RCCB Rating Chart: 40A vs 63A and 30mA vs 100mA Explained

RCCB rating chart: compare 40A vs 63A current ratings and 30mA vs 100mA residual current settings. Learn selection and overcurrent protection checks.

Quick answer: On an RCCB, 40 A or 63 A is the rated current (In) that its contacts are designed to carry under specified conditions. 30 mA or 100 mA is the rated residual operating current (IΔn). These values describe different functions. An RCCB detects residual current; it does not provide integral overload or short-circuit protection. Select it together with a suitable upstream or downstream overcurrent protective device, the circuit design and the exact manufacturer’s instructions.

KUANGYA VKL001 RCCB with rated current and residual-current markings
Check both the current rating (A) and residual-current sensitivity (mA) on the exact RCCB model.

What do the numbers on an RCCB mean?

MarkingMeaningWhat it does not mean
40 A or 63 A (In)Rated current-carrying capacity of the RCCBThe current at which it trips for overload
30 mA or 100 mA (IΔn)Rated residual operating currentThe normal load current of the circuit
Type AC, A, F or BResidual-current waveform capabilityOvercurrent trip curve B or C
2P or 4PNumber of polesProof that the device suits every earthing system
Conditional short-circuit ratingRating under stated coordination with an upstream protective deviceStandalone short-circuit interruption by the RCCB

For example, a 63 A, 30 mA Type A RCCB is rated to carry 63 A under its specified conditions and to respond to the residual-current waveforms covered by Type A at its declared sensitivity. It is not a 63 A miniature circuit breaker.

RCCB 40A vs 63A: which should you choose?

The 63 A version has a higher current-carrying rating. It does not provide stronger electric-shock protection when both devices have the same 30 mA sensitivity and the same residual-current type. It also does not allow an undersized cable or an incorrectly selected upstream breaker.

Check the maximum sustained current through the RCCB, the rating and characteristic of the protective fuse or breaker, cable ampacity, enclosure temperature, grouping, busbar and terminal ratings, and the manufacturer’s coordination data. The sum of all downstream breaker nameplate ratings is not automatically the actual simultaneous load; equally, assuming that loads never run together can understate the thermal duty.

Practical example: If a distribution board can carry more than 40 A through its RCCB under normal operation, a 40 A device should not be chosen simply because its leakage sensitivity is 30 mA. A 63 A device may be appropriate, but its upstream overcurrent protection and conductor sizing still need verification. Conversely, installing a 63 A RCCB where the circuit is limited to a lower current does not make its residual-current protection less sensitive.

Eaton’s RCD application guide explains that a fuse or breaker can carry more than its nameplate current before tripping. For that reason, RCCB contact protection must follow the particular manufacturer’s coordination table rather than a universal “same ampere rating” rule.

30mA vs 100mA vs 300mA: sensitivity is a separate decision

RCCB markingTypical design roleImportant check
30 mAAdditional protection against electric shock where requiredApplicable wiring rules, load leakage and RCD type
100 mAApplication-specific or upstream residual-current protectionEarthing arrangement and coordination with downstream devices
300 mACertain upstream or fire-risk-related applicationsLocal rules, selectivity and equipment instructions

A 100 mA or 300 mA RCCB is not a drop-in substitute for a required 30 mA device on a final circuit. Whether a delayed or selective upstream RCD is suitable depends on the installation and tested coordination. The residual-current type matters as well: electronic loads can produce waveforms that a Type AC device is not designed to detect. Follow the equipment manual and local rules when choosing Type A, F or B.

Does an RCCB trip on overload or short circuit?

No. An RCCB without integral overcurrent protection monitors the imbalance between current leaving and returning through its protected conductors. A line-to-neutral overload can occur without the residual current needed to operate the RCCB. A separate fuse or circuit breaker must provide the required overcurrent and short-circuit protection. If one device must combine both functions, review an RCBO instead.

CHINT’s NL1 product documentation explicitly describes an RCCB as residual-current protection without overcurrent protection. The declared conditional short-circuit rating is valid only with its specified upstream short-circuit protective device.

Five checks before ordering an RCCB

  1. System: Confirm voltage, frequency, phase arrangement and whether 2P or 4P is required.
  2. Current: Determine the current the RCCB must continuously carry, including simultaneous loading and applicable derating.
  3. Residual protection: Choose IΔn and Type AC/A/F/B from the protection objective, connected equipment and local rules.
  4. Overcurrent coordination: Check the fuse or breaker that protects the RCCB and the available fault current against the exact device documentation.
  5. Installation: Verify conductor size, terminal and busbar compatibility, ambient temperature and a testing plan.

For an example of available ratings, KUANGYA’s VKL001 RCCB lists 2P and 4P options, 40 A and 63 A among its current ratings, and 30 mA, 100 mA and 300 mA sensitivities. Confirm the exact variant and certificates before specifying it. Our RCCB vs RCBO comparison explains when an integrated overcurrent device may be preferable.

Frequently asked questions

Will a 40A RCCB trip when the load reaches 41A?

No. The 40 A label is a rated current-carrying value, not an overload trip setting. The separate overcurrent protective device must be selected to protect the RCCB and conductors.

Is a 63A 30mA RCCB safer than a 40A 30mA RCCB?

Both have the same declared residual-current sensitivity if they are otherwise the same type. The 63 A version has a higher rated current-carrying capacity. Safety depends on correct selection and coordination for the whole circuit.

Can I replace a 30mA RCCB with a 100mA model to stop nuisance tripping?

Do not change sensitivity merely to hide repeated trips. First investigate leakage, moisture, wiring and load characteristics. A circuit that requires 30 mA additional protection must retain a compliant protective arrangement.

Selection support

Send KUANGYA the supply voltage, phases, earthing arrangement, expected load current, prospective fault current, upstream protective device, desired IΔn, residual-current type and destination market. We can then identify a suitable RCCB variant for engineering review. Contact KUANGYA.

elaine
elaine

Head of Marketing at Kuangya, focused on the global promotion of electrical protection and power distribution solutions.● Core Areas: Brand building in the PV, energy storage, and industrial power markets.
● Professional Products: Fuses, Surge Protective Devices (SPD), Miniature Circuit Breakers (MCB), and transfer switches.
● Value Proposition: Serving the global renewable energy market with "Safety, Reliability, and Innovation" as our cornerstones.Welcome to connect and collaborate to jointly advance the progress of intelligent power distribution technology.

Articles: 181