RCCB VKL11F — Residual Current Circuit Breaker

  • Kuangya VKL11F type f rccb for mixed-frequency residual-current protection in single- and three-phase systems

  • 2P/4P, In 16–100 A; IΔn 10/30/100/300 mA; Ue 240 V (2P) / 415 V (4P); Ui 500 V; 50/60 Hz

  • Uimp 4/6 kV; Inc = IΔc 6/10 kA (with upstream SCPD); IP20 terminals; DIN-rail EN 60715

Get A Quotation

Category:

Overview

The VKL11F type f rccb detects earth leakage including mixed-frequency components that commonly
occur with inverters, VFD-driven motors, and UPS equipment. It disconnects the circuit when residual current
exceeds the set threshold to protect people and installations against electric shock and fire hazards.
Available as 2P (single-phase) and 4P (three-phase).

Key Features

  • Poles: 2P / 4P
  • Rated current (In): 16, 25, 32, 40, 63, 80, 100 A
  • Rated sensitivity (IΔn): 10 / 30 / 100 / 300 mA
  • Rated voltage (Ue): 240 V~ (2P) / 415 V~ (4P)
  • Insulation voltage (Ui): 500 V   |   Frequency: 50/60 Hz
  • Residual making & breaking (IΔm): 500 / 630 / 800 / 1000 A (per In group)
  • Conditional short-circuit current: Inc = IΔc 6 kA / 10 kA (with upstream SCPD)
  • Impulse withstand (Uimp): 4 kV / 6 kV
  • Dielectric test voltage: 2.5 kV for 1 min (power frequency)
  • Tripping behavior: Instantaneous; Short time delay (10–300 ms); Selective S (150–500 ms)
  • Break time under IΔn (Normal): ≤ 100 ms
  • Terminal protection degree: IP20
  • Endurance: ≥ 20,000 mechanical / ≥ 2,000 electrical operations
  • Mounting: DIN rail EN 60715 (35 mm), fast clip

Technical Data

ModelVKL11F
StandardIEC/EN 61008-1
Poles2P, 4P
Rated current (In)16A, 25A, 32A, 40A, 63A, 80A, 100A
Rated sensitivity (IΔn)10 mA, 30 mA, 100 mA, 300 mA
Rated voltage (Ue)2P: 240 V~; 4P: 415 V~
Insulation voltage (Ui)500 V
Rated frequency50/60 Hz
Residual making & breaking (IΔm)500 A (In 16–40 A); 630 A (In 63 A); 800 A (In 80 A); 1000 A (In 100 A)
Conditional short-circuit current (Inc = IΔc)6000 A, 10000 A (with upstream SCPD)
Impulse withstand (Uimp)4 kV / 6 kV
Dielectric test voltage2.5 kV, 1 min
Tripping classesInstantaneous / Short time delay (10–300 ms) / Selective S (150–500 ms)
Break time under IΔn≤ 100 ms (Normal type)
Pollution degree2
Electrical life≥ 2000 operations
Mechanical life≥ 20000 operations
Terminal protection degreeIP20
Ambient temperature−25 °C to +55 °C (daily average ≤ 35 °C)
Storage temperature−40 °C to +70 °C
Terminal connectionCable / Pin-type busbar
Terminal size (cable)25–35 mm²; 18–3 / 18–2 AWG
Terminal size (busbar)10/16 mm²; 18–8 / 18–5 AWG
Tightening torque2.5 N·m (≈ 22 in-lbs)
MountingDIN rail EN 60715 (35 mm)
ConnectionTop and bottom
Waveform classType F (mixed-frequency residual currents)

Applications

  • Inverter/UPS outputs, VFD-driven motors, appliances with mixed-frequency leakage
  • Residential, commercial, and light-industrial panels requiring type f rccb protection