream devices. Use Time-Current Curves (TCC) to verify that the downstream device clears the fault before the upstream device unlatches.<\/p>\n\n\n\n<p><strong>Table 4: Protection Methods for Different Fault Conditions<\/strong><\/p>\n\n\n\n<figure class=\"wp-block-table\"><table class=\"has-fixed-layout\"><tbody><tr><th>Fault Type<\/th><th>Characteristics<\/th><th>Recommended Device<\/th><th>Response Time<\/th><\/tr><tr><td><strong>Overload<\/strong><\/td><td>101-200% current (slow rise)<\/td><td>Thermal-Magnetic DC Breaker<\/td><td>Seconds to Minutes<\/td><\/tr><tr><td><strong>Short Circuit<\/strong><\/td><td>10-20x current (instant spike)<\/td><td>gPV Fuse or Magnetic Breaker<\/td><td>&lt;10ms<\/td><\/tr><tr><td><strong>Ground Fault<\/strong><\/td><td>Current leaking to earth<\/td><td>GFDI \/ RCD<\/td><td>&lt;100ms<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<hr class=\"wp-block-separator has-alpha-channel-opacity\"\/>\n\n\n\n<h2 class=\"wp-block-heading\">Mistake 10: Neglecting Arc Flash Hazards<\/h2>\n\n\n\n<p>Just because it&#8217;s DC doesn&#8217;t mean it won&#8217;t explode.<\/p>\n\n\n\n<p><strong>The Problem:<\/strong><br>DC arcs are hotter and sustain longer than AC arcs. An arc flash in a large battery bank or a 1500V solar combiner can release temperatures exceeding 20,000\u00b0C. Engineers often calculate Arc Flash boundaries for the AC switchgear but ignore the DC side.<\/p>\n\n\n\n<p><strong>The Solution:<\/strong><\/p>\n\n\n\n<ul class=\"wp-block-list\">\n<li><strong>Compliance:<\/strong>\u00a0Follow NFPA 70E and IEEE 1584 guidelines for DC calculations.<\/li>\n\n\n\n<li><strong>PPE:<\/strong>\u00a0Wear appropriate Personal Protective Equipment (PPE) when working on energized DC gear.<\/li>\n\n\n\n<li><strong>Design:<\/strong>\u00a0Use &#8220;Touch-Safe&#8221; fuse holders and dead-front panels to prevent accidental contact that could initiate an arc.<\/li>\n<\/ul>\n\n\n\n<p>![Image: Technician wearing appropriate Arc Flash PPE working on a commercial DC combiner box]<\/p>\n\n\n\n<hr class=\"wp-block-separator has-alpha-channel-opacity\"\/>\n\n\n\n<h2 class=\"wp-block-heading\">Standards Comparison: Ensuring Global Compliance<\/h2>\n\n\n\n<p>To ensure your system is safe and insurable, you must use components certified to the correct standard. Using a UL component in a European IEC project (or vice versa) can sometimes lead to inspection failures if not properly cross-referenced.<\/p>\n\n\n\n<p><strong>Table 5: IEC vs. UL Certification Standards<\/strong><\/p>\n\n\n\n<figure class=\"wp-block-table\"><table class=\"has-fixed-layout\"><tbody><tr><th>Specification<\/th><th>IEC 60269-6 (Global)<\/th><th>UL 2579 (North America)<\/th><\/tr><tr><td><strong>Scope<\/strong><\/td><td>PV specific fuses (gPV)<\/td><td>Fuses for Photovoltaic Systems<\/td><\/tr><tr><td><strong>Time Constant<\/strong><\/td><td>5ms to 15ms<\/td><td>5ms to 12ms<\/td><\/tr><tr><td><strong>Voltage Ratings<\/strong><\/td><td>600V, 1000V, 1500V DC<\/td><td>300V, 600V, 1000V, 1500V DC<\/td><\/tr><tr><td><strong>Breaking Capacity<\/strong><\/td><td>10kA, 20kA, 30kA<\/td><td>10kA, 15kA, 20kA, 30kA<\/td><\/tr><tr><td><strong>Testing Approach<\/strong><\/td><td>Performance parameters<\/td><td>System-level safety &amp; NEC alignment<\/td><\/tr><\/tbody><\/table><\/figure>\n\n\n\n<hr class=\"wp-block-separator has-alpha-channel-opacity\"\/>\n\n\n\n<h2 class=\"wp-block-heading\">Frequently Asked Questions (FAQ)<\/h2>\n\n\n\n<p><strong>Q: Can I use a standard AC fuse in my <a href=\"https:\/\/cnkuangya.com\/pv-combiner-box\/\">solar combiner box<\/a>?<\/strong><br><strong>A:<\/strong>\u00a0Absolutely not. AC fuses are not designed to quench a DC arc. Using an AC fuse poses a severe fire risk. Always look for the &#8220;gPV&#8221; rating or UL 2579 listing.<\/p>\n\n\n\n<p><strong>Q: Why do my DC breakers keep tripping on hot afternoons?<\/strong><br><strong>A:<\/strong>&nbsp;This is likely due to thermal derating. If the ambient temperature inside the enclosure is high, the thermal element in the breaker expands, lowering its trip threshold. Check your sizing calculations and apply the correct temperature correction factor.<\/p>\n\n\n\n<p><strong>Q: Do I really need a torque screwdriver? My hand feels calibrated.<\/strong><br><strong>A:<\/strong>&nbsp;Yes, you need one. Human perception of torque is notoriously inaccurate. Under-torquing leads to heat and fire; over-torquing leads to mechanical breakage. It is a small investment for system safety.<\/p>\n\n\n\n<p><strong>Q: What is the difference between a load-break and non-load-break disconnect?<\/strong><br><strong>A:<\/strong>&nbsp;A load-break disconnect is designed to safely interrupt the full electrical current. A non-load-break disconnect (isolator) should only be opened after the current has been stopped (e.g., by the inverter). Opening a non-load-break switch under load will draw a dangerous arc.<\/p>\n\n\n\n<hr class=\"wp-block-separator has-alpha-channel-opacity\"\/>\n\n\n\n<h2 class=\"wp-block-heading\">Final Thoughts<\/h2>\n\n\n\n<p>Wiring DC protection systems correctly is about respecting the physics of direct current. It requires more than just connecting wires; it demands a deep understanding of polarity, temperature, inductance, and arc behavior.<\/p>\n\n\n\n<p>By avoiding these 10 common mistakes, you aren&#8217;t just ticking boxes on an inspection form; you are ensuring the longevity of your investment and the safety of the people who maintain it.<\/p>\n","protected":false},"excerpt":{"rendered":"<p>The call came in on a Monday morning\u2014the kind of call every electrical engineer dreads. A 100kW commercial rooftop system, commissioned just six months prior, was dead. The site manager described a &#8220;burning plastic smell&#8221; wafting from the main DC combiner box. When I arrived at the site, the cause wasn&#8217;t a defective component or [&hellip;]<\/p>\n","protected":false},"author":4,"featured_media":2298,"comment_status":"open","ping_status":"open","sticky":false,"template":"","format":"standard","meta":{"footnotes":""},"categories":[45],"tags":[],"class_list":["post-2295","post","type-post","status-publish","format-standard","has-post-thumbnail","hentry","category-dc-protection-safety"],"blocksy_meta":[],"_links":{"self":[{"href":"https:\/\/cnkuangya.com\/ar\/wp-json\/wp\/v2\/posts\/2295","targetHints":{"allow":["GET"]}}],"collection":[{"href":"https:\/\/cnkuangya.com\/ar\/wp-json\/wp\/v2\/posts"}],"about":[{"href":"https:\/\/cnkuangya.com\/ar\/wp-json\/wp\/v2\/types\/post"}],"author":[{"embeddable":true,"href":"https:\/\/cnkuangya.com\/ar\/wp-json\/wp\/v2\/users\/4"}],"replies":[{"embeddable":true,"href":"https:\/\/cnkuangya.com\/ar\/wp-json\/wp\/v2\/comments?post=2295"}],"version-history":[{"count":1,"href":"https:\/\/cnkuangya.com\/ar\/wp-json\/wp\/v2\/posts\/2295\/revisions"}],"predecessor-version":[{"id":2296,"href":"https:\/\/cnkuangya.com\/ar\/wp-json\/wp\/v2\/posts\/2295\/revisions\/2296"}],"wp:featuredmedia":[{"embeddable":true,"href":"https:\/\/cnkuangya.com\/ar\/wp-json\/wp\/v2\/media\/2298"}],"wp:attachment":[{"href":"https:\/\/cnkuangya.com\/ar\/wp-json\/wp\/v2\/media?parent=2295"}],"wp:term":[{"taxonomy":"category","embeddable":true,"href":"https:\/\/cnkuangya.com\/ar\/wp-json\/wp\/v2\/categories?post=2295"},{"taxonomy":"post_tag","embeddable":true,"href":"https:\/\/cnkuangya.com\/ar\/wp-json\/wp\/v2\/tags?post=2295"}],"curies":[{"name":"wp","href":"https:\/\/api.w.org\/{rel}","templated":true}]}}