Address
304 North Cardinal
St. Dorchester Center, MA 02124
Work Hours
Monday to Friday: 7AM - 7PM
Weekend: 10AM - 5PM
Address
304 North Cardinal
St. Dorchester Center, MA 02124
Work Hours
Monday to Friday: 7AM - 7PM
Weekend: 10AM - 5PM
Four-pole surge protection device for electrical panel designed for 230/400 V AC systems.
Withstands impulse current Iimp 25 kA (10/350 μs) per pole; In 25 kA; Imax 100 kA.
Pluggable cartridge with thermal disconnector, visual indicator, and optional RC signaling
Parameter | Value |
---|---|
Product Code | KYSPD-25T1-4P |
Category | Surge Protection Device for Electrical Panel (Type 1 / Class I) |
Nominal System Voltage (Uo/Un) | 230 / 400 V AC |
Max. Continuous Operating Voltage (Uc) | 320 / 385 / 440 V AC |
Nominal Discharge Current (In, 8/20 μs) | 25 kA |
Max. Discharge Current (Imax, 8/20 μs) | 100 kA |
Impulse Discharge Current (Iimp, 10/350 μs) | 25 kA per pole |
Voltage Protection Level (Up) | ~1.6–2.0 kV |
Response Time | < 25 ns |
Short-Circuit Current Rating (ISCCR) | 50 kA |
Backup Fuse (max) | 315 A gL/gG |
Operating Temperature | -40 °C … +70 °C |
Mounting | 35 mm DIN rail (EN 60715) |
Enclosure | Thermoplastic, UL94 V-0 |
Protection Degree | IP20 (built-in) |
Remote Signaling | Optional RC contacts |
Standards | IEC 61643-11 / EN 61643-11 |
This surge protection device for electrical panel is suitable for TN-S, TN-C, and TT systems, offering reliable lightning protection in demanding environments.
It should be installed at the service entrance or electrical panel as the first-stage surge protection device for electrical panel.
This surge protection device for electrical panel can handle Iimp 25 kA per pole (10/350 μs).
Yes, it is suitable for TN-S, TN-C, and TT systems.
Yes, the pluggable module allows quick replacement for maintenance.
Optional RC contacts provide remote status indication for this surge protection device for electrical panel.
IEC/EN 61643-11 for surge protective devices.
Reviews